Page 5
BackLite
Auto
The BackLite setting is used to control how the LCD backlight functions. Use
<UP> or <DOWN> to select either Auto, Off or On. Auto means the backlight only
lights when a menu is accessed or when the setpoint is activated (ie: when a key
is pressed), Off means the backlight is always off and On means it is always on.
Factory default is Auto.
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
9. BACKLIGHT
Only if
Temperature Sensor
option Installed
Only for
Temperature or Setpoint
Models
T Offset
0.0
°
C
Temp
Units
°
C
Display
CO2 ppm
CO2
1235 ppm
Temp
24.3
°
C
1235 ppm
24.3
°
C
CO2
1235 ppm
Temp
24.3
°
C
The T Offset value allows calibration of the temperature value displayed on the
LCD. Units (°C/°F) follow the Temp Units setting. Use <UP> or <DOWN> to add
or subtract an offset from the temperature value. The range is -5.0 to 5.0 °C or
-9.0 to 9.0 °F in 0.1° increments. Factory default is 0.0 °C.
The Temp Units setting is used to select °C or °F display of temperature. Use
<UP> or <DOWN> to select. The selection will also control available setpoint
ranges if the setpoint option is installed. Factory default is °C.
Display is used to control what information is displayed on the LCD. The
selections depend on the installed options. Use <UP> or <DOWN> to select
either CO
2
ppm, Temp, CO
2
+Temp, Rotate or None. Factory default is CO
2
ppm.
For a basic CO
2
only device, the selection is limited to CO
2
ppm or None.
CO
2
ppm
Only the actual ppm value of
the CO
2
reading will be displayed
Temp
Only temperature is displayed
(°C or °F depends on units setting)
CO
2
& Temp CO
2
ppm and temperature both
displayed at the same time
Rotate
All available sensor readings rotate
at 2 second intervals
None
No measurement information is displayed in
normal mode, the setpoint information will
still be displayed in setpoint mode, the menu
will still display in Setup Menu mode
10. TEMPERATURE OFFSET
7. TEMPERATURE UNITS
8. DISPLAY
Output
Test OFF
The Output Test value controls the analog output signal for testing purposes.
Use <UP> or <DOWN> to toggle the output signal to OFF (normal operation),
MIN (minimum output) or MAX (maximum output). The actual output signal will
depend on the PCB switch position (mA or VOLT) and the V Output setting (for
voltage operation). Press <MENU> to set it back to OFF and advance. Factory
default is OFF.
<MENU>
Press to advance to next menu item
6. OUTPUT TEST