background image

Page  3

CALIBRATION

The transmitter features a simple snap-mount sensor pcb that is pre-calibrated. This means that the entire 

sensor pcb can simply be replaced with a new calibrated pcb if desired without having to remove the 

enclosure. This sensor swap requires no tools and can be completed in seconds. Simply disconnect the 

device wiring, remove the old sensor pcb, snap in the new pcb and reconnect the device power. There is 

no need to make any adjustments or apply gas to the transmitter using the sensor swap method.

The device may also be calibrated or verified with CO gas if required. This requires a field calibration kit 

consisting of a bottle of gas (250 ppm CO in air for example), a tank pressure regulator with flow restrictor 

and the necessary tubing with a calibration cap to cover to the sensor. Calibration can be done at 20-27 C.

Verification with gas can be done without removing the device cover. Simply apply gas using the calibration 

cap attached directly to the port on the cover as shown in Figure 6 and monitor the output signal.

The device cover must be removed to perform an actual calibration. In this case, the gas calibration cap 

attaches to the sensor fixture inside the enclosure as shown in Figure 7. The sensor must be continuously 

powered for at least 1/2 hour prior to calibration. Calibrate the sensor first in clean air with no CO gas 

present. Simply adjust the ZERO pot on the sensor board until a  0 Vdc output is obtained. For this case, 

adjust the output slightly above 0 Vdc and then slowly reduce the output signal to 0 Vdc. The output signal 

may be monitored with a voltmeter connected to the OUTPUT and COMMON terminals.

Then attach the gas supply. Turn the regulator on/off knob fully off and attach it to the 250 ppm gas bottle 

and firmly tighten it by hand. Moisten the sponge and squeeze out any excess water. Place the sponge 

in the cap so that it will not touch the sensor but does not plug the hole in the side of the cap. Attach the 

cap to the fixture over the sensor. Slowly turn the valve knob on the regulator to let the gas begin flowing.

The regulator will restrict the flow rate to the specified 200 ml/min and the sponge will ensure the gas is 

in the right humidity range. Wait for 5 minutes and then adjust the SPAN pot on the sensor board until the 

output reads 250 ppm. For the 0-300 ppm device span, 250 ppm would equal 8.33 Vdc. Close the valve on 

the tank and take the cap off from the sensor. Calibration is complete.

If the gas cap is too loose on the fixtures, simply place a wrap of electrical tape around the cap to tighten it.

Figure 6

Figure 7

IN-GE-CMD5B1000XXX-002

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for CMD5B1000 Series

Page 1: ...gs MOUNTING The transmitter should be mounted on a flat surface three to five feet from the floor of the area to be controlled Do not mount the sensor near doors opening windows supply air diffusers or other known air disturbances Avoid areas with vibrations or rapid temperature changes The transmitter has two integrated mounting tabs on either side of the enclosure that facilitate a 10 size screw...

Page 2: ... used to directly control alarms ventilation fans or may be connected to digital inputs of the B A S for status monitoring OPERATION In normal operation the sensor will measure the CO level in the surrounding air and output a proportional value on the 0 10 Vdc output The CO measurement range is 0 300 ppm An optional relay can be used to indicate an alarm condition The trip point for the relay can ...

Page 3: ... at least 1 2 hour prior to calibration Calibrate the sensor first in clean air with no CO gas present Simply adjust the ZERO pot on the sensor board until a 0 Vdc output is obtained For this case adjust the output slightly above 0Vdc and then slowly reduce the output signal to 0Vdc The output signal may be monitored with a voltmeter connected to the OUTPUT and COMMON terminals Then attach the gas...

Page 4: ...Vdc 20 or 24 Vac 10 non isolated half wave rectified Consumption Relay model 40 mA max Non relay Model 20 mA max Output Signal 0 10 Vdc Output Drive Capability 10K Ω min Optional Relay Contacts Form C contacts N O and N C 5 Amps 250 Vac 5 Amps 30 Vdc Relay Trip Point 25 60 or 150 ppm jumper selectable Relay Hysteresis 3 or 9 ppm Wiring Connections Screw terminal block 14 to 22 AWG Enclosure Polyca...

Reviews: