background image

Page  1

INTRODUCTION

The carbon dioxide transmitter uses Infrared Technology to monitor 

CO

2

 levels within a range of 0 - 2000 ppm. Options include a control 

relay, override switch, up/down set-point control, relative humidity 

sensor and temperature sensor.

The device includes native BACnet® protocol with 15 BACnet® 

objects and an RS-485 MS/TP network connection to offer a single-

point solution for control of indoor air quality and comfort. Features 

include a back-lit LCD and user menu for easy installation, field-

proven RH sensor and user input controls to add local set-point 

and override functions at the same network point.

BEFORE INSTALLATION

Read these instructions carefully before installing and commissioning the device. Failure to follow these 

instructions may result in product damage. Do not use in an explosive or hazardous environment, with 

combustible or flammable gases, as a safety or emergency stop device or in any other application where 

failure of the product could result in personal injury. Take electrostatic discharge precautions during 

installation. 

Do not exceed device ratings.

MOUNTING

The transmitter installs directly on a standard electrical box and should be mounted five feet from the floor 

of the area to be controlled. Do not mount the sensor near doors, opening windows, supply air diffusers or 

other known disturbances. Avoid areas where the detector is exposed to vibrations or rapid temperature 

changes.

The cover is hooked to the base at the top edge and must be removed from the bottom edge first. Use a small 

Phillips screwdriver to loosen the security screw as shown in Figure 1. 

Complete removal of the screw is not required. Use the screwdriver to 

carefully pry each bottom corner if necessary. Tip the cover away from 

the base and sit it aside as shown in Figure 2.

Sit the PCB aside until the base is mounted on the wall. For added 

protection, place the PCB in the supplied anti-static bag.

Mount the base by screwing to an electrical box or directly to the wall 

as shown in Figure 4. The mounting hole locations are shown on page 

4.

After the base is screwed to an electrical box or directly to the wall 

using the appropriate holes, remove the PCB from the anti-static bag, 

feed connection wires through the center hole and place the top of 

the PCB into the PCB holders on the backplate and snap the bottom of 

the PCB into place as shown in Figure 4.

Making wiring connections as per the Wiring Illustrations on page 2 

and install the decorative cover by placing the top of the cover into 

the cover holder on the top of the backplate and snapping the bottom 

into place as shown in Figure 4. Tighten  the security screw with a 

Phillips screwdriver.

Figure 1

Figure 2

Figure 4

Figure 3

Cover

PCB

Backplate

IN-GE-CDD3A1XXXBAC-03

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Room Carbon Dioxide  

Transmitter with BACnet

®

CDD3A1 Series - Installation Instructions

Summary of Contents for CDD3A1 Series

Page 1: ...etector is exposed to vibrations or rapid temperature changes Thecoverishookedtothebaseatthetopedgeandmustberemovedfromthebottomedgefirst Useasmall Phillips screwdriver to loosen the security screw as shown in Figure 1 Complete removal of the screw is not required Use the screwdriver to carefully pry each bottom corner if necessary Tip the cover away from the base and sit it aside as shown in Figu...

Page 2: ...es in a daisy chain configuration The total segment length should be less than 4000 feet 1220 meters and the maximum number of nodes on one segment length is 64 Nodes are any device connected to the loop and include controllers but do not include the EOL terminators To install more than 64 devices or to increase network length repeaters will be required for proper communication The maximum daisy c...

Page 3: ...he menu Various options are available such as temperature ranges in C or F RH values or ppm values See the Setup Menu section for more details Changing the scale in the menu will affect the BACnet object and the LCD display of the set point values If the device has the optional Override switch installed pressing the OVERRIDE key will cause the LCD to change to show the override status The display ...

Page 4: ...ault is for 0 100 10 steps This can be changed to one of the following selections C1 for 18 24 C set point 0 5 C steps C2 for 10 45 C set point 0 5 C steps F1 for 67 73 F set point 1 F steps F2 for 50 113 F set point 1 F steps RH for 30 70 RH set point 1 RH steps ppm for 500 1500 ppm set point 50 ppm steps MENU Press to advance to next menu item SAVE Press to exit the menu and return to normal ope...

Page 5: ... 15 seconds typical Stability 1 2 RH typical 50 RH in 5 years OPTIONAL RELAY OUTPUT Contact Ratings Form A contact N O 2 Amps 140 Vac 2 Amps 30 Vdc Relay Trip Point Programmable 500 to 1500 ppm via BACnet Relay Hysteresis Programmable 25 to 200 ppm via BACnet GENERAL Power Supply 20 to 28 Vac dc non isolated half wave rectified Consumption 80 mA max 24 Vdc 140 mA max 24 Vac with all options Protec...

Reviews: