background image

Model SMD-301 meets the requirements for smoke 

dampers established by:

National Fire Protection Association 

    NFPA Standards 92A, 92B, 101 & 105

IBC  International Building Codes
New York City 

(MEA listing #260-91-M)

CSFM California State Fire Marshal 

  Leakage (Smoke) Damper Listing (#2330-0981:104)

Application

Model SMD-301 is a leakage rated  smoke damper with extremely 

low leakage. The SMD-301 serves the function of both a control 

damper and smoke damper. High strength airfoil blades insure 

lowest resistance to airflow in HVAC systems with velocities to 

3000 fpm (15.2m/s) and 4 in. wg (1.0 kPa) Model SMD-301 may be 

installed vertically (with blades running horizontal) or horizontally 

and is rated for airflow and leakage in either direction.

UL555S Leakage Rating

 

Leakage Class:

 

I

 

Operational Rating 

 

Maximum Velocity:

 

3000 fpm (15.2 m/s)

 

 

Maximum Pressure:

 

4 in. wg (1 kPa)

 

 

Maximum Temperature:

 

350ºF (177ºC) depending on 

 

 

actuator

Standard Construction

 

Frame:

  

5 in. x 1 in. (127mm x 25mm)

 

 

galvanized steel hat channel with

 

 

reinforced corners. A low profile 

 

 

head and sill are used on sizes less 

 

 

than 17 in. (432mm) high to 

 

 

maximize free area and 

 

 

performance. 

 

Blades:

  

Double skin airfoil shape of 

 

 

galvanized steel with full length

 

 

structural reinforcement. 14 ga.  

 

 

(2 mm) equivalent thickness.  

 

Seals:

 

Extruded silicone rubber blade

 

 

seals.  Flexible stainless steel jamb

 

 

seals. 

 

Linkage:

 

Concealed in jamb. 

 

Axles:

 

1

/

2

 in. (13mm) dia. plated steel. 

 

Bearings:

 

Bronze sleeve type.

Size Limitations:

 

Minimum Size:

 

8 in. W x 6 in. H 

 

 

(203mm W x 152mm H) 

 

Maximum Size:

 

 

Single Section: 

32 in. W x 50 in. H 

 

 

(813mm W x 1270mm H) 

 

Multiple Section: 

128 in. W x 100 in. H 

 

 

(3251mm W x 2540mm H) or 

 

 

256 in. W x 50 in. H 

 

 

(6502mm W  x 1270mm H)

Optional Features:

• Galvanized steel sleeves.
• Stainless steel bearings
• OCI (Open closed indication switches)
•  Electric or pneumatic actuators to accomplish smoke

 

management and system functions.

• Transitions (R, C, O)
• POC retaining angles
• Momentary Switch
• Smoke detectors
• Sealed transitions and sleeves
• Fail open

SMD-301

Smoke Dampers

Steel Airfoil Blades

UL 555S Leakage Class I

*W&H dimensions furnished approximately 

1

/

4

 in. (6mm) undersize.

Right hand drive is shown. Left hand drive is available upon request.

Damper also may be rotated 180° in the field for opposite side drive.

(Add sleeve thickness for overall sleeved damper dimension)

H*

W*

LH

RH

“UL CLASSIFIED (see complete marking on 

product)”

“UL CLASSIFIED to Canadian safety standards 

(see complete marking on product)”

 

Standard 555S (

Listing #R13317)

R

Greenheck Fan Corporation certifies that the 

model SMD-301 shown herein is licensed to 
bear the AMCA Seal. The ratings shown are 
based on tests and procedures performed 
in accordance with AMCA Publication 511 
and comply with the requirements of the 

AMCA Certified Ratings Programs. The 
AMCA Certified Ratings Seal applies to air 

performance ratings only.

Installation instructions available at www.greenheck.com

Summary of Contents for Steel Airfoil Blades SMD-301M

Page 1: ...b seals Linkage Concealed in jamb Axles 1 2 in 13mm dia plated steel Bearings Bronze sleeve type Size Limitations Minimum Size 8 in W x 6 in H 203mm W x 152mm H Maximum Size Single Section 32 in W x 5...

Page 2: ...strates a fully ducted damper This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstr...

Page 3: ...ity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 03 500 0 01 500 0 01 500 0 01 500 0 02 1000 0 12 1000 0 06 1000 0 0...

Page 4: ...Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 01 500 0 01 500 0 01 500 0 01 500 0 01 100...

Page 5: ...Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 04 500 0 03 500 0 03 500 0 03 500 0 03 1000 0 18 1000 0 13 10...

Page 6: ...301 The standard A dimensions listed in the table provide adequate space for the mounting of actuators and controls If space constraints are a problem the A dimension can be varied between 53 8 in 13...

Page 7: ...r pneumatic type for 25 psi minimum 30 psi maximum operation Damper blades shall be of the double skin airfoil type and shall have an equivalent metal thickness of 14 ga 2mm Damper frame shall be galv...

Reviews: