Copyright © 2008 Greenheck Fan Corporation

FSDR-511 Rev. 6 June 2008

3.375 IN.

FUSIBLE LINK 
(standard)
LOCATION

CLEARANCE FOR
EXPANSION

TOP VIEW OF DAMPER 

6 IN. MAX 

SLEEVE LENGTH 

Wall

DUCT 
CONNECTION 
AREA 

AIRFLOW 

1.5 IN.

ACTUATOR

16.00 IN MAX

OPTIONAL BLADE POSITION 

INDICATOR AND/OR ELECTRIC 

LINK. 

DUCT 
CONNECTION 
AREA 

1.5 IN.

1.50 IN. 

Optional 
Second 
Retaining 
Plate 

Do not place retainer 
plate in this groove 

5.375 in.

3.06 in. or 7.43 in.*

* 7.43 in. when OCI, RRL, RRL/OCI,
   TOR, or PRV is selected

Retaining plate

Specificatons

True Round Combination Fire Smoke Dampers meeting the 
following specifications shall be furnished and installed 
where shown on plans and/or as described in schedules. 
Dampers shall meet the requirements of the latest edition of 
NFPA 80, 90A, 92A, 92B, 101, & 105.

Damper shall be constructed of 20 ga. (1mm) galvanized 
steel frame/sleeve; blade constructed of double skin 
galvanized steel round style blade; silicone rubber blade 
seal; ½ in. plated steel axles; stainless steel bearing. 
Damper is provided with one retainer plate.
Dampers shall be tested, rated and labeled in accordance 
with the latest edition of UL standards 555 and 555S. 
Dampers shall have a UL555 fire rating of 1½ hours. Each 
damper shall be equipped with a heat responsive device, 
which has been tested and approved for use with the 
damper assembly in accordance with UL555. The heat 
responsive device shall have a temperature rating of 
(specifier select one or the following) 165°F (74°C), 212°F 
(100°C), 286°F (141°C), or 350°F (177°C).

Dampers shall be UL labeled for use in dynamic systems. 
The damper shall have a dynamic closure airflow rating 
equal to or greater than the airflow at the dampers installed 
location and a dynamic closure pressure rating of 4 in. wg 
(1kPa). All UL555 and UL555S dynamic closure and leakage 

ratings shall be qualified for airflow and pressure in either 
direction through the damper. UL ratings shall allow for 
mounting damper vertically or horizontally.

Dampers shall have a UL555S leakage rating of Class I and 
a temperature rating of 250°F (121°C) minimum. Dampers 
shall have a UL555S operational airflow rating equal to 
or greater than the airflow at its installed location and an 
operational pressure rating of 4 in. wg (1kPa). Damper 
actuators shall be factory mounted and qualified for use 
with the damper in accordance with UL555S.

Damper actuators shall be (specifier select one of the 
following) electric type for 120 or 24 volt operation and 
pneumatic type for 25 psi minimum (30 psi maximum) 
operation. Manufacturer’s submittal data shall indicate 
actuator space requirements around the damper.

The Damper manufacturer’s submittal data shall certify all 
air performance pressure drop data is tested in accordance 
with the AMCA certified ratings program for test figures 
5.2, 5.3, and 5.5. Damper air performance data shall be 
developed in accordance with the latest edition of AMCA 
Standard 500-D.

Basis of design is Greenheck’s model FSDR-511.