background image

Page  2

Mount the base by screwing to an electrical box or directly to the wall as shown in Figure 4.

After the base is screwed to an electrical box or directly to the wall using the appropriate holes, remove the 

PCB from the anti-static bag, feed connection wires through the center hole and place the top of the PCB 

into the PCB holders on the backplate and snap the bottom of the PCB into place as shown in Figure 4.

Making wiring connections as per the Wiring Illustrations below and install the decorative cover by placing 

the top of the cover into the cover holder on the top of the backplate and snapping the bottom into place 

as shown in Figure 4. Tighten  the security screw with a Phillips screwdriver.

WIRING

Deactivate the 24 Vac/dc power supply until all connections are made 

to the device to prevent electrical shock or equipment damage. Follow 

proper electrostatic discharge (ESD) handling procedures when installing 

the device or equipment damage may occur. Use 22 AWG shielded 

wiring for all connections and do not locate the device wires in the same 

conduit with wiring used to supply inductive loads such as motors. Make 

all connections in accordance with national and local codes.

This is a 3-wire sourcing device. Connect the plus dc or the ac voltage 

hot side to the PWR terminal. The supply common is connected to the 

COM terminal. The device is reverse voltage protected and will not 

operate if connected backwards. It has a half-wave power supply so 

the supply common is the same as the signal common. Several devices 

may be connected to one power supply and the output signals all share 

the same common. Use caution when grounding the secondary of a 

transformer or when wiring multiple devices to ensure the ground point 

is the same on all devices and the controller.

The analog output is available on the CO

2

 terminal. This signal 

is switch selectable for either voltage or 4-20 mA active output 

as shown in Figure 7. In voltage mode the output is selectable 

for either 0-5 or 0-10 Vdc later during the menu setup (the 

factory default is 0-5 Vdc). The current output operates in the 

active mode and does not require a loop power supply (the 

signal current is generated by the transmitter and must not be 

connected to a powered input or device damage will result).

Check the controller Analog Input to determine the proper 

connection before applying power. Both current and voltage 

signals are referenced to the COM terminal. The analog 

output signal is typically connected directly to the Building 

Automation System (B.A.S.) and used as a control parameter 

or for logging purposes.

Figure 5

Figure 7

Figure 8

Figure 9

Figure 10

Figure 6

Power Supply

Wiring for voltage output signal 

and 24 Vdc power from controller

Wiring for all output and external 24 Vac power 

transformer or external 24 Vac power supply

CO

2

COM

PWR

N.O.

RELAY

S COM

SWITCH

+

-

CO

2

COM

PWR

0-5 or 0-10 Vdc AI

COMMON

+24 Vdc

COMMON

Digital Input

COMMON

Digital Input

Analog Input

COMMON

Analog Input

COMMON

COMMON

24 Vac

Controller

Alarm

Controller

Controller

24 Vac Transformer / 

Power Supply

mA

VOLT

Current

4-20 mA

Voltage

0-5 or 0-10 Vdc

VOLT

mA

0001248

CO2 SENSOR

ROLL

SAVE

MENU

OVERRIDE

TEMP

CO2

COM

PWR

S COM

SWITCH

N.O.

RELAY

OUTPUT

mA

VOLT

SWITCH

TEMP

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

IN-GE-CDD4B1XXX-01 05/20

Summary of Contents for CDD4B1 Series

Page 1: ...s not intended for life safety applications MOUNTING The transmitter installs directly on a standard electrical box and should be mounted five feet from the floor of the area to be controlled Do not mount the sensor near doors opening windows supply air diffusers or other known disturbances Avoid areas where the detector is exposed to vibrations or rapid temperature changes Prevent measurement err...

Page 2: ...t signals all share the same common Use caution when grounding the secondary of a transformer or when wiring multiple devices to ensure the ground point is the same on all devices and the controller The analog output is available on the CO2 terminal This signal is switch selectable for either voltage or 4 20 mA active output as shown in Figure 7 In voltage mode the output is selectable for either ...

Page 3: ...ue is used to control output ventilation devices or initiate alarms The CO2 value is also displayed locally on the optional LCD If a relay is installed it can control a small fan or alarm by setting the trip value and hysteresis to appropriate values If a temperature sensor is installed it will be wired to an analog input of the BAS that is set for the specific resistance type This could be a 10 K...

Page 4: ...g purposes Press either SAVE or MENU to turn the relay o and advance to the next item 5 RELAY TEST This item is used for 0 ppm gas calibration and is explained in the Calibration section This item is used for 1000 ppm gas calibration and is explained in the Calibration section Calibrat 0 PPM Calibrat 1000 PPM MENU Press to exit the menu and return to normal mode MENU Press to exit the menu and ret...

Page 5: ...he chamber after the plastic cap is removed Gently remove one cap and connect the tubing note that strong shock or vibration can affect calibration Ensure the device has been operating normally for at least five minutes before applying gas Turn the valve knob on the regulator to start the gas flow The regulator will restrict the flow rate to the specified 100 ml min After a brief period the gas wi...

Page 6: ...Vac with all options Output Signals 4 20 mA active sourcing 0 5 Vdc or 0 10 Vdc field selectable Output Drive Capability Current 550Ω maximum Voltage 5 000Ω minimum Protection Circuitry Reverse voltage protected over voltage protected Operating Conditions 0 to 50 C 32 to 122 F 0 t 95 RH non condensing Wiring Connections Screw terminal block 14 to 22 AWG Sensor Coverage Area 100 m2 1000 ft2 typical...

Page 7: ...IN CANADA Page 7 DIMENSIONS 84mm 3 3 58mm 2 3 82 6mm 3 25 29mm 1 15 119mm 4 7 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com IN GE CDD4B1XXX 01 05 20 ...

Reviews: