background image

Page  2

 

PRINTED IN C

ANAD

A       

WIRING

• 

Deactivate the 24 Vac/dc power supply until all connections are made to the device to prevent equipment damage.

• 

Use 14-22 AWG shielded wiring for all connections and do not locate the device wires in the same conduit with wiring used to supply 

inductive loads such as motors. Make all connections in accordance with national and local codes.

• 

The temperature transmitter comes with the temperature sensor pre-wired to the transmitter board. If removal is required for installation 

then it may be re-wired as shown in Figure 6.

• 

Pull at least six inches of control wire into the enclosure, then complete the wiring connection according to the wire diagram for the 

applicable power supply and output signal type as shown in Figure 7.

• 

Connect the DC positive or the AC voltage hot side to the PWR terminal. For voltage output or AC power, the supply Common is connected 

to the COM terminal. The device is reverse voltage protected and will not operate if connected backwards. It has a half-wave power supply 

so the supply Common is the same as the signal Common. See Figure 7.

• 

The analog output is available on the OUT terminal. Check the controller Analog Input to determine the proper connection before applying 

power as shown in Figure 7.

• 

Once all connections are made and checked, power can be applied.

Wiring for 0-5 or 0-10 Vdc output 

signal and 24 Vdc power from 

controller

Wiring for all output signals with 

external 24 Vac power transformer

24 Vdc Power Supply

Wiring for 4-20 mA loop-powered 

output and external 24 Vdc power 

supply

Wiring for 4-20 mA loop-powered 

output and external 24 Vdc power 

from controller

Transmitter Wiring to Controller

Wiring for 0-5 or 0-10 Vdc output 

signal and with external 24 Vdc 

power supply

24 Vdc Power Supply

Figure 6

Figure 7

SPECIFICATIONS: 

Sensor Type: ....................................1000Ω Platinum, IEC 751, 385 Alpha, thin film

Sensor Accuracy: ..........................

RTD Class A: 

±0.15°C (±0.27°F) @ 0°C (32°F)

 

RTD 1/3 DIN: 

±0.1°C (±0.18°F) @ 0°C (32°F)

 

RTD 1/10 DIN: 

±0.03°C (±0.054°F) @ 0°C (32°F)

Wire Material: .................................FT-6 Plenum rated cable

Probe Sensing Range: ................-40 to 60°C (-40 to 140°F)

Probe Material: ..............................304 Series stainless steel

Probe Dimensions: ......................50 mm (2”) x 6.00” (0.236”)

Wire Length: ...................................3.05 m (10’)

Output Signal:................................4-20 mA current loop, 0-5 vdc, or 0-10 vdc

 

(factory configured)

Transmitter Accuracy: ................±0.2% of span, including linearity

Power Supply: ................................15 to 30 Vdc, 12 to 28 Vac

Consumption (max):...................

Current:

 20 mA

 

Voltage:

 11 mA

Protection Circuitry: ....................Reverse voltage protected and output limited

Output Drive @ 24 Vdc: .............

Current:

 700 ohms max 

 

Voltage:

 20K ohms min

LCD Display Units: ........................°C or °F (factory configured)

Display Range: ...............................3 digit for -88.8 to 888 as required

Display Size: ....................................38.1mm W x 16.5 mm H (1.5" to 0.65")

Digit Height: ...................................11.4 mm (0.45") plus °C/°F symbol

Ambient Operating Range: .....0 to 50°C (32 to 122°F), 0-95 %RH

Enclosure: .........................................

B:

 Grey polycarbonate UL94-V0, IP65 (NEMA 4X)

 

F:

 Same as B, with thread adapter (1/2” NPT to M16)

 

cable gland fitting

Wiring Connections: ...................Screw terminal block (14 to 22 AWG)

Country of Origin: ........................Canada

2 wire temperature sensor wiring to transmitter

SEN

Negative No Polarity
Excitation No Polarity

DIMENSIONS

 

3.05 m

10.00’

6.0 mm

0.236"

50 mm

2”

FT-6 Rated Plenum Cable, 22 AWG 304 Series S/S Probe

116.5 mm

4.585"

53.7 mm

2.115"

112.5 mm

4.43"

99.7 mm

3.925"

0.5" NPT

PW

R

CO

M

OU

T

SENSOR

IN-GE-HATDFLXXX-02

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com