Page 16
This item allows zero calibration of the NO
2
sensor. Ensure the
sensor is in clean air. Press and hold the <UP> key for 3 seconds
to initiate the calibration process. When the calibration is
complete, the display will indicate DONE. Then press <MENU>
to advance to the next selection. A NO
2
Zero Calibration
Counter is incremented every time this step is performed. NO
2
Re-Cal timer is reset whenever this step is performed.
This item allows span calibration of the NO
2
sensor. Apply 10
ppm NO
2
gas to the sensor. Press and hold the <UP> key for 3
seconds to initiate the calibration process. When the calibration
is complete, the display will indicate DONE. Then press <MENU>
to advance to the next selection. A NO
2
10 Calibration Counter is
incremented every time this step is performed. The NO
2
Re-Cal
timer is reset whenever this step is performed.
NO2 Zero
Cal GO
NO2 10
Cal GO
NO2 Zero
Cal DONE
NO2 10
Cal DONE
48. ZERO
CALIBRATION
49. SPAN
CALIBRATION
<MENU>
Press to advance to next menu item
then
then
Only if
NO
2
Sensor
is installed
This item allows offset calibration of the temperature sensor.
Use <UP> or <DOWN> to add an offset to the temperature
measurement. -1.0 subtracts 1.0° from the reading, +1.2 adds
1.2° to the reading. Units depend on the range selected, either
°C or °F. The offset resets to 0.0 if the units are changed. The
range is -5.0 to +5.0 for °C and -10.0 to +10.0 for °F. Resolution
is 0.1°.
T Offset
0.0
°
C
50. TEMP
OFFSET
Only if
Temperature Sensor
in installed
<MENU>
Press to advance to next menu item
<MENU>
Press to exit the Setup Menu and return to normal mode
IN-GE-GDTXXX-06