background image

50 in. 

32 in. (813mm)

32 in. (813mm) 64 in. (1626mm)

50 in. 

96 in. (2435mm)

50 in.

100 in. 

 

(1270mm)

32 in. (813mm)

 (2540mm)

 

(1270mm)

32 in. (813mm)

128 in. (2540mm)

(1270mm)

50 in. 

 

(1270mm)

Transitioned Damper 

Dimensions

When a fire/smoke damper is being used in conjunction with round or oval ductwork, the 

SMD-301 can be supplied in a factory sleeve with round or oval transitions on both ends of 

the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show overall 

damper size.

These dimensions are furnished 

approximately 

1

/

4

 in. (6mm) undersize, 

except round and oval dimensions 

which are approximately 

1

/

8

 in. (3mm) 

undersize.
Ts = (2)(Sleeve Thickness)

Smoke Dampers meeting the following specifications shall be 

furnished and installed where shown on plans and/or as described 

in schedules. Dampers shall meet the requirements of NFPA 92A, 

92B, 101 and 105 and further shall be tested, rated and labeled in 

accordance with the latest edition of UL Standard 555S. Smoke 

dampers shall be of low leakage design qualified to UL 555S 

Leakage Class I.

Each damper /actuator combination shall have a UL555S elevated 

temperature rating of 250°F (121º C) minimum and shall be rated to 

operate at maximum design air flow at its installed location. Each 

damper shall be supplied with an appropriate actuator installed by 

the damper manufacturer at the time of damper fabrication. Damper 

actuator shall be (specifier select one of the following) electric 

type for 120 (24 or 230) Volt operation or pneumatic type for 25 psi 

minimum (30 psi maximum) operation.

Damper blades shall be of the double skin airfoil type and shall have 

an equivalent metal thickness of 14 ga. (2mm) Damper frame shall 

be galvanized steel formed into a structural hat channel shape with 

reinforced corners. Bearings shall be sintered bronze sleeve type 

rotating in extruded holes in the damper frame. Blade edge seals 

shall be silicone rubber designed to inflate and provide a tighter 

seal against leakage as pressure on either side of the damper 

increases. Jamb seals shall be stainless steel compression type. 

Blades shall be completely symmetrical relative to their axle pivot 

point, presenting identical resistance to airflow in either direction or 

pressure on either side of the damper. 

Damper must be rated for mounting vertically (with blades running 

horizontal) or horizontally and be UL 555S rated for leakage and 

airflow in either direction through the damper. 

The basis of design is Greenheck Model SMD-301

.

Damper Sizing Information

Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size. 

The following figures show damper sections and assemblies that have been qualified for operation with a single actuator. 

Larger sizes can be accommodated using multiples of these assembles.

Specifications

D*  +  2 in. (51mm) +T  s 

D* 

TYPE  R 

 

16 in. (406mm) 

Min. 

8

 in.

D*  +  2 in. (51mm)+T  s 

TYPE  O 

H* 

W* 

  

+  2 in. (51mm)+T s 

H*  +  2 in. (51mm)+T s 

W* 

H* 

TYPE  C 

  

H*  +  2 in. (51mm)+T s 

 

(54mm)

16 in. (406mm) 

Min. 

8

 in. 

(54mm)

16 in. (406mm) 

Min. 

W* +  2 in. (51mm)+T s 

(54mm)

8

 in.

Single Section

Double Section

Copyright ©2006 Greenheck Fan Corporation

 SMD-301 Rev. 4 June  2006

Summary of Contents for Steel Airfoil Blades SMD-301M

Page 1: ...b seals Linkage Concealed in jamb Axles 1 2 in 13mm dia plated steel Bearings Bronze sleeve type Size Limitations Minimum Size 8 in W x 6 in H 203mm W x 152mm H Maximum Size Single Section 32 in W x 5...

Page 2: ...strates a fully ducted damper This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstr...

Page 3: ...ity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 03 500 0 01 500 0 01 500 0 01 500 0 02 1000 0 12 1000 0 06 1000 0 0...

Page 4: ...Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 01 500 0 01 500 0 01 500 0 01 500 0 01 100...

Page 5: ...Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 04 500 0 03 500 0 03 500 0 03 500 0 03 1000 0 18 1000 0 13 10...

Page 6: ...301 The standard A dimensions listed in the table provide adequate space for the mounting of actuators and controls If space constraints are a problem the A dimension can be varied between 53 8 in 13...

Page 7: ...r pneumatic type for 25 psi minimum 30 psi maximum operation Damper blades shall be of the double skin airfoil type and shall have an equivalent metal thickness of 14 ga 2mm Damper frame shall be galv...

Reviews: