Page 14
<MENU>
Press to advance to next menu item
Use <UP> or <DOWN> to select a unique address from 0-127.
The default BACnet address is 3. Each device on the network
must have a unique address.
BACnet
MAC 3
40. ADDRESS
Only if
BACnet
®
model
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
Use <UP> or <DOWN> to toggle the voltage output type to
either 0-5 Vdc or 0-10 Vdc. The default is 0-5 Vdc.
Output
0-5 Vdc
38. OUTPUT
Only if
Output is Voltage
is installed
Use <UP> or <DOWN> to select a unique slave address from
1-255. The default Modbus slave address is 1. Each device on
the network must have a unique address.
ModBus
Addr 1
39. ADDRESS
Only if
Modbus
model
Use <UP> or <DOWN> to select either CO ppm, NO
2
ppm, CO + NO
2
, Temp,
CO + Temp, NO
2
+Temp, Status or None.
When set to CO ppm, only the actual ppm value of the CO reading will be
displayed on the LCD. When set to NO
2
ppm, only the NO
2
ppm reading will
be displayed and CO + NO
2
will display both values. If set to Temp, only the
temperature is displayed. If set to CO + Temp, then the CO and temperature
values are displayed. If set to NO
2
+Temp, then the NO
2
and temperature
values are displayed. If set to Status, the ppm values will not be displayed only
the device operating status. If set to None, there will not be any LCD display
information in Normal mode (the LCD will still work for menu operation).
The default and available options depend on the installed sensors. For example,
if the device only has a CO sensor, then CO ppm is the default and the only other
options available will be Status and None. If both sensors are installed, then the
default will be CO + NO
2
. If the temperature sensor is not installed (or resistive)
then no Temp display will be available. For Status, the normal display is CO
Detector, NO
2
Detector or CO / NO
2
Detector as applicable. If set to None, then the
backlight will be forced to Auto. If set to None, the test function still causes the
LCD to display while in test mode.
<MENU>
Press to advance to next menu item
Display
CO ppm
36. DISPLAY
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
Backlite
Auto
Use <UP> or <DOWN> to select the LCD backlight operation as Auto, Off or On.
Auto means the backlight only operates when the menu is accessed, On means
the backlight is always on and Off means it never lights. The default is Auto.
37. BACKLITE