SPECIFICATIONS

Gas Type Detected .................................................Carbon dioxide (CO

2

)

Sensor Type ..............................................................Dual channel non-dispersive infrared (NDIR)

Sensor Accuracy ......................................................± (30 ppm + 3% of measured value)

Measurement Range .............................................0-2000 ppm (default), adjustable 1000-10,000 ppm

Temperature Dependency ..................................±2.5 ppm/

°

C

Response Time ........................................................20 seconds (T63)

Warm-Up Time .........................................................1 minute

Sensor Coverage Area ...........................................100 m

2

(1000 ft

2

) typical

Sensor Life Span......................................................>15 years

Transmitter Accuracy ............................................±0.25% of span

 

(including linearity, hysteresis and repeatability)

Power Supply ...........................................................24 Vdc ±20% or 24 Vac ±10%

 

(non-isolated half-wave rectified)

Protection Circuitry ................................................Reverse voltage and transient protected

Input Voltage Effect ...............................................Negligible over specified operating range

Output Signal Type ................................................4-20 mA (3-wire), 0-5 or 0-10 Vdc (field selectable)

Current Consumption ...........................................

Current:

 75 mA @ 24 Vdc max, 150 mA @ 24 Vac max

 

Voltage:

 50 mA @ 24 Vdc max, 100 mA @ 24 Vac max

Output Drive @ 24 Vdc .........................................

Current:

 550Ω max

 

Voltage:

 10,000Ω min

Ambient Operating Range ..................................0 to 50°C (32 to 122°F), 0 to 95 %RH non-condensing

Storage Conditions ................................................-40 to 70°C (-40 to 158°F)

LCD Display Units ...................................................ppm (CO

2

), °C/°F (optional temperature/setpoint)

Display Range ..........................................................0-10000 ppm, 0 to 50°C / 32 to 122°F

Display Size ...............................................................35mm W x 15mm H (1.4" x 0.6")

Digit Height ..............................................................2-line x 8 character

OPTIONAL TEMPERATURE SENSOR

Type .............................................................................Various Thermistors and RTDs

Accuracy ....................................................................

Thermistors:

 ±0.2°C (±0.36°F) @ 25°C (77°F)

 

Platinum RTD's:

 ±0.3°C (±0.54°F) @ 0°C (32°F)

 

Nickel RTD's:

 ±0.4°C (±0.72°F) @ 0°C (32°F)

Range ..........................................................................0 to 50°C (32 to 122°F)

Output ........................................................................2-wire resistive

Relay (Optional 2-wire output) ..........................Form A (N.O.), 2 Amps @ 140 Vac / 30 Vdc

Override Switch (Optional 2-wire output) .....50 mA @ 12 Vdc max

OPTIONAL SETPOINT CONTROL

Type .............................................................................Front panel up/down pushbuttons

Range ..........................................................................±10 resistive steps, range 16 to 26°C in 0.5°C increments or 

 

60 to 80°F in 1°F increments

Midpoint ....................................................................Default 21°C/70°F, programmable 18 to 25°C (64 to 77°F)

Resolution .................................................................Programmable 0.5 / 1°C/°F

Action .........................................................................Programmable direct or reverse acting

Enclosure ...................................................................White ABS, IP30 (NEMA 1)

 

84mm W x 119mm H x 29mm D (3.3" x 4.7" x 1.15")

Wiring .........................................................................Screw terminal block (14 - 22 AWG)

Approvals ..................................................................CE

Country of Origin .......................................................Canada

Enter the Setup Menu and use the <MENU> key to advance to the “Calibrat” item. Press and hold either 

the <UP> or <DOWN> key for 5 seconds to start the gas calibration. The LCD will indicate “Calibrat 

/ Done” if the process was successful. If “Calibrat / Fail” is displayed then the process may have to be 

repeated. Press the <MENU> key to return to normal operation, shut off the gas supply and remove the 

sensor adapter.

DIMENSIONS

84mm

3.3"

58mm

2.3"

82.6mm

3.25"

29mm

1.15"

119mm

4.7"

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

IN-GE-CD2RMCXXX-04

Summary of Contents for CD2RMC Series

Page 1: ...r conditioned spaces contact factory or other applications Do not exceed device ratings This product is not intended for life safety applications NOTE This CO2 sensor incorporates a Self Calibration feature to correct CO2 sensor drift This feature is recommended for applications where the CO2 will be exposed to fresh air 400 ppm at least one hour per day If the monitored space is occupied 24 hours...

Page 2: ...he enclosure and complete the wiring connection according to the wiring diagram Figure 6 This is a 3 wire sourcing device Connect the plus DC or the AC voltage hot side to the PWR terminal and the common is connected to the COM terminal The device is reverse voltage protected and will not operate if connected backwards It has a half wave power supply so the supply common is the same as the signal ...

Page 3: ...s required If the optional temperature sensor is installed the relay operation may be assigned to operate as a temperature high or low alarm instead of a CO2 alarm All the same relay parameters may be configured to set up the alarm as required SETPOINT MODE The optional setpoint control is operated by two front panel switches for UP and DOWN and the resistive output signal simulates a slidepot act...

Page 4: ... required Factory default is Direct MENU Press to advance to next menu item 5 OUTPUT SIGNAL DIRECTION When either the UP or DOWN keys are pressed the LCD temporarily changes to display the temperature setpoint value in C or F as set by Temp Units in the Setup Menu The display will show the previous temperature setpoint setting such as 22 ºC or 77 ºF If no other action is taken for 5 seconds then t...

Page 5: ...installed Factory default is C Display is used to control what information is displayed on the LCD The selections depend on the installed options Use UP or DOWN to select either CO2 ppm Temp CO2 Temp Rotate or None Factory default is CO2 ppm For a basic CO2 only device the selection is limited to CO2 ppm or None CO2 ppm Only the actual ppm value of the CO2 reading will be displayed Temp Only tempe...

Page 6: ...es in 1 minute increments to prevent false alarms The default is 0 minutes no delay Use UP or DOWN to toggle the relay ON or OFF to test the relay operation Press MENU to reset to OFF and advance or or 12 RELAY SETPOINT 13 RELAY HYSTERESIS 14 RELAY DELAY 15 RELAY TEST RELAY ASSIGNMENT DEFAULT SETPOINT SETPOINT RANGE RESOLUTION Temp High 26 0 C 79 0 F 5 0 to 40 0 C 40 0 to 100 0 F 0 5 Temp Low 15 0...

Page 7: ...several minutes and then press and hold UP or down button for five seconds until display shows Calibrat Done or Calibrat Fail Refer to Calibration section in this document for more details MENU Press to exit the menu and return to normal mode MENU Press to exit the menu and return to normal mode 19 CO2 CALIBRATION 20 CO2 CALIBRATION CALIBRATION Calibration with gas requires a field calibration kit...

Page 8: ...racter OPTIONAL TEMPERATURE SENSOR Type Various Thermistors and RTDs Accuracy Thermistors 0 2 C 0 36 F 25 C 77 F Platinum RTD s 0 3 C 0 54 F 0 C 32 F Nickel RTD s 0 4 C 0 72 F 0 C 32 F Range 0 to 50 C 32 to 122 F Output 2 wire resistive Relay Optional 2 wire output Form A N O 2 Amps 140 Vac 30 Vdc Override Switch Optional 2 wire output 50 mA 12 Vdc max OPTIONAL SETPOINT CONTROL Type Front panel up...

Reviews: