Page 10
Alarm 1
Trip 50
Alarm 1
Trip 2
Press the <UP> or <DOWN> to change the Alarm1 Setpoint
within the limits. If Alarm1 is assigned to CO the range is 20 to
500 ppm in 10 ppm increments and default is 50 ppm. If Alarm1
is assigned to NO2 the range is 1 to 10 ppm in 1 ppm increments
and default is 2 ppm.
Only if
Relay1
is installed
16. ALARM 1
SETPOINT
Alarm 1
Hyst 10
Alarm 1
Hyst 0.5
Press the <UP> or <DOWN> to change the Alarm1 Hysteresis
within the limits. If the Alarm1 is assigned to CO the range is
10 to 100 ppm in 5 ppm increments and default is 10 ppm. If
Alarm1 is assigned to NO
2
the range is 0.5 to 2.0 ppm in 0.5 ppm
increments. The default is 0.5 ppm.
17. ALARM 1
HYSTERESIS
Alarm 1
Dly 2Min
Relay 1
Direct
Relay 1
Test OFF
Press the <UP> or <DOWN> to change the Alarm1 Delay time
within the limits. The delay time may be set from 0 to 10 minutes
in 1-minute increments. The default is 2 minutes.
Press the <UP> or <DOWN> to toggle the available options.
Relay 1 operation may be set to Direct or Reverse. Direct
operation means the relay is normally not energized and will
energize on an alarm condition (the NO/NC PCB designations
are correct). Reverse operation means the relay is normally
energized and will de-energize on an alarm condition (the NO/
NC PCB designations are reversed). Reverse operation can be
used for ‘Fail Safe’ operation as the relay will change state on
power loss. The default is Direct.
Press the <UP> or <DOWN> to toggle Relay1 ON or OFF to test
the relay operation.
18. ALARM 1
DELAY
19. RELAY
OPERATION
20. RELAY TEST
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
Alarm 2
CO
Press the <UP> or <DOWN> to scroll through the available
options. The available options are CO or NO
2
. Alarm 2 may be
assigned to either sensor. The default is CO.
Only if
Relay2 & 2 sensors
are installed
21. ALARM 2
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
Alarm 2
Trip 150
Alarm 2
Trip 4
Press the <UP> or <DOWN> to change the Alarm2 setpoint
within the limits. If Alarm2 is assigned to CO the range is 20
to 500 ppm in 10 ppm increments and default is 150 ppm. If
Alarm2 is assigned to NO
2
the range is 1 to 10 ppm in 1 ppm
increments. Default is 4 ppm.
22. ALARM 2
TRIP POINT
<MENU>
Press to advance to next menu item
IN-GE-GDTXXX-06