background image

9

1. Installation of venting must conform with local

building codes. In the absence of local codes,
installation must conform with the National Fuel
Gas Code, ANSI Z223.1 or in Canada, CAN/CGA-
B149 installations codes.

2. The classification for vertical and horizontal venting

of all units is category III.  The ANSI requirements
for vents classified as category III is that they must
be gas tight. Seal the joints with a metallic tape or
silastic suitable for temperatures up to 350 degrees
F. the venting system shall be installed in
accordance with these instructions.

3. All pipe is field supplied by others. For the vent

pipe, use pipe approved for a category III appliance
or single wall, 26 gauge or heavier galvanized vent
pipe. For the combustion air pipe on separated
combustion units, sealed single-wall galvanized air
pipe is recommended. Refer to the National Fuel
Gas Code for additional piping guidelines. 

4. Select the vent and combustion air pipe size from

the tables (1) and (2) shown on the following pages.
Select the size of the vent and combustion air pipe
that fits the flue outlet and combustion air intake.
Use only the pipe size specified.

5. Install the vent and combustion air pipes with

minimum downward slopes (from the unit) of 1/4
inch per foot, suspend securely from overhead
structures at points no greater than 3 feet apart.
Fasten individual pipe lengths together with at least
three corrosion resistant sheet metal screws.

6. For the vent pipe, a minimum of 12 inches of

straight pipe is recommended at the flue outlet
before any elbows.

7. Avoid venting through unheated spaces if possible.

To minimize condensation, insulate any vent runs
greater than 5 feet that must pass through an
unheated space.

8. For the combustion air pipes, long runs in cold

climates may require insulation to prevent the
buildup of condensation on the outside of the pipes
where the pipe passes through heated spaces.

9. Vertical combustion air pipes should be fitted with a

tee with a drip leg and clean out cap to prevent any
moisture in the combustion air pipe from entering
the unit. The drip leg should be cleaned out
periodically during the heating season.

10.For separated combustion systems, the wall

thickness for the purpose of venting is 1 inch
minimum, 48 inches maximum.

• Standard Indoor Venting (uses building air for combustion)

• Separated Combustion Concentric Venting (uses outside air for combustion, one exterior roof or wall

penetration)

• Separated Combustion 2-Pipe Venting (uses outside air for combustion, two exterior roof or wall penetrations)

For each method, the units can be vented horizontally through an exterior wall or vertically through the roof.
Refer to the following pages for specific venting instructions. Construct the vent system for the selected
method, as shown in these instructions. When looking in the direction of airflow, the venting is on the right side
of the unit.

Furnace

Vent

Standard

Separated Combustion

Separated

Size

Lengths

Indoor

Concentric

Combustion 2-pipe

100 - 300

min

5 ft.

5 ft.

5 ft.

max

70 ft.

70 ft.

70 ft.

350 - 400

min

5 ft.

5 ft.

5 ft.

max

70 ft.

70 ft.

50 ft.

VENT LENGTHS FOR EXHAUST AND COMBUSTION AIR

Venting Instructions:

Indoor Units

Venting Methods for Indoor Units

Summary of Contents for IGX

Page 1: ...Unit is approved for installation downstream from refrigeration units In these conditions condensate could form in the duct furnace and provision must be made to dispose of the condensate WARNING Impr...

Page 2: ...tal and Downblast Discharge with Optional Mixing Box 5 Downblast Discharge Optional with Combination Extension 6 7 Venting for Indoor units 8 17 Control Center Layout 18 Start Up Electrical 19 Mixing...

Page 3: ...ed by others Figure 1 Step 3 Install Venting Ductwork The instructions for the indoor venting are listed on the following pages Refer to your unit submittal to determine the correct venting option ins...

Page 4: ...B The use of a duct adapter is recommended on a downblast arrangement to properly align the ductwork with the supply unit The duct adapter is only a guide and is not intended to be used as support for...

Page 5: ...equipment support s Installation Instructions for Roof Mounted with Optional Mixing Box Arrangements HZ and DB Step 5 Assemble and Attach Weatherhood The weatherhood can now be assembled and attached...

Page 6: ...e equipment support s to the roof remove metal cover flash to wooden nailer and reinstall cover Step 2 Install Combination Extension Install combination extension over curb use wood screws to lag in p...

Page 7: ...bar hooked to the factory lifting lugs as shown in the diagram to lift and center the unit on the curb equipment support s NOTE THE USE OF ALL LIFTING LUGS IS MANDATORY WHEN LIFTING UNIT Use self tapp...

Page 8: ...l clearance of 4 feet from electric meters gas meters regulators and relief equipment In Canada the minimum clearance is 6 feet 5 Local codes may supercede any of the above provisions 6 Be sure that t...

Page 9: ...s recommended at the flue outlet before any elbows 7 Avoid venting through unheated spaces if possible To minimize condensation insulate any vent runs greater than 5 feet that must pass through an unh...

Page 10: ...tion air from the outside The rule of thumb is that an opening of one square inch should be provided for every 1000 BTU per hour of input rating Vent Construction To vent using this method the vent te...

Page 11: ...tical Venting A1 A 12 inch minimum A1 12 inch minimum but should size according to expected snow depth Standard Indoor Venting EXHAUST Exhaust Vent Terminal Air Inlet Building Roof Venting Instruction...

Page 12: ...of the box Make sure to add the thickness of the wall or roof and the length of the mounting brackets Attach the proper length of pipe to the CVA using three corrosion resistant sheet metal screws and...

