CO2 Span

2000 ppm

The CO

2

 Span value controls the analog output scaling. CO

2

 span can be changed

from 1000 to 10,000 ppm in 500 ppm increments using <UP> or <DOWN>. If CO

2

 

Span = 2000 ppm, then the output signal is scaled 0-2000 ppm = 4-20 mA. Factory 

default is 2000 ppm.

<MENU> 

Press to advance to next menu item

1. SPAN

Altitude

0 m

Self-Cal

ON

The Altitude value allows CO

2

 compensation for local atmospheric pressure and 

altitude and ensures the highest CO

2

 accuracy. Altitude can be changed from 0 to 

2550 meters in 50 meter steps using <UP> or <DOWN>. It will take a few moments 

to change the setting, then the menu will advance to the next step. Factory default 

is 0 m (sea level).

The Self-Cal feature <MENU> when enabled requires the sensor to be exposed 

to fresh air for at least one hour every twenty-four hours.  When first installed the 

sensor requires a minimum of seven days of operation with fresh air exposer daily 

to allow the algorithm to adjust for self-calibration.  Default for device is having 

this feature enabled “ON”. If disabling this feature a manual calibration should be 

performed to ensure accuracy of the device.

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

3. ALTITUDE

2. SELF CALIBRATION

V Output

0-5 Vdc

The V Output value controls the analog output voltage span if the PCB switch is set 

to VOLT. V Output can be set to either 0-5 Vdc or 0-10 Vdc using <UP> or <DOWN>. 

This setting has no effect if the PCB switch is set to mA. Factory default is 0-5 Vdc.

<MENU> 

Press to advance to next menu item

4. OUTPUT VOLTAGE SPAN

Output

Direct

The Output value controls the analog output signal direction. Use <UP> or 

<DOWN> to change the setting from Direct (4-20 mA, 0-5 Vdc or 0-10 Vdc) to 

Reverse (20-4 mA, 5-0 Vdc or 10-0 Vdc) if reverse action is required. Factory default 

is Direct.

<MENU> 

Press to advance to next menu item

5. OUTPUT SIGNAL DIRECTION

When either the <UP> or <DOWN> keys are pressed, the LCD temporarily changes to display the 

temperature setpoint value in °C or °F as set by Temp Units in the Setup Menu. The display will show the 

previous temperature setpoint setting such as 22 ºC or 77 ºF. If no other action is taken for 5 seconds 

then the device will reset to normal operation. While the display is still flashing the setpoint can be 

modified by pressing the <UP> or <DOWN> keys to increase or decrease the setpoint value. The LCD 

will update to show the new setpoint and the output signal will update accordingly. When the desired 

setpoint is shown on the LCD, leave the unit for 5 seconds to reset to normal operation and save the 

new setting. As the setpoint is changed the SETPNT output signal will change in resistance. The display 

midpoint and step resolution can both be programmed using the Setup Menu.

SETUP MENU

The device has several parameters that can be configured locally via the Setup menu using the keypad 

and LCD. Any changes made are saved in non-volatile memory and are restored in case of a power loss. 

The menu can be accessed at any time after the start-up mode and if there is 5 minutes of inactivity the 

menu will close and normal operation will continue.

To enter the menu, press and release the <MENU> key. This will enter the Setup Menu step 1, pressing 

the <MENU> key a second time saves the setting and advances to step 2. Each press of the <MENU> key 

saves the current setting and advances the menu item. The <UP> and <DOWN> keys are used to make 

changes to program variables by scrolling through the available options. The first column below shows 

what will be displayed on the LCD, including the default value.

<MENU> 

Press and release the <MENU> key to enter the Setup Menu

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

IN-GE-CD2RMCXXX-04

Summary of Contents for CD2RMC Series

Page 1: ...r conditioned spaces contact factory or other applications Do not exceed device ratings This product is not intended for life safety applications NOTE This CO2 sensor incorporates a Self Calibration feature to correct CO2 sensor drift This feature is recommended for applications where the CO2 will be exposed to fresh air 400 ppm at least one hour per day If the monitored space is occupied 24 hours...

Page 2: ...he enclosure and complete the wiring connection according to the wiring diagram Figure 6 This is a 3 wire sourcing device Connect the plus DC or the AC voltage hot side to the PWR terminal and the common is connected to the COM terminal The device is reverse voltage protected and will not operate if connected backwards It has a half wave power supply so the supply common is the same as the signal ...

Page 3: ...s required If the optional temperature sensor is installed the relay operation may be assigned to operate as a temperature high or low alarm instead of a CO2 alarm All the same relay parameters may be configured to set up the alarm as required SETPOINT MODE The optional setpoint control is operated by two front panel switches for UP and DOWN and the resistive output signal simulates a slidepot act...

Page 4: ... required Factory default is Direct MENU Press to advance to next menu item 5 OUTPUT SIGNAL DIRECTION When either the UP or DOWN keys are pressed the LCD temporarily changes to display the temperature setpoint value in C or F as set by Temp Units in the Setup Menu The display will show the previous temperature setpoint setting such as 22 ºC or 77 ºF If no other action is taken for 5 seconds then t...

Page 5: ...installed Factory default is C Display is used to control what information is displayed on the LCD The selections depend on the installed options Use UP or DOWN to select either CO2 ppm Temp CO2 Temp Rotate or None Factory default is CO2 ppm For a basic CO2 only device the selection is limited to CO2 ppm or None CO2 ppm Only the actual ppm value of the CO2 reading will be displayed Temp Only tempe...

Page 6: ...es in 1 minute increments to prevent false alarms The default is 0 minutes no delay Use UP or DOWN to toggle the relay ON or OFF to test the relay operation Press MENU to reset to OFF and advance or or 12 RELAY SETPOINT 13 RELAY HYSTERESIS 14 RELAY DELAY 15 RELAY TEST RELAY ASSIGNMENT DEFAULT SETPOINT SETPOINT RANGE RESOLUTION Temp High 26 0 C 79 0 F 5 0 to 40 0 C 40 0 to 100 0 F 0 5 Temp Low 15 0...

Page 7: ...several minutes and then press and hold UP or down button for five seconds until display shows Calibrat Done or Calibrat Fail Refer to Calibration section in this document for more details MENU Press to exit the menu and return to normal mode MENU Press to exit the menu and return to normal mode 19 CO2 CALIBRATION 20 CO2 CALIBRATION CALIBRATION Calibration with gas requires a field calibration kit...

Page 8: ...racter OPTIONAL TEMPERATURE SENSOR Type Various Thermistors and RTDs Accuracy Thermistors 0 2 C 0 36 F 25 C 77 F Platinum RTD s 0 3 C 0 54 F 0 C 32 F Nickel RTD s 0 4 C 0 72 F 0 C 32 F Range 0 to 50 C 32 to 122 F Output 2 wire resistive Relay Optional 2 wire output Form A N O 2 Amps 140 Vac 30 Vdc Override Switch Optional 2 wire output 50 mA 12 Vdc max OPTIONAL SETPOINT CONTROL Type Front panel up...

Reviews: