16
1. Construct the vent system as shown below. Looking
in the direction of airflow, the venting is on the right
side of unit.
2. The termination of horizontally vented systems must
extend 12 inches beyond the exterior surface of an
exterior wall.
3. The combustion air pipe must be a minimum of 12
inches below the vent pipe and 24 inches from the
exterior wall.
4. Support the vent and combustion air pipe as shown
below.
Horizontal Venting
Exterior Wall
B
A
EXHAUST
COMBUSTION AIR
Pitch vent pipe downward from
furnace .25 inches per foot
C
Field Supplied
Support Brackets
The venting parts listed above are supplied by Greenheck.
All vent piping is FIELD SUPPLIED by others.
A = 24 inch minimum
B = 12 inch minimum
C = 12 inch minimum
Exhaust Vent
Terminal
Combustion Air
Inlet Terminal
Venting Instructions:
2-Pipe Horizontal
Separated Combustion 2-Pipe Venting Kit - Horizontal
Furnace Size
100 - 150 mbh
200 - 400 mbh
Kit contents: (2) 4 inch vent terminal (2) 6 inch vent terminal
All measurements shown are diameters.