Roof Supply Fan

5

®

Roof Supply Fan

1.25

Curb Corner
Anchor Detail

1.25

Roof Curb
Model SD, SDP, GPF or Equivalent 
18 ga. Min. 
24 in. 

(610 mm)

 Tall Max. 

Welded Steel Construction

Roof Curb 

Roof Curb 

1/4 in. - 14 Self-Drilling Screw 
Min. 1/2 in. 

(13 mm)

 of Threads Through

Roof Truss
1/8 in. 

(3 mm)

 Thick 

or 12 ga. Min. 

3/8 in. 

(10 mm) 

S.S. Hilti Kwik Bolt 3 

Expansion Anchors
Min. 2-1/2 in. 

(64 mm)

 Engagement

2000 Min. PSI
Concrete

Concrete

Deck Anchoring

Steel

Deck Anchoring

Timber Anchoring

Roof Curb

Wood Timber
Min. 4 in. 

(102 mm) 

Nominal Thickness
Min. G = 0.42

G = specific gravity
of lumber

3/8 in. 

(10 mm)

 Lag Bolt (Zinc Plated) 

Min. 3 in. 

(76 mm)

 Thread Engagement

High Wind Ratings

Seismic Ratings

Fan Size

Curb Cap Size

Fastener Size  

and Type

Fasteners  

Per Side

Total 

Fasteners 

Fan Size

Fasteners 

per side

 Total

Fasteners

Concrete

90, 100, 120

26x26 to 34x34 

(660x660 to 864x864 mm)

3/8-inch S.S. 

Hilti Kwik Bolt 3 

Expansion 

Anchors

3

6

90, 100, 120

3

6

150

40x40 

(1016x1016 mm)

4

8

150

4

8

180, 200

46x46 to 52x52 

(1168x1168 to 1321x1321 mm)

5

10

180, 200

5

10

Steel

90, 100, 120

26x26 to 34x34 

(660x660 to 864x864 mm)

1/4 in. - 14  

Self-Drilling 

Screw

3

6

90, 100, 200

3

6

150

40x40 

(1016x1016 mm)

4

8

150

4

8

180, 200

46x46 to 52x52 

(1168x1168 to 1321x1321 mm)

5

10

180, 200

5

10

Timber

90, 100, 120

26x26 to 34x34 

(660x660 to 864x864 mm)

3/8-inch  
Lag Bolt 

(zinc plated)

3

6

90, 100, 120

3

6

150

40x40 

(1016x1016 mm)

4

8

150

4

8

180, 200

46x46 to 52x52 

(1168x1168 to 1321x1321 mm)

5

10

180, 200

5

10

All dimensions are in inches 

(millimeters)

.

Mounting for Severe Duty Installations

Fan to Curb: 

Three (3) fasteners are required 

per side on all sides. Must be equally spaced.

Curb to Deck: 

Fasteners need to be located on two 

opposite ends of the curb.

IMPORTANT

Installation instructions for seismic ratings are only recommendations. Final design must be determined by 
Structural Engineer of Record (SEOR) including requirements for curb construction, mounting of unit to curb and 
mounting of curb to structure.

Summary of Contents for RSF

Page 1: ...e National Fire Protection Agency NFPA where applicable Follow the Canadian Electric Code CEC in Canada 2 The rotation of the wheel is critical It must be free to rotate without striking or rubbing any stationary objects 3 Motor must be securely and adequately grounded 4 Do not spin fan wheel faster than max cataloged fan RPM Adjustments to fan speed significantly affect motor load If the fan RPM i...

Page 2: ...age during storage These suggestions are provided solely as a convenience to the user Indoor The ideal environment for the storage of fans and accessories is indoors above grade in a low humidity atmosphere which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly maintained between 30 to 110 F 1 to 43 C Wide temperature swings may cause condensation and sweat...

Page 3: ... 152 113 180 46 611 8 5 17 8 341 4 353 8 121 4 221 2 191 2 101 8 113 4 441 2 261 4 91 8 4 16x20 5 400 285 406x508 1168 1153 1318 870 899 311 571 495 257 298 1130 667 232 4 20x20 181 129 508x508 200 52 731 8 583 16 391 4 403 8 121 4 231 4 251 4 133 8 143 8 501 2 301 4 101 8 8 20x25 6 620 431 1321 1857 1478 997 1026 311 591 641 340 365 1283 768 257 508x635 281 196 All dimensions are in inches millim...

Page 4: ...n inches millimeters Recommended curb size shown is outside curb dimension without roofing and flashing Note In cases where extreme snow depths may be encountered extended base may be required to raise unit or condensation pans may be required in ductwork Prepunched mounting holes and 21 2 in skirt to aid in installation Ductwork by others Duct adapter optional allows ductwork to be completed prio...

Page 5: ...i Kwik Bolt 3 Expansion Anchors 3 6 90 100 120 3 6 150 40x40 1016x1016 mm 4 8 150 4 8 180 200 46x46 to 52x52 1168x1168 to 1321x1321 mm 5 10 180 200 5 10 Steel 90 100 120 26x26 to 34x34 660x660 to 864x864 mm 1 4 in 14 Self Drilling Screw 3 6 90 100 200 3 6 150 40x40 1016x1016 mm 4 8 150 4 8 180 200 46x46 to 52x52 1168x1168 to 1321x1321 mm 5 10 180 200 5 10 Timber 90 100 120 26x26 to 34x34 660x660 t...

Page 6: ...pulleys must be adjusted an equal number of turns open Any increase in fan speed results in an increase in horsepower required for the motor Motor amperage should always be checked and compared to nameplate rating when changing fan speed DANGER Disconnect and secure to the off position all electrical power to the fan prior to inspection or servicing Failure to comply with this safety precaution co...

Page 7: ...s and adjusting the jack screws as required All units are supplied with either a painted steel motor bracket or a galvanized motor plate for larger motor frames To adjust belt tension on units equipped with the painted steel motor bracket simply adjust the single jack screw For units equipped with a galvanized motor plate both jack screws must be adjusted equally Check pulley and belt alignment af...

Page 8: ... page or in the literature section of the website at Greenheck com Resources Library Literature Galvanized motor plate shown Painted steel motor bracket used on units with smaller motor frame sizes Belt Filters Shaft Pulley Blower Mounting Angle Vibration Isolators 4 Motor Pulley Motor Motor Plate Blower Unit Parts List CAUTION La présence d un moteur antidéflagrant sur un ventilateur ne garantit ...

Reviews: