background image

Page  3

OUTPUT SCALING

The CO

2

 output signal is scaled such that 4-20 mA (or 0-5 / 0-10 Vdc) equals 0-2000 ppm by default. The 

signal span may be changed via the Setup Menu from 1000 to 10,000 ppm in 500 ppm increments.

START-UP MODE

Verify the device is properly wired and connections are tight. Ensure the mA / VOLT switch is set for the 

correct signal type. Apply power and the LCD will indicate the software version number, the output 

signal type and then the sensor will begin a one minute warm-up countdown. When the warm-up time 

expires the device will enter normal mode.

NORMAL MODE

The sensor will begin reading the CO

2

 level (and temperature if it is installed), output the correct analog 

signal and display the values on the LCD. If the relay is installed, the measurements will be compared to 

the setpoint and appropriate action taken. The keypad is monitored and if the <MENU> key is pressed 

the device will enter the Setup Menu. If the setpoint option is installed, then pressing either the <UP> 

or <DOWN> keys will cause the device to enter the setpoint mode. The Setup Menu can be accessed to 

configure the device for required operation.

RELAY MODE

The optional relay can be used as an alarm signal to indicate that a setpoint has been exceeded. For 

the basic CO

2

 product, the relay may be configured via the Setup Menu as a high or low alarm and the 

setpoint value, hysteresis and on-delay time may be set. The relay will activate and close the contacts 

if the CO

2

 measurement goes above the setpoint (for a high alarm) or below the setpoint (for a low 

alarm). If required, this action can be delayed by a time period (relay delay time) to prevent false alarms. 

After the relay is activated, the measurement must fall below the setpoint - hysteresis value (for a high 

alarm) or go above the se hysteresis value (for a low alarm) to deactivate the relay and open the 

contacts. The high/low assignment, setpoint, delay time and hysteresis values may all be programmed 

via the Setup Menu as required.

If the optional temperature sensor is installed, the relay operation may be assigned to operate as a 

temperature high or low alarm instead of a CO

2

 alarm. All the same relay parameters may be configured 

to set up the alarm as required.

SETPOINT MODE

The optional setpoint control is operated by two front panel switches for <UP> and <DOWN> and the 

resistive output signal simulates a slidepot action with + and - 10 steps from the midpoint. For example, 

if the device is ordered with a 0-10KΩ resistance value, then the resistive output midpoint is 5KΩ and 

each press of the <UP> key will increase the output resistance by 500Ω up to 10KΩ and each press of 

the <DOWN> key will decrease the output resistance down to 0Ω. There are several optional “slidepot” 

values available for the product such as 20-30KΩ, 475-10,475Ω, etc and each range may be set as direct 

or reverse acting via the Setup Menu.

voltage signals are referenced to the COM terminal. The current output operates in the active mode and 

does not require a loop power supply (the signal current is generated by the transmitter and must not be 

connected to a powered input or device damage will result).

The optional relay output connects to the RELAY terminals. The relay output is completely isolated and 

has a Normally Open (NO) signal. This signal can be used to directly control an alarm or ventilation fan. See 

specifications for contact ratings. See Figure 8.

The optional override signal is a two-wire dry contact normally open switch connected to the SWITCH 

terminals. See Figure 9.

The optional setpoint signal is a resistive signal that can vary from 0-10K ohms (for example) to simulate 

a slidepot action. It is available on the SETPNT terminal and is referenced to COM. Several resistive values 

are available and the operation may be configured as normal or reverse acting via the Setup Menu. See 

Figure 9

The optional two-wire temperature sensor output is available with various RTDs and thermistors to suit all 

control applications and is available on the TEMP terminals. See Figure 9.

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

IN-GE-CD2RMCXXX-04

Summary of Contents for CD2RMC Series

Page 1: ...r conditioned spaces contact factory or other applications Do not exceed device ratings This product is not intended for life safety applications NOTE This CO2 sensor incorporates a Self Calibration feature to correct CO2 sensor drift This feature is recommended for applications where the CO2 will be exposed to fresh air 400 ppm at least one hour per day If the monitored space is occupied 24 hours...

Page 2: ...he enclosure and complete the wiring connection according to the wiring diagram Figure 6 This is a 3 wire sourcing device Connect the plus DC or the AC voltage hot side to the PWR terminal and the common is connected to the COM terminal The device is reverse voltage protected and will not operate if connected backwards It has a half wave power supply so the supply common is the same as the signal ...

Page 3: ...s required If the optional temperature sensor is installed the relay operation may be assigned to operate as a temperature high or low alarm instead of a CO2 alarm All the same relay parameters may be configured to set up the alarm as required SETPOINT MODE The optional setpoint control is operated by two front panel switches for UP and DOWN and the resistive output signal simulates a slidepot act...

Page 4: ... required Factory default is Direct MENU Press to advance to next menu item 5 OUTPUT SIGNAL DIRECTION When either the UP or DOWN keys are pressed the LCD temporarily changes to display the temperature setpoint value in C or F as set by Temp Units in the Setup Menu The display will show the previous temperature setpoint setting such as 22 ºC or 77 ºF If no other action is taken for 5 seconds then t...

Page 5: ...installed Factory default is C Display is used to control what information is displayed on the LCD The selections depend on the installed options Use UP or DOWN to select either CO2 ppm Temp CO2 Temp Rotate or None Factory default is CO2 ppm For a basic CO2 only device the selection is limited to CO2 ppm or None CO2 ppm Only the actual ppm value of the CO2 reading will be displayed Temp Only tempe...

Page 6: ...es in 1 minute increments to prevent false alarms The default is 0 minutes no delay Use UP or DOWN to toggle the relay ON or OFF to test the relay operation Press MENU to reset to OFF and advance or or 12 RELAY SETPOINT 13 RELAY HYSTERESIS 14 RELAY DELAY 15 RELAY TEST RELAY ASSIGNMENT DEFAULT SETPOINT SETPOINT RANGE RESOLUTION Temp High 26 0 C 79 0 F 5 0 to 40 0 C 40 0 to 100 0 F 0 5 Temp Low 15 0...

Page 7: ...several minutes and then press and hold UP or down button for five seconds until display shows Calibrat Done or Calibrat Fail Refer to Calibration section in this document for more details MENU Press to exit the menu and return to normal mode MENU Press to exit the menu and return to normal mode 19 CO2 CALIBRATION 20 CO2 CALIBRATION CALIBRATION Calibration with gas requires a field calibration kit...

Page 8: ...racter OPTIONAL TEMPERATURE SENSOR Type Various Thermistors and RTDs Accuracy Thermistors 0 2 C 0 36 F 25 C 77 F Platinum RTD s 0 3 C 0 54 F 0 C 32 F Nickel RTD s 0 4 C 0 72 F 0 C 32 F Range 0 to 50 C 32 to 122 F Output 2 wire resistive Relay Optional 2 wire output Form A N O 2 Amps 140 Vac 30 Vdc Override Switch Optional 2 wire output 50 mA 12 Vdc max OPTIONAL SETPOINT CONTROL Type Front panel up...

Reviews: