background image

Page  2

WIRING

The particulate matter sensor has standard screw block connectors and easy wire access to facilitate wiring. 

It is recommended that shielded twisted pair wiring at least 22 AWG be used for all connections and that 

the device wires not be run in the same conduit with wiring used to supply inductive loads such as motors. 

Disconnect the power supply before making any connections to prevent electrical shock or equipment 

damage. Make all connections in accordance with national and local electrical codes.

The device power (24 Vac/dc) is connected to the terminal marked PWR (POWER). This terminal is used for 

the positive dc voltage or the hot side of the ac voltage. The device is reverse voltage protected and as 

such will not operate if connected backwards.

The common of the power supply is connected to the terminal marked COM (COMMON). Note that this 

device has a half-wave type power supply which means the power supply common is the same as the output 

signal common. Therefore, several devices may be connected to 

one power supply and the output signals all share the same signal 

common. Use caution when grounding the secondary of an ac 

transformer or when wiring multiple devices to ensure that the 

circuit ground point is the same on all devices and the controller. 

In general, the transformer should not be connected to earth 

ground when using devices with an RS-485 network connection.

The analog output signal is available on the OUT (OUTPUT) 

terminal. This signal is jumper selectable for either voltage or 

4-20 mA output signal type. See Figure 5. The voltage output 

signal defaults to 0-5 Vdc but may be changed to 0-10 Vdc via 

the menu. These options are clearly indicated on the device 

PCB. The analog output signal is typically connected directly to 

the Building Automation System (B.A.S.) and used as a control 

parameter or for logging purposes. Check the controller Analog 

Input type to determine the correct connection and signal type 

before applying power. The device generates the analog output 

signal (sourcing) and must not be connected to a powered input 

or device damage may occur.

For voltage type output signal the device has a minimum load 

that it is able to drive, similarly for current type output signal the 

device has a maximum load that it is able to drive with a particular 

power supply voltage. Observe and follow these ratings in the 

Specification section or inaccurate reading may result. The 4-20 

mA output signal can easily be converted to a 1-5 Vdc signal 

for controllers accepting this type of input. Simply insert a 250 

ohm (0.1% is best) resistor between the “+” and “-” inputs of the 

controller. This will convert the 4-20 mA signal to the desired 1-5 

Vdc. See Figure 6.

using the appropriate holes, remove the PCB from the anti-static bag and feed the wires through the 

center hole of the PCB. Place the top of the PCB into the latches on the top of the backplate and gently 

snap the bottom edge of the PCB into place as shown in Figure 4.

Make wire connections as per the Wiring Illustrations on Page 2 and install decorative cover by placing the 

top of the cover into the cover holder on the top of the backplate and snapping the bottom into place as 

shown in Figure 4. Tighten security screw with a screwdriver.

+ 24 Vdc/24 Vac (HOT)
COMMON
Analog Input

PWR

COM

OUT

Controller

Figure 4

Figure 6

Figure 5

Cover

PCB

Backplate

4-20 mA

4-20 mA

VOLT

VOLT

IN-GE-PMRMCXXX-05

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for PMRMC Series

Page 1: ...cautions during installation and do not exceed the device ratings MOUNTING The particulate matter transmitter mounts directly on a wall or onto an electrical wall box and should be mounted to a wall box five feet from the floor Do not mount the sensor near doors opening windows supply air diffusers or other known air disturbances Avoid areas where the sensor is exposed to vibrations or rapid tempe...

Page 2: ... options are clearly indicated on the device PCB The analog output signal is typically connected directly to the Building Automation System B A S and used as a control parameter or for logging purposes Check the controller Analog Input type to determine the correct connection and signal type before applying power The device generates the analog output signal sourcing and must not be connected to a...

Page 3: ...gth segment depends on transmission speed baud rate wire size and number of nodes If communication is slow or unreliable it may be necessary to wire two daisy chains to the controller with a repeater for each segment An optional signal is the alarm relay output available on the NO NORMALLY OPEN NC NORMALLY CLOSED and R COM RELAY COMMON terminals The R COM terminal is not connected to the power sup...

Page 4: ...tup The network version of the product allows for configuration of settings via BACnet or Modbus protocol and the BACnet objects or Modbus registers are updated with the appropriate values and alarm conditions are monitored OPERATION ALARM All models except for the analog output only without relay will have a PM setpoint alarm The alarm will controltheoptionalrelayornetworkvariablesasapplicabletot...

Page 5: ...UT MENU Press to advance to next menu item Only if Relay OR Network Option installed PM Alarm 150 ug Alrm Hys 20 ug Alrm Dly 0 min PM Alarm Test Off Setpoint for PM alarm and relay if installed activation Default setpoint for alarm activation is 150 ug m3 Use ROLL to adjust from 50 900 ug m3 Resolution is 10 ug m3 The default PM alarm hysteresis is 20 ug m3 Use ROLL to change to 10 15 20 25 30 35 ...

Page 6: ...fault network baud rate is 9600 Use ROLL to select 9600 19200 38400 57600 76800 or 115200 as required The default network address is 3 for BACnet and 1 for Modbus Use ROLL to select 0 127 for a BACnet device or 1 255 for a Modbus device 11 BAUD RATE 12 ADDRESS MENU Press to advance to next menu item MENU Press to advance to next menu item OPERATION TESTING COMMISSIONING OPTIONAL To perform testing...

Page 7: ...n 0 to 50 ug m3 Moderate Yellow 51 to 150 ug m3 Poor Red 151 to 1000 ug m3 PM Alarm Relay optional Contact Ratings Form C N O N C 2A 140 Vac 2A 30 Vdc Relay Setpoint Hysteresis Programmable via menu Relay Time Delay Programmable via menu General LCD Size 35mm W x 15mm H 1 4 x 0 6 alpha numeric 2 line x 8 characters LCD Backlight Enable or disable via menu Display Values 0 to 500 Air Quality Index ...

Page 8: ...ed to add support to their systems to communicate with the device BACnet and Modbus setup guide downloads are available online BACnet PROTOCOL https downloads greystoneenergy com SG SG PMXXXBAC pdf MODBUS PROTOCOL https downloads greystoneenergy com SG SG PMXXXMOD pdf IN GE PMRMCXXX 05 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com ...

Reviews: