Page 2
WIRING
•
Use 18 - 24 AWG shielded wiring for all connections. Do not locate the device wires in the same conduit with wiring used to supply inductive
loads such as motors. Make all connections in accordance with national and local codes.
•
Pull at least six inches of wire into the enclosure, then complete the wiring connection according to wiring diagrams below.
•
Thermistors are a 2 wire hook up and are not polarity sensitive. See Figure 6.
•
RTD’s are a 3 wire hook up see Figure 7.
SPECIFICATIONS
:
Sensor Type: ...................................Various thermistors or RTD
Sensor Accuracy: .........................
RTD Class A:
±0.15°C (±0.27°F) @ 0°C (32°F)
RTD 1/3 DIN:
±0.1°C (±0.18°F) @ 0°C (32°F)
RTD 1/10 DIN:
±0.03°C (±0.054°F) @ 0°C (32°F)
NTC Thermistor Type 39:
±0.05°C (±0.09°F), 0 to 70°C (32 to 158°F)
NTC Thermistor Type 55:
±0.03°C (±0.054°F),
0 to 70°C (32 to 158°F)
NTC Thermistor Type 40/46:
±0.1°C (±0.18°F),
0 to 70°C (32 to 158°F)
Probe Material: .............................Machined aluminum heat sink
Probe Dimensions: ..............38.1mm x 12.7mm (1.5” x 0.5”)
Probe Sensing Range: ...............
RTD:
-20 to 100°C (-4 to 212°F)
Thermistors:
-40 to 100°C (-40 to 212°F)
Ambient Operating Range: .... -40 to 50°C (-40 to 122°F)
Probe Size: ......................................38 mm (1.5") square
Wire Material: ................................
RTD:
FT-4, 22 AWG, 3 Wire
Thermistor:
PVC insulated, parallel bonded, 22 AWG, 2 Wire
Enclosure: ........................................
A:
ABS, UL94-V0, IP65 (NEMA4X)
C:
Same as A, with terminal block
E:
Same as C, with thread adapter (1/2" NPT to M16),
cable gland fitting, and terminal block
Termination: ..................................
A:
Pigtail, 2 or 3 wire
C & E:
terminal block, 2 or 3 wire
Country of Origin: .......................Canada
PRINTED IN C
ANAD
A
TYPICAL WIRE RESISTANCE VALUES
When using low resistance sensors, long wire runs can add significant error
to the readings. Use the following chart to determine errors due to wire
resistance or consider using a 1000 ohm sensor or a transmitter for better
accuracy. Locate the type of wire being used. Multiply the total length of the
wire (distance from the controller to the sensor and back) by the number
found in the chart below for total resistance.
Figure 6 2 Wire Termination for Thermistor
Figure 7 3 Wire Termination for RTD
To Controller
Analog Input (AI)
(No Polarity)
To Controller
Analog Input (AI)
(No Polarity)
To Controller
Analog Input (AI) or
Customer supplied
transmitter
To Controller
Analog Input (AI) or
Customer supplied
transmitter
Green
Red
Black
EMT Connector
EMT Connector
To Controller
Analog Input (AI)
(No Polarity)
To Controller
Analog Input (AI)
(No Polarity)
To Controller
Analog Input (AI) or
Customer supplied
transmitter
To Controller
Analog Input (AI) or
Customer supplied
transmitter
Green
Black
Red
EMT Connector
EMT Connector
Wiring for Enclosures C & E
*For illustrative purposes only, terminal block mounted on inside of cover
*
*
GAUGE WIRE TYPE 18 AWG 22 AWG 24 AWG
STRANDED (OHMS/FOOT) 5.85 mΩ 14.75 mΩ 23.29 mΩ
SOLID (OHMS/FOOT) 6.4 mΩ 15.85 mΩ 25.72 mΩ
NOTE:
The sensor accuracies listed in the specifications section apply to the
sensing element only prior to product assembly and may not be reflected in
the complete assembly.
Due to the measurement uncertainty, it is possible, that the true resistance
value of the single delivered sensor at 0°C can be out of the defined tolerance
class. Profiling each assembly to take into consideration lead wire and the
attachment method should be completed.
DIMENSIONS
69.8 mm
2.75"
76.2 mm
3.00"
82.5 mm
3.25"
52.0 mm
2.05"
28.6 mm
1.125"
0.5" NPT
254 mm (10")
S/S Pipe Clamp
Quick Release
Machined Aluminum
Heat Sink
IN-GE-HATSSOXXX-03
Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com