Press the <SAVE> key to restore calibration to original factory settings.

Press <SAVE> to exit the menu and return to normal operation or <MENU> to 

repeat the menu.

<MENU> 

Press to advance to next menu item

12. RESTORE DEFAULTS

13. MENU EXIT

Only if 

Viewable LCD

 option Installed

BackLite

Enable

Use the <ROLL> key to enable or disable the LCD backlight. When enabled the 

backlight is always on, when disabled it never lights. Press the <SAVE> key to 

save the setting. The factory default is Enable.

11. BACKLIGHT

<MENU> 

Press to exit the menu and return to normal mode

CALIBRATION

Calibration with gas requires a field calibration kit with pressure regulator, necessary tubing and 

appropriate bottles of CO

2

 gas.

The dual-channel sensor with extended range requires a 3-point calibration with 0, 1000 and 20,000 

ppm gas (in order).

0 PPM CALIBRATION

Turn the regulator knob off and attach it to the Nitrogen gas bottle and hand tighten. Remove the cover 

of the unit to be calibrated to expose the gas sensor chamber. The tubing from the gas bottle can be 

connected to either port on the chamber after the plastic cap is removed. Gently remove one cap and 

connect the tubing, note that strong shock or vibration can affect calibration.

Ensure the device has been operating normally for at least five minutes before applying gas. Turn the 

valve knob on the regulator to start the gas flow. The regulator will restrict the flow rate to the specified 

100 ml/min. After a brief period the gas will flow into the chamber. Wait 1 to 2 minutes until the CO

2

 

reading stabilizes.

Enter the Setup menu and use the <MENU> key to advance to Calibrat 0 PPM. Press and hold the 

<SAVE> key for 2 seconds and the display will change to Waiting Calibrat then to Waiting 5 minute to 

indicate that the process of setting the internal calibration is taking place.

This takes about 5 minutes while the LCD counts down. Do not disturb the unit or the gas flow. When 

complete the unit will display the ppm value and Cal Done. Press the <SAVE> key to return to normal 

operation and shut the gas off.

This item is used for 20,000 ppm gas calibration and is explained in the Calibration 

section.

Calibrat

20000 PPM

<MENU> 

Press to exit the menu and return to normal mode

10. CO

2

 CALIBRATION

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

IN-GE-CDD4B1XXX-01 05/20

Summary of Contents for CDD4B1 Series

Page 1: ...s not intended for life safety applications MOUNTING The transmitter installs directly on a standard electrical box and should be mounted five feet from the floor of the area to be controlled Do not mount the sensor near doors opening windows supply air diffusers or other known disturbances Avoid areas where the detector is exposed to vibrations or rapid temperature changes Prevent measurement err...

Page 2: ...t signals all share the same common Use caution when grounding the secondary of a transformer or when wiring multiple devices to ensure the ground point is the same on all devices and the controller The analog output is available on the CO2 terminal This signal is switch selectable for either voltage or 4 20 mA active output as shown in Figure 7 In voltage mode the output is selectable for either ...

Page 3: ...ue is used to control output ventilation devices or initiate alarms The CO2 value is also displayed locally on the optional LCD If a relay is installed it can control a small fan or alarm by setting the trip value and hysteresis to appropriate values If a temperature sensor is installed it will be wired to an analog input of the BAS that is set for the specific resistance type This could be a 10 K...

Page 4: ...g purposes Press either SAVE or MENU to turn the relay o and advance to the next item 5 RELAY TEST This item is used for 0 ppm gas calibration and is explained in the Calibration section This item is used for 1000 ppm gas calibration and is explained in the Calibration section Calibrat 0 PPM Calibrat 1000 PPM MENU Press to exit the menu and return to normal mode MENU Press to exit the menu and ret...

Page 5: ...he chamber after the plastic cap is removed Gently remove one cap and connect the tubing note that strong shock or vibration can affect calibration Ensure the device has been operating normally for at least five minutes before applying gas Turn the valve knob on the regulator to start the gas flow The regulator will restrict the flow rate to the specified 100 ml min After a brief period the gas wi...

Page 6: ...Vac with all options Output Signals 4 20 mA active sourcing 0 5 Vdc or 0 10 Vdc field selectable Output Drive Capability Current 550Ω maximum Voltage 5 000Ω minimum Protection Circuitry Reverse voltage protected over voltage protected Operating Conditions 0 to 50 C 32 to 122 F 0 t 95 RH non condensing Wiring Connections Screw terminal block 14 to 22 AWG Sensor Coverage Area 100 m2 1000 ft2 typical...

Page 7: ...IN CANADA Page 7 DIMENSIONS 84mm 3 3 58mm 2 3 82 6mm 3 25 29mm 1 15 119mm 4 7 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com IN GE CDD4B1XXX 01 05 20 ...

Reviews: