Page  5

BackLite

Auto

The BackLite setting is used to control how the LCD backlight functions. Use 

<UP> or <DOWN> to select either Auto, Off or On. Auto means the backlight only 

lights when a menu is accessed or when the setpoint is activated (ie: when a key 

is pressed), Off means the backlight is always off and On means it is always on. 

Factory default is Auto.

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

9. BACKLIGHT

Only if 

Temperature Sensor

 option Installed

Only for 

Temperature or Setpoint

 Models

T Offset

0.0 

°

C

Temp

Units 

°

C

Display

CO2 ppm

CO2

1235 ppm

Temp

24.3 

°

C

1235 ppm

24.3 

°

C

CO2

1235 ppm

Temp

24.3 

°

C

The T Offset value allows calibration of the temperature value displayed on the 

LCD. Units (°C/°F) follow the Temp Units setting. Use <UP> or <DOWN> to add 

or subtract an offset from the temperature value. The range is -5.0 to 5.0 °C or 

-9.0 to 9.0 °F in 0.1° increments. Factory default is 0.0 °C.

The Temp Units setting is used to select °C or °F display of temperature. Use 

<UP> or <DOWN> to select. The selection will also control available setpoint 

ranges if the setpoint option is installed. Factory default is °C.

Display is used to control what information is displayed on the LCD. The 

selections depend on the installed options. Use <UP> or <DOWN> to select 

either CO

2

 ppm, Temp, CO

2

+Temp, Rotate or None. Factory default is CO

2

 ppm. 

For a basic CO

2

 only device, the selection is limited to CO

2

 ppm or None.

CO

2

 ppm 

Only the actual ppm value of 

 

the CO

2

 reading will be displayed

Temp 

Only temperature is displayed 

 

(°C or °F depends on units setting)

CO

2

 & Temp  CO

2

 ppm and temperature both 

 

displayed at the same time

Rotate 

All available sensor readings rotate 

 

at 2 second intervals

None 

No measurement information is displayed in  

 

normal mode, the setpoint information will  

 

still be displayed in setpoint mode, the menu  

 

will still display in Setup Menu mode

10. TEMPERATURE OFFSET

7. TEMPERATURE UNITS

8. DISPLAY

Output

Test OFF

The Output Test value controls the analog output signal for testing purposes. 

Use <UP> or <DOWN> to toggle the output signal to OFF (normal operation), 

MIN (minimum output) or MAX (maximum output). The actual output signal will 

depend on the PCB switch position (mA or VOLT) and the V Output setting (for 

voltage operation). Press <MENU> to set it back to OFF and advance. Factory 

default is OFF.

<MENU> 

Press to advance to next menu item

6. OUTPUT TEST

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

IN-GE-CD2RMCXXX-04

Summary of Contents for CD2RMC Series

Page 1: ...r conditioned spaces contact factory or other applications Do not exceed device ratings This product is not intended for life safety applications NOTE This CO2 sensor incorporates a Self Calibration feature to correct CO2 sensor drift This feature is recommended for applications where the CO2 will be exposed to fresh air 400 ppm at least one hour per day If the monitored space is occupied 24 hours...

Page 2: ...he enclosure and complete the wiring connection according to the wiring diagram Figure 6 This is a 3 wire sourcing device Connect the plus DC or the AC voltage hot side to the PWR terminal and the common is connected to the COM terminal The device is reverse voltage protected and will not operate if connected backwards It has a half wave power supply so the supply common is the same as the signal ...

Page 3: ...s required If the optional temperature sensor is installed the relay operation may be assigned to operate as a temperature high or low alarm instead of a CO2 alarm All the same relay parameters may be configured to set up the alarm as required SETPOINT MODE The optional setpoint control is operated by two front panel switches for UP and DOWN and the resistive output signal simulates a slidepot act...

Page 4: ... required Factory default is Direct MENU Press to advance to next menu item 5 OUTPUT SIGNAL DIRECTION When either the UP or DOWN keys are pressed the LCD temporarily changes to display the temperature setpoint value in C or F as set by Temp Units in the Setup Menu The display will show the previous temperature setpoint setting such as 22 ºC or 77 ºF If no other action is taken for 5 seconds then t...

Page 5: ...installed Factory default is C Display is used to control what information is displayed on the LCD The selections depend on the installed options Use UP or DOWN to select either CO2 ppm Temp CO2 Temp Rotate or None Factory default is CO2 ppm For a basic CO2 only device the selection is limited to CO2 ppm or None CO2 ppm Only the actual ppm value of the CO2 reading will be displayed Temp Only tempe...

Page 6: ...es in 1 minute increments to prevent false alarms The default is 0 minutes no delay Use UP or DOWN to toggle the relay ON or OFF to test the relay operation Press MENU to reset to OFF and advance or or 12 RELAY SETPOINT 13 RELAY HYSTERESIS 14 RELAY DELAY 15 RELAY TEST RELAY ASSIGNMENT DEFAULT SETPOINT SETPOINT RANGE RESOLUTION Temp High 26 0 C 79 0 F 5 0 to 40 0 C 40 0 to 100 0 F 0 5 Temp Low 15 0...

Page 7: ...several minutes and then press and hold UP or down button for five seconds until display shows Calibrat Done or Calibrat Fail Refer to Calibration section in this document for more details MENU Press to exit the menu and return to normal mode MENU Press to exit the menu and return to normal mode 19 CO2 CALIBRATION 20 CO2 CALIBRATION CALIBRATION Calibration with gas requires a field calibration kit...

Page 8: ...racter OPTIONAL TEMPERATURE SENSOR Type Various Thermistors and RTDs Accuracy Thermistors 0 2 C 0 36 F 25 C 77 F Platinum RTD s 0 3 C 0 54 F 0 C 32 F Nickel RTD s 0 4 C 0 72 F 0 C 32 F Range 0 to 50 C 32 to 122 F Output 2 wire resistive Relay Optional 2 wire output Form A N O 2 Amps 140 Vac 30 Vdc Override Switch Optional 2 wire output 50 mA 12 Vdc max OPTIONAL SETPOINT CONTROL Type Front panel up...

Reviews: