Link-Belt MG-534 Calibration
14
W450160 10/07
Menu 02 – Zero Sensor
The zero sensor menu enables the calibration of the boom extension sensor and the boom angle
sensor. Each sensor is assigned an analog input number which corresponds to the input that it is
connected to.
IMPORTANT!
MAkE SuRE ThE BOOM IS fuLLy RETRACTED BEfORE PERfORMINg ThIS CALIBRATION.
Boom extension sensor - Analog Input 2.
•
Boom angle sensor - Analog Input 3.
•
Boom Extension Sensor Zero
From the previous menu, press the key adjacent to
Menu Up
to go to “02 Zero Sensor”.
Press the key adjacent to
02 Zero Sensor
.
Press the key adjacent to
Zero No. 2 X
(where X = actual
input).
LOAD
0.8
ANGLE
41.8
RADIUS
76.2 FT
LENGTH
106.0
02 Zero Sensor
Menu Up
Menu Down
Exit
LOAD
0.8
ANGLE
41.8
RADIUS
76.2 FT
LENGTH
106.0
Zero No.2 6
Zero Sensor
Menu Up
Menu Down
Exit