Page 8
Press the <UP> or <DOWN> keys to scroll through the available
options. The temperature sensing range and output scale can
be changed to -20 to 50°C, 0 to 50°C, -4 to 122°F, 32 to 122°F if
necessary. The factory default temperature range is -20 to 50°C.
T Range
-20-50
°
C
Only if
Temperature is sensor is installed
& the output type is
Voltage or mA
2. TEMP RANGE
<MENU>
Press to advance to next menu item
Press the <UP> or <DOWN> keys to scroll through the available
options. The buzzer alarm trip point for NO
2
may be set to OFF
or from 1 to 10 ppm in 1 ppm increments. The default is 2 ppm.
The buzzer may operate as a CO alarm, an NO
2
alarm or both
depending on the trip point settings. If set to OFF, then the
buzzer will not operate as an NO
2
alarm.
Buzzer
Enable
Use <UP> or <DOWN> to enable or disable the buzzer alarm. When disabled,
the buzzer will not sound if the buzzer trip point is exceeded. The buzzer will still
beep on startup and will still beep for a fault alarm (if enabled) and Re-Cal alarm
(if enabled). The factory default is Enable.
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
3. BUZZER
CO Buzz
Dly 5Min
Press the <UP> or <DOWN> keys to scroll through the available
options. The CO buzzer delay may be set from 0 to 10 minutes
in 1-minutes increments. Is only available if the CO Buzzer Trip is
enabled not set to OFF. The default is 5 minutes.
NO2 Buzz
Trip 2
NO2 Buzz
Dly 5Min
Buzzer
Test OFF
Press the <UP> or <DOWN> keys to scroll through the available
options. The NO
2
buzzer delay may be set from 0 to 10 minutes
in 1-minute increments. The default is 5 minutes.
Press the <UP> or <DOWN> to toggle the buzzer ON or OFF.
CO Buzz
Trip 150
Press the <UP> or <DOWN> keys to scroll through the available
options. The buzzer alarm trip point for CO may be set to OFF
or from 20 to 500 ppm in 10 ppm increments. The default if 150
ppm. The buzzer may operate as a CO alarm, an NO
2
alarm or
both depending on the trip point settings. If set to OFF, then the
buzzer will not operate as a CO alarm.
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
4. CO BUZZER
TRIP POINT
Only if the
buzzer
&
CO sensor
is installed
Only if the
buzzer
&
NO
2
sensor
is installed
Only if the
buzzer
is enabled
5. CO BUZZER
DELAY
6. NO
2
BUZZER
TRIP POINT
7. NO
2
BUZZER
DELAY
8. BUZZER
<MENU>
Press to advance to next menu item
IN-GE-GDTXXX-06