Page 13: ...Side Air Inlet Concentric Side CVA Flue Outlet Non Concentric Side Air Inlet Non Concentric Side Flue Outlet Concentric Side Air Inlet Concentric Side Flue Outlet Non Concentric Side Air Inlet Non Con...

Page 14: ...stallation of the combustion air intake guard 3 Caulk between the wall and the air intake pipe 4 Maintain 12 inches from the combustion air inlet guard to the back of the vent terminal 5 Now attach th...

Page 15: ...6 Caulk the gap between the combustion air cap and the vent pipe with silicone sealant or other appropriate sealants suitable for metal to metal contact and temperatures of 350 degrees F Vertical Ven...

Page 16: ...e as shown below Horizontal Venting Exterior Wall B A EXHAUST COMBUSTION AIR Pitch vent pipe downward from furnace 25 inches per foot C Field Supplied Support Brackets The venting parts listed above a...

Page 17: ...ing A A A B C A1 A 12 inch minimum A1 12 inch minimum but should size according to expected snow depth B 24 inch minimum C 12 inch minimum EXHAUST COMBUSTION AIR Tee with drip leg and cleanout cap Com...

Page 18: ...nal Exhaust Starter and Fusing Shown 6 Terminal Strip 24 Volt power at strip for control wiring Note This is a typical control center an exact wiring diagram is shipped with the unit Control Center La...

Page 19: ...ad for CUBE exhaust fan through side breather tube The power lead should be of sufficient length as to allow the CUBE fan to hinge open and to allow service of the burner controls NOTE Any wiring runn...

Page 20: ...the customer to program occupied and unoccupied operation periods Building Pressure Control requires field wiring from the unit to the factory provided remote control panel This option enables outdoor...

Page 21: ...to measure the air volume is by using the pitot traverse method in the ductwork away from the blower Other methods can be used but should be proven and accurate To adjust the air volume change the fa...

Page 22: ...8 988 926 871 823 780 741 1 PVF 150 150 120 4444 3704 3175 2778 2469 2222 2020 1852 1709 1587 1481 1389 1307 1235 1170 1111 1 PVF 200 200 160 5926 4938 4233 3704 3292 2963 2694 2469 2279 2116 1975 185...

Page 23: ...ncy shut off and easy servicing of the controls 5 A 1 8 inch NPT plugged tap shall be installed immediately ahead of the gas supply connection to the furnace 6 After gas piping is completed carefully...

Page 24: ...gnites burner by sparking 13 Flame Sensor Ensures that each burner has ignited Furnace Control Center Layout Figure 7 Furnace Control Center 1 2 3 4 5 6 7 10 11 12 13 8 9 WARNING Disconnect power supp...

Page 25: ...fied the combination gas valve is de energized and the combustion blower shuts off following a 30 second post purge period Recovery from Lockout The ignition control will automatically reset after 1 h...

Page 26: ...the pressure use the low fire adjustment screw on the combination gas valve High Fire Adjustment Low Fire Adjustment Solenoid Staged Temperature Controls The furnace stage controls are located in the...

Page 27: ...ure for each furnace at the pressure test port see Figure 7 using a high quality manometer that can measure low gas pressures The pressure at high fire should be 3 5 in wc for natural gas and 10 0 in...

Page 28: ...per operation and water drainage Piping should be of adequate size to provide sufficient supply of water to meet the maximum demand of the unit Installation Instructions for Optional Evaporative Cooli...

Page 29: ...a without any air flow through the unit A jumper wire is required on the terminal strip to provide power to the evaporative cooler pump See the wiring diagram for the proper location This saturation p...

Page 30: ...ULATION THROUGH THE COIL AT ALL TIMES IS HIGHLY RECOMMENDED 5 Pipe sizes for the system must be selected on the basis of the head pressure available from the circulation pump Piping should be in accor...

Page 31: ...eck for correct drives and rpm with catalog data Dampers or registers closed Open and adjust Dirty or clogged filters Clean or replace Leaks in ductwork Repair Elbows or other obstructions Correct or...

Page 32: ...airflow fault will be declared If proper airflow is detected at any time a normal ignition sequence will begin Once proper airflow is detected the normal Sequence Of Operation for ignition will follo...

Page 33: ...uble flush and clean the system more frequently C If this condition persists chemicals may need to be added Water pH should be maintained between 6 and 8 A Irregular water distribution on face of medi...

Page 34: ...hesive spray can be applied to increase filter efficiency If disposable filters are installed check by holding up to a light source If light cannot pass through the filter it should be replaced Replac...

Page 35: ...easer or compressed air Wipe the inside of the burner clean Cleaning the burner with a degreaser will slow the future buildup of dirt Before reinstalling the burner assembly look down the heat exchang...

Page 36: ...hould be shut off and all the lines drained when the temperature drops below 50 F 4 When the evaporative cooler is going to be used for the first time each season it is recommended that the media be f...

Page 37: ...his build up from plugging the drain and causing the drain pan to overflow Inspect twice a year to avoid the possibility of overflow Also drain pans should be kept clean to prevent the spread of disea...

Page 38: ...38 Documentation Date Problem Resolution...

Page 39: ..._______________ Fax ___________________ Work Done By ___________________________________ Name Plate Information Model ________________________________________ Volts ___________ Hertz __________ Phase...

Page 40: ...o the nearest authorized motor service station Greenheck will not be responsible for any removal or installation costs Due to continuing research Greenheck reserves the right to change specifications...

Reviews: