2

Installation

Greenheck Model ESRMD & ERD fans are thoroughly inspected and test run at the factory, however
damage may occur during handling and shipping. Consequently, it is important that the fan be carefully
inspected for visible and concealed damage before installation. Report any damaged or missing items to
the shipper immediately.

Follow the installation sequence shown below. Attach the plenum and hood to the roof curb using a
suitable fastener in each of the prepunched mounting holes. Care must be taken not to bend or distort
the plenum and fan components during installation.

Electrical Connections

Before electrical connections are made, the supply voltage, phase and ampere capacity must be
checked for compatibility with the fan motor. In addition, the supply wiring must be properly fused and
conform to local and national electrical codes.

If fan is to be wired to a control center, which is available through Greenheck, the control center wiring
instructions must be followed.

Pre-Starting Checks

Check all fasteners and set screws for tightness. The propeller should rotate freely and not rub on the fan
panel. The unit was aligned and test run at the factory prior to shipment, however movement of various
components may occur during shipment. Proper propeller rotation should be determined by momentarily
energizing the fan in the exhaust mode. If the rotation in the exhaust mode is for supply the motor wiring
between the fan and the controls should be changed. For 3 phase units, simply interchange any two of
the three electrical supply leads. Single phase units should not rotate the wrong direction, since the fan
has been pre-run at the factory.

Guards

Guards are required to protect the fan and nearby personnel. If guards are not ordered with the fan, they
must be supplied by the installer. When ordered with the fan, the guard is attached to the bottom of the
double venturi panel.

Damper Plenum Linkage Adjustments

Plenum dampers should open to 45

o

from closed position.  Consult factory before adjusting damper

linkages.

Hood

Mounting 
Channels

Lifting Lugs

Roof
Curb

Plenum

Fig. 1

Fig. 2

Installation Sequence

1. The roof curb is mounted and 

secured over the roof opening to
the roof structurals.

2. The plenum (factory assembled) 

is lowered through the curb and 
roof opening until its mounting 
channels rest on the roof curb. 
Lifting Lugs are provided. (Fig. 1)

3. The hood is lowered onto the 

curb/plenum assembly. (Fig. 1)

4. The hood and plenum are 

secured to the roof curb. (Fig. 2)

Summary of Contents for ERD

Page 1: ...81 2 29x29 27w x 26h 21 20 341 2 30 46 38 63 35x35 33w x 30h 27 20 401 2 36 52 44 715 8 41x41 39w x 38h 33 22 461 2 42 58 50 753 4 47x47 44w x 42h 38 36 521 2 48 64 56 825 8 53x53 50w x 48h 44 36 581 2 54 70 62 91 59x59 56w x 54h 50 36 641 2 Non Filtered Hood Filtered Hood Upblast Hood Approximate Unit Weights Size ESRMD Hood Size ESRMDF Hood Size ERD Hood Size ESRDM ESRMDF ERD F G H F G H F G H A...

Page 2: ...d and test run at the factory prior to shipment however movement of various components may occur during shipment Proper propeller rotation should be determined by momentarily energizing the fan in the exhaust mode If the rotation in the exhaust mode is for supply the motor wiring between the fan and the controls should be changed For 3 phase units simply interchange any two of the three electrical...

Page 3: ...ed directly with water steam or solvents 3 Filter Maintenance Model ESRMDF Aluminum mesh filters should be cleaned on a regular basis for optimum fan efficiency The frequency of cleaning depends upon the cleanliness of the incoming air To remove filters in fan sizes 24 30 first remove the hood This is accomplished by removing the two fasteners on one side of the hood and loosening the other two fa...

Page 4: ...0 SCHOFIELD WISCONSIN 54476 0410 PH 715 359 6171 Warranty Greenheck warrants this equipment free from defects in material and workmanship for a period for one year from the purchase date Any units or parts which prove to be defective during the warranty period will be replaced at our option when returned to our factory transportation prepaid Motors are warranted by the motor manufacturer for a per...

Reviews: