12 in.

24 in. o.c.

Maximum

Floor Runner

2 in.

Ceiling Runner

2 Panhead

Screws

24 in. o.c.

Maximum

(metal studs)

24 in. o.c.

Maximum

(metal studs)

16 in. o.c.

Maximum

(wood studs)

16 in. o.c.

Maximum

(wood studs)

2 in.

Fig. 9

8. BREAKAWAY CONNECTIONS
Traditional Breakaway Style Transverse Joints

Transverse joints illustrated at right have always been 
approved as breakaway connections. SMACNA testing 
has also approved the following variations as breakaway 
connections.
 

•  The breakaway connections shown to the right  

(Fig. 11) can be applied with maximum of two #10 
(19mm) sheet metal screws on each side and on the 
bottom located in the center of the slip pocket and 
penetrating both sides of the slip pocket. 

 

•  Transverse joints illustrated 

can be applied as top and 
bottom joints with Drive Slip 
- side joints in duct heights 
up to 20 inches (508mm) 
see Fig. 10.

Round and Oval Duct Breakaway Connections

Round or flat oval ducts connected to Type R or O damper 
collars shall be attached with #10 (19mm) sheet metal 
screws as follows:
 

•  Ducts to 22 in. (558mm) wide or diameter and smaller 

shall have three screws.

 

•  Ducts larger than 22 in. wide (558mm) or diameter 

up to and including 36 in.  (914mm) wide or diameter 
shall have five screws.

NOTE:

  All breakaway connections described may have duct 

sealant applied, PA2084T duct sealant adhesive 
manufactured by Precision, DP1010 water base duct 
sealant manufactured by Design Polymetrics, or Grey 
Pookie in accordance with SMACNA recommendations.

Manufactured Flanged System Breakaway 
Connections (Fig. 12)

Flanged connection systems manufactured by Ductmate, 
Ward, and Nexus are approved as breakaway connections 
when installed as illustrated (Fig. 12). 

%SPJOU

Fig. 10

1MBJOi4w 4MJQ)FNNFEi4w 4MJQ%PVCMFi4w 4MJQ

*OTPJOU4UBOEJOHi4w4UBOEJOHi4w "MU

4UBOEJOHi4w "MU4UBOEJOHi4w4UBOEJOHi4w

 #BS3FJOGPSDFE "OHMF3FJOGPSDFE

Fig. 11

'JSF%BNQFS4MFFWF

/FPQSFOFHBTLFU

CFUXFFOBMMBOHMFT

'MBOHFETZTUFNBOHMFT

 "UUBDIQFS

NBOVGBDUVSFShT

JOTUSVDUJPOT

%VDU

%POPUCPMUDPSOFST

JOMPOHJONBY

UIJDLOFTTQMBTUJDDMFBUT

JODD NJOQFSTJEF

Fig. 12

6

Summary of Contents for FSD-3XXV Series

Page 1: ...dance with combination fire smoke damper requirements established by National Fire Protection Association NFPA Standards 80 90A 92A 92B 101 105 BOCA National Building Codes ICBO Uniform Building Codes IBC International Building Codes SBCCI Standard Building Codes New York City MEA listing 260 91 M California State Fire Marshal Listing 3225 0981 103 and 3230 0981 104 Receiving and Handling Upon rec...

Page 2: ...e installed into duct or opening square and free of twist or other misalignment Damper must not be squeezed or stretched into duct or opening Out of square racked twisted or misaligned installations can cause excessive leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and af...

Page 3: ...l floor openings are Galvanized steel fire dampers and sleeves 1 8 in 3mm per foot of damper width and height with a minimum clearance of 1 4 in 6mm maximum of 1 1 2 in 38mm Recommended clearances for width and or height dimensions of 1 36 in 914mm or less 1 2 in 13mm clearance These are total clearances ignoring fastener heads and do not need to be equally spaced around the damper 2 SLEEVE LENGTH...

Page 4: ... be attached to the damper using one or more of the following methods of attachment refer to label on outside of sleeve for No Screw area Tack or spot welds 10 3 4 in max 19mm sheet metal screws 1 4 in 6mm bolts and nuts 3 16 in 5mm steel pop rivets A minimum of two connections per side top and bottom 12 in 305mm O C maximum for openings of 48 in W x 32 in H 1219mm x 812mm and less and 6 in 152mm ...

Page 5: ...he TOR thermostats and indicator switches If either the TOR or the RRL is ordered with a pneumatic actuator an EP switch is required with an appropriate electric power circuit to allow the electric thermostat to control the pneumatic actuator PRV The PRV pneumatic relief valve option is heat responsive device used with pneumatic actuators This can be used in place of EP switch where a RRL is used ...

Page 6: ...each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket Transverse joints illustrated can be applied as top and bottom joints with Drive Slip side joints in duct heights up to 20 inches 508mm see Fig 10 Round and Oval Duct Breakaway Connections Round or flat oval ducts connected to Type R or O damper collars shall be attached with 10 19mm ...

Page 7: ...ls do not use oil based lubricants or any other lubricants that attract contaminants such as dust Dampers and their actuator s must be maintained cycled and tested a minimum in accordance with The latest editions of NFPA 80 90A 92A 92B 101 105 UL864 AMCA 503 03 and local codes Actuator manufacturer recommendations Damper Troubleshooting The following is a possible cause and correction list for com...