Roof Supply Fan

1

®

Document 453148

Models RSF and RSFP

Roof Supply Fan

Installation, Operation and Maintenance Manual

Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, 
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure 
to comply with these instructions will result in voiding of the product warranty and may result in personal injury 
and/or property damage.

Centrifugal Supply Fans

Fans are specifically designed for filtered roof supply 
applications. Fans feature permanent washable 
aluminum filters for years of reliable use and double-
width forward-curved wheels for high efficiency and 
low sound. Available with straight-sided hood or 
architectural louvered penthouse housing.

Only qualified personnel should install this fan. 
Personnel should have a clear understanding of these 
instructions and should be aware of general safety 
precautions. Improper installation can result in electric 
shock, possible injury due to coming in contact with 
moving parts, as well as other potential hazards. Other 
considerations may be required if high winds or seismic 
activity are present. If more information is needed, 
contact a licensed professional engineer before moving 
forward.

1.  Follow all local electrical and safety codes, as well as 

the National Electrical Code (NEC) and the National 
Fire Protection Agency (NFPA), where applicable. 
Follow the Canadian Electric Code (CEC) in Canada.

2.  The rotation of the wheel is critical. It must be free 

to rotate without striking or rubbing any stationary 
objects.

3.  Motor must be securely and adequately grounded.

4.  Do not spin fan wheel faster than max cataloged fan 

RPM. Adjustments to fan speed significantly affect 
motor load. If the fan RPM is changed, the motor 
current should be checked to make sure it is not 
exceeding the motor nameplate amps.

5.  Do not allow the power cable to kink or come in 

contact with oil, grease, hot surfaces or chemicals. 
Replace cord immediately if damaged.

6.  Verify that the power source is compatible with the 

equipment.

7.  Never open access doors to a duct while the fan is 

running.

DANGER

Always disconnect, lock and tag power source before 
installing or servicing. Failure to disconnect power 
source can result in fire, shock or serious injury.

CAUTION

When servicing the fan, motor may be hot enough 
to cause pain or injury. Allow motor to cool before 
servicing.

CAUTION

Precaution should be taken in explosive atmospheres.

DANGER

Pour écarter les risques d’incendie, de choc électrique 
ou de blessure grave, veiller à toujours débrancher, 
verrouiller et étiqueter la source de courant avant 
l’installation ou l’entretien.

ATTENTION

Lors de toute intervention sur la soufflante, le moteur 
peut être suffisamment chaud pour provoquer une 
douleur voire une blessure. Laisser le moteur refroidir 
avant toute maintenance.

ATTENTION

Faire preuve de précaution dans les atmosphères 
explosives.

General Safety Information

Summary of Contents for RSF

Page 1: ...e National Fire Protection Agency NFPA where applicable Follow the Canadian Electric Code CEC in Canada 2 The rotation of the wheel is critical It must be free to rotate without striking or rubbing any stationary objects 3 Motor must be securely and adequately grounded 4 Do not spin fan wheel faster than max cataloged fan RPM Adjustments to fan speed significantly affect motor load If the fan RPM i...

Page 2: ...age during storage These suggestions are provided solely as a convenience to the user Indoor The ideal environment for the storage of fans and accessories is indoors above grade in a low humidity atmosphere which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly maintained between 30 to 110 F 1 to 43 C Wide temperature swings may cause condensation and sweat...

Page 3: ... 152 113 180 46 611 8 5 17 8 341 4 353 8 121 4 221 2 191 2 101 8 113 4 441 2 261 4 91 8 4 16x20 5 400 285 406x508 1168 1153 1318 870 899 311 571 495 257 298 1130 667 232 4 20x20 181 129 508x508 200 52 731 8 583 16 391 4 403 8 121 4 231 4 251 4 133 8 143 8 501 2 301 4 101 8 8 20x25 6 620 431 1321 1857 1478 997 1026 311 591 641 340 365 1283 768 257 508x635 281 196 All dimensions are in inches millim...

Page 4: ...n inches millimeters Recommended curb size shown is outside curb dimension without roofing and flashing Note In cases where extreme snow depths may be encountered extended base may be required to raise unit or condensation pans may be required in ductwork Prepunched mounting holes and 21 2 in skirt to aid in installation Ductwork by others Duct adapter optional allows ductwork to be completed prio...

Page 5: ...i Kwik Bolt 3 Expansion Anchors 3 6 90 100 120 3 6 150 40x40 1016x1016 mm 4 8 150 4 8 180 200 46x46 to 52x52 1168x1168 to 1321x1321 mm 5 10 180 200 5 10 Steel 90 100 120 26x26 to 34x34 660x660 to 864x864 mm 1 4 in 14 Self Drilling Screw 3 6 90 100 200 3 6 150 40x40 1016x1016 mm 4 8 150 4 8 180 200 46x46 to 52x52 1168x1168 to 1321x1321 mm 5 10 180 200 5 10 Timber 90 100 120 26x26 to 34x34 660x660 t...

Page 6: ...pulleys must be adjusted an equal number of turns open Any increase in fan speed results in an increase in horsepower required for the motor Motor amperage should always be checked and compared to nameplate rating when changing fan speed DANGER Disconnect and secure to the off position all electrical power to the fan prior to inspection or servicing Failure to comply with this safety precaution co...

Page 7: ...s and adjusting the jack screws as required All units are supplied with either a painted steel motor bracket or a galvanized motor plate for larger motor frames To adjust belt tension on units equipped with the painted steel motor bracket simply adjust the single jack screw For units equipped with a galvanized motor plate both jack screws must be adjusted equally Check pulley and belt alignment af...

Page 8: ... page or in the literature section of the website at Greenheck com Resources Library Literature Galvanized motor plate shown Painted steel motor bracket used on units with smaller motor frame sizes Belt Filters Shaft Pulley Blower Mounting Angle Vibration Isolators 4 Motor Pulley Motor Motor Plate Blower Unit Parts List CAUTION La présence d un moteur antidéflagrant sur un ventilateur ne garantit ...

Reviews: