Page 32
DLT 2.0 Differential Level Transmitter
TRANSDUCER
GND
DLT 2.0
Installed in
Non-
H
azardous Location
The intrinsic safety barrier
assemblies installed in the
DLT
2
.
0
limit the voltage and
current supplied to the
transducers to the values
listed under ‘Barrier
Specifications’. To safely
install
G
reyline transducers
certified for use in hazardous
locations you must refer to
the installation
drawings/specifications of
the certified transducers.
TRANSDUCER
CONNECTIONS
ST
AHL
9001/02-093-390-101
1
2
3
4
ST
AHL
9001/02-093-390-101
1
2
3
4
BARRIER SPECI
F
ICATIONS
9001
/
02
-
093
-
390
-
101
STAHL BARRIER
9
.
6V,
2
7 ohms
U
m
2
5
0V
V
0C
9
.
3V
I
SC
390
mA
P
0
906
.8m
W
C
a
4
.
1
µF
L
a
0
.
16
m
H
System Parameters
Entity Parameters
GN3SPEC-ISB-04
(
rated 9.6
V
, 27 ohms
)
(
rated 9.6
V
, 27 ohms
)