Model IGX Make-Up Air
45
®
Troubleshooting
Evaporative Cooling
Problem: Evaporative Cooling Module Does Not Operate - Single Pass Control
Is fan operating correctly?
Yes
È
No
Æ
Refer to the Troubleshooting, Supply Fan.
24 VAC between terminals Y1 and C
Yes
È
No
Æ
Cool switch (S4) off.
Turn cool switch (S4) on.
Cool switch not wired
. Wire cool switch (S4).
(If a cool switch is not required and a cooing inlet air sensor is
provided, place jumper from R to Y1 to allow the cooling to enable
based on the cooling inlet air sensor).
24 VAC between terminal A2 and A1
on cooling relay (RC)?
Yes
È
No
Æ
Optional inlet air sensor (TS4) holding.
Adjust TS4 setting.
Reference Supply Fan, Start-Up.
Fan Interlock (ST1 or RF) open.
Refer to Troubleshooting, Supply
Fan.
24 VAC between terminals 62 and 61?
Yes
È
No
Æ
Single pass transformer TR2 circuit breaker tripped.
Reset
transformer circuit breaker. If circuit breaker continues to trip, inspect
circuit for improper wiring or grounding.
Single pass transformer TR2 failed.
Replace cooling transformer.
24 VAC between terminals 8 and 61?
Yes
È
No
Æ
Cooling relay (RC) failure.
Check for loose connections or bent relay
pins, repair or replace relay.
Water flowing to media?
Yes
È
No
Æ
Manual ball valve closed.
Open and adjust ball valve.
Single pass valves (VS, VSD) not wired.
Wire single pass valves.
Single pass valve(s) failed.
Replace failed valve(s).
Everything is working properly, consult factory.
Problem: Water Blows through Evaporative Cooling Module
Are the headers in place and located
near the entering air side of the
media?
Yes
È
No
Æ
Replace headers and/or move the headers.
Reference Start-Up:
Optional Features, Evaporative Cooling Module.
Water supply to header too high?
No
È
Yes
Æ
Use the header control valve to reduce the supply of water.
Air velocity greater than specified?
Yes
Æ
Reduce the air velocity through the media.
Reference Supply Fan,
Start-Up.
Everything is working properly, consult factory.