background image

Page  2

WIRING

Deactivate the 24 Vac/dc power supply until all connections are made 

to the device to prevent electrical shock or equipment damage. 

Follow proper electrostatic discharge (ESD) handling procedures 

when installing the device or equipment damage may occur.

Use 22 AWG shielded wiring for all connections and do not locate the 

device wires in the same conduit with wiring used to supply inductive 

loads such as motors. Connect the cable shield to ground at the 

controller only. Make all connections in accordance with national and 

local codes.

Connect the 24 Vac/dc power supply to the terminals labeled POWER 

and COMMON. Use caution if 24 Vac power is used and one side of 

the transformer is earth grounded. In general, the transformer should 

NOT be connected to earth ground when using devices with RS-485 network connections. The device is 

reverse voltage protected and will not operate if connected backwards.

Connect the RS-485 network with twisted shielded pair to the terminals marked A(-), B(+) and SHIELD. 

The positive wire connects to B(+) and the negative wire connects to A(-) and the cable shield must be 

connected to the SHIELD terminal on each device. If the device is installed at either end of an RS-485 

network, and end-of-line (EOL) termination resistor (121 Ω) should be installed in parallel to the A(-) and 

B(+) terminals. This device includes a network termination jumper and will connect the (121 Ω) resistor 

correctly on the PCB. Simply move the jumper to the EOL position and no external resistor is required. The 

ground wire of the shielded pair should be connected to earth ground at the end of the network and the 

master is not grounded. Do not run bus wiring in the same conduit as line voltage wiring or other wiring 

that switches power to highly inductive loads such as contactors, coils, or motors.

A network segment is a single shielded wire loop run between several devices (nodes) in a daisy chain 

configuration. The total segment length should be less than 4000 feet (1220 meters) and the maximum 

number of nodes on one segment length is 64. Nodes are any device connected to the loop and include 

controllers but do not include the EOL terminators. To install more than 64 devices, or to increase network 

length, repeaters will be required for proper communication. The maximum daisy chain length (segment) 

depends on transmission speed (baud rate), wire size and number of nodes. If communication is slow or 

unreliable, it may be necessary to wire two daisy chains to the controller with a repeater for each segment.

An optional signal is the relay output available on the N. OPEN and RELAY COM terminals. The RELAY COM 

terminal is NOT connected to the power supply COMMON terminal. The relay output is completely isolated 

and has a Normally Open (NO) signal. This signal can be used to directly control an alarm or ventilation fan.

SET-UP

The device parameters must be set before connection to the network and will ensure each device will have 

a unique MAC address and Device Instance for start-up.  On start-up, the MAC address is appended to the 

Device Object: Vendor Identifier to create the unique Device Instance (Device Object : Object Identifier). 

Once connected to a network, the Device Object : Object Identifier can be written to any unique value via 

BACnet® and then the MAC address will no longer be appended to the value. Once set, all parameters are 

saved in non-volatile memory. The local menu and LCD are used to set the BACnet® MAC device address 

(0-127) and the baud. The menu and set-up procedure is described in the Start-up section.

Figure 5

Figure 6

Building Controller

Device 01

Device 02

Device 03

Set EOL Jumper

Connect Shield

One End Only

Power

COMMON

Power

COMMON

Power

COMMON

A(-)

B(+)

SHLD

A(-)

B(+)

SHLD

A(-)

B(+)

SHLD

BACnet® Master

24 Vac / dc

Common

A(-)

B(+)

Shield

EOL

DOWN

A-

B+

SHIELD

COMMON

POWER

UP

SAVE

MENU

N. OPEN

RELAY COM

RELAY

CO2 SENSOR

0001246

EOL

IN-GE-CDD3A1XXXBAC-03

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for CDD3A1 Series

Page 1: ...etector is exposed to vibrations or rapid temperature changes Thecoverishookedtothebaseatthetopedgeandmustberemovedfromthebottomedgefirst Useasmall Phillips screwdriver to loosen the security screw as shown in Figure 1 Complete removal of the screw is not required Use the screwdriver to carefully pry each bottom corner if necessary Tip the cover away from the base and sit it aside as shown in Figu...

Page 2: ...es in a daisy chain configuration The total segment length should be less than 4000 feet 1220 meters and the maximum number of nodes on one segment length is 64 Nodes are any device connected to the loop and include controllers but do not include the EOL terminators To install more than 64 devices or to increase network length repeaters will be required for proper communication The maximum daisy c...

Page 3: ...he menu Various options are available such as temperature ranges in C or F RH values or ppm values See the Setup Menu section for more details Changing the scale in the menu will affect the BACnet object and the LCD display of the set point values If the device has the optional Override switch installed pressing the OVERRIDE key will cause the LCD to change to show the override status The display ...

Page 4: ...ault is for 0 100 10 steps This can be changed to one of the following selections C1 for 18 24 C set point 0 5 C steps C2 for 10 45 C set point 0 5 C steps F1 for 67 73 F set point 1 F steps F2 for 50 113 F set point 1 F steps RH for 30 70 RH set point 1 RH steps ppm for 500 1500 ppm set point 50 ppm steps MENU Press to advance to next menu item SAVE Press to exit the menu and return to normal ope...

Page 5: ... 15 seconds typical Stability 1 2 RH typical 50 RH in 5 years OPTIONAL RELAY OUTPUT Contact Ratings Form A contact N O 2 Amps 140 Vac 2 Amps 30 Vdc Relay Trip Point Programmable 500 to 1500 ppm via BACnet Relay Hysteresis Programmable 25 to 200 ppm via BACnet GENERAL Power Supply 20 to 28 Vac dc non isolated half wave rectified Consumption 80 mA max 24 Vdc 140 mA max 24 Vac with all options Protec...

Reviews: