1000 PPM CALIBRATION

Connect the 1000 ppm CO

2

 gas bottle and apply the gas as before. The CO

2

 reading on the LCD will begin 

to approach 1000 ppm. Wait 1 to 2 minutes until the CO

2

 reading stabilizes.

Enter the Setup menu and use the <MENU> key to advance to Calibrat 1000 PPM. Press and hold the 

<SAVE> key for 2 seconds and the display will change to Waiting Calibrat then to Waiting 5 minute 

to indicate that the device is calibrating. Again, this process takes about 5 minutes. When calibration 

is complete the unit will display the ppm and Cal Done. Press the <SAVE> key to return to normal 

operation and shut the gas off.

20,000 PPM CALIBRATION

Connect the 20,000 ppm CO2 and apply the gas as before. The LCD will begin to approach 20,000 ppm. 

Wait 1 to 2 minutes until the CO2 reading stabilizes. 

Enter the Setup menu and use the <MENU> key to advance to Calibrat 20,000 PPM. Press and hold the 

<SAVE> key for 2 seconds and the display will change to Waiting Calibrat then to Waiting 5 minute.

Again, wait 5 minutes and when calibration is complete the unit will display the ppm and Cal Done. Press 

the <SAVE> key to return to normal operation and shut the gas off.

Disconnect the tubing and replace the cap on the sensor chamber as calibration is complete.

SPECIFICATIONS

Power Supply ...........................................................20 - 28 Vac/dc (non-isolated half-wave rectified)

Consumption ...........................................................100 mA max @ 24 Vdc, 185 mA max @ 24 Vac (with all options)

Output Signals .........................................................4-20 mA active (sourcing), 0-5 Vdc or 0-10 Vdc (field selectable)

Output Drive Capability .......................................

Current:

 550Ω maximum

 

Voltage:

 5,000Ω minimum

Protection Circuitry ................................................Reverse voltage protected, over-voltage protected

Operating Conditions ...........................................0 to 50°C (32 to 122°F), 0 t 95 %RH non-condensing

Wiring Connections ...............................................Screw terminal block (14 to 22 AWG)

Sensor Coverage Area ...........................................100 m

2

 (1000 ft

2

) typical

Enclosure ...................................................................Wall mount enclosure, 84mm W x 119mm H x 29mm D 

 

(3.3" x 4.7" x 1.15")

Approvals ..................................................................CE

Country of Origin .......................................................Canada

CO2 SIGNAL

Measurement Type ................................................Dual-Wavelength, Non-Dispersive Infrared (NDIR)

 

diffusion sampling

Measurement Range .............................................0 to 20,000 ppm, programmable span

Standard Accuracy .................................................±75 ppm or 10% of reading (whichever is greater)

Temperature Dependence ..................................0.2 %F.S. per °C

Stability ......................................................................<5 %F.S. or <10% reading annual

Pressure Dependence ...........................................0.135% of reading per mm Hg

Altitude Correction ................................................Programmable from 0 to 5000 ft via keypad

Response Time ........................................................<2 minutes for 90% step change

Warm-up Time .........................................................<2 minutes

LCD DISPLAY

Resolution .................................................................1 ppm CO

2

Size ...............................................................................35mm x 15mm (1.4" x 0.6") alpha-numeric 2 line x 8 character

OPTIONAL TEMPERATURE SENSOR

Sensing Element .....................................................Various RTDs and thermistors available as

 

2-wire resistance output

CONTACT RATINGS

Contact Ratings .......................................................Form A contact (N.O.), 2 Amps @ 140 Vac, 2 Amps @ 30 Vdc

Relay Trip Point ........................................................Programmable via keypad

Relay Hysteresis.......................................................Programmable via keypad

OPTIONAL MANUAL SWITCH

Type .............................................................................Front panel, momentary pushbutton

Ratings ........................................................................50 mA @ 12 Vdc, N.O., SPST

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

IN-GE-CDD4B1XXX-01 05/20

Summary of Contents for CDD4B1 Series

Page 1: ...s not intended for life safety applications MOUNTING The transmitter installs directly on a standard electrical box and should be mounted five feet from the floor of the area to be controlled Do not mount the sensor near doors opening windows supply air diffusers or other known disturbances Avoid areas where the detector is exposed to vibrations or rapid temperature changes Prevent measurement err...

Page 2: ...t signals all share the same common Use caution when grounding the secondary of a transformer or when wiring multiple devices to ensure the ground point is the same on all devices and the controller The analog output is available on the CO2 terminal This signal is switch selectable for either voltage or 4 20 mA active output as shown in Figure 7 In voltage mode the output is selectable for either ...

Page 3: ...ue is used to control output ventilation devices or initiate alarms The CO2 value is also displayed locally on the optional LCD If a relay is installed it can control a small fan or alarm by setting the trip value and hysteresis to appropriate values If a temperature sensor is installed it will be wired to an analog input of the BAS that is set for the specific resistance type This could be a 10 K...

Page 4: ...g purposes Press either SAVE or MENU to turn the relay o and advance to the next item 5 RELAY TEST This item is used for 0 ppm gas calibration and is explained in the Calibration section This item is used for 1000 ppm gas calibration and is explained in the Calibration section Calibrat 0 PPM Calibrat 1000 PPM MENU Press to exit the menu and return to normal mode MENU Press to exit the menu and ret...

Page 5: ...he chamber after the plastic cap is removed Gently remove one cap and connect the tubing note that strong shock or vibration can affect calibration Ensure the device has been operating normally for at least five minutes before applying gas Turn the valve knob on the regulator to start the gas flow The regulator will restrict the flow rate to the specified 100 ml min After a brief period the gas wi...

Page 6: ...Vac with all options Output Signals 4 20 mA active sourcing 0 5 Vdc or 0 10 Vdc field selectable Output Drive Capability Current 550Ω maximum Voltage 5 000Ω minimum Protection Circuitry Reverse voltage protected over voltage protected Operating Conditions 0 to 50 C 32 to 122 F 0 t 95 RH non condensing Wiring Connections Screw terminal block 14 to 22 AWG Sensor Coverage Area 100 m2 1000 ft2 typical...

Page 7: ...IN CANADA Page 7 DIMENSIONS 84mm 3 3 58mm 2 3 82 6mm 3 25 29mm 1 15 119mm 4 7 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com IN GE CDD4B1XXX 01 05 20 ...

Reviews: