WIRING

Use 22 AWG shielded wire for all connections and do not locate the device wires in the same conduit with 

wiring used to supply inductive loads such as motors. Disconnect the power supply before making any 

connections to prevent electrical shock or equipment damage. Make all connections in accordance with 

national and local codes.

Connect either an AC or DC power supply to POWER and COMMON and the 0-10 Vdc signal is available 

on the OUTPUT terminal with respect to COMMON as shown in Figure 4. The device is reverse voltage 

protected and will not operate if the power supply is connected backwards.

Ensure the controller Analog Input (AI) matches the transmitter output signal type before power is applied. 

The output signal has a minimum load that it will drive, follow the ratings in the Specification section or 

inaccurate readings may result.

If equipped, the relay output is available on the NO, NC and R.COM terminals. The relay R.COM terminal is 

NOT connected to the signal or power supply COMMON terminal. The relay output is completely isolated 

and has both Normally Open (NO) and Normally Closed (NC) signals. These signals can be used to directly 

control alarms, ventilation fans or may be connected to digital inputs of the B.A.S. for status monitoring.

OPERATION

In normal operation the sensor will measure the CO level in the 

surrounding air and output a proportional value on the 0-10 Vdc 

output. The CO measurement range is 0-300 ppm. An optional relay can 

be used to indicate an alarm condition. The trip point for the relay can 

be programmed to three different settings with an on-board jumper as 

shown in Figure 5. If the CO level exceeds the trip point then the relay is 

activated. The relay will remain activated until the CO level drops below 

the (trip level – hysteresis) where hysteresis is 3% or 9 ppm.

START-UP

Verify that the Carbon Monoxide Transmitter is properly wired according to the wiring diagrams and all 

connections are tight. Apply power to the device and the sensor will begin reading the CO level and output 

the analog signal.

Figure 4

Figure 5

HI
MID
LOW

RELAY TRIP

PWR

COM

OUT

NO
NC
R. COM

HI

MID

LOW

RELAY TRIP

SPAN

ZERO

CO

SENSOR

C W R

Analog Input for 4-20 mA CO Signal

Controller

24 Vac Power

Analog Input for

0-10 Vdc CO Signal

Hot

Com

PWR

COM

OUT

+

Controller

24 Vdc Power

PWR

COM

OUT

Analog Input for 

0-10 Vdc CO Signal

IN-GE-CMD5B1000XXX-002

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for CMD5B1000 Series

Page 1: ...gs MOUNTING The transmitter should be mounted on a flat surface three to five feet from the floor of the area to be controlled Do not mount the sensor near doors opening windows supply air diffusers or other known air disturbances Avoid areas with vibrations or rapid temperature changes The transmitter has two integrated mounting tabs on either side of the enclosure that facilitate a 10 size screw...

Page 2: ... used to directly control alarms ventilation fans or may be connected to digital inputs of the B A S for status monitoring OPERATION In normal operation the sensor will measure the CO level in the surrounding air and output a proportional value on the 0 10 Vdc output The CO measurement range is 0 300 ppm An optional relay can be used to indicate an alarm condition The trip point for the relay can ...

Page 3: ... at least 1 2 hour prior to calibration Calibrate the sensor first in clean air with no CO gas present Simply adjust the ZERO pot on the sensor board until a 0 Vdc output is obtained For this case adjust the output slightly above 0Vdc and then slowly reduce the output signal to 0Vdc The output signal may be monitored with a voltmeter connected to the OUTPUT and COMMON terminals Then attach the gas...

Page 4: ...Vdc 20 or 24 Vac 10 non isolated half wave rectified Consumption Relay model 40 mA max Non relay Model 20 mA max Output Signal 0 10 Vdc Output Drive Capability 10K Ω min Optional Relay Contacts Form C contacts N O and N C 5 Amps 250 Vac 5 Amps 30 Vdc Relay Trip Point 25 60 or 150 ppm jumper selectable Relay Hysteresis 3 or 9 ppm Wiring Connections Screw terminal block 14 to 22 AWG Enclosure Polyca...

Reviews: