background image

Page  3

If the device includes the optional network connection, use 

twisted shielded pair to connect to the terminals marked 

A-, B+ and SHLD (SHIELD). The positive wire connects to B+, 

the negative to A- and the cable shield must be connected 

to the SHLD terminal on each device. The shield wire should 

be connected to earth ground at one end of the network 

only. See Figure 7. If the device is installed at either end of 

an RS-485 network, an end-of-line (EOL) termination resistor 

(121 ohms) should be installed in parallel with the A- and B+ 

terminals. This device includes a network termination resistor 

and jumper that can be used to connect the EOL resistor on 

the PCB. Simply move the jumper to the EOL position and no 

external resistor is required. See Figure 8.

A network segment is a single shielded wire loop run between 

several devices (nodes) in a daisy chain configuration. The 

total segment length should be less than 1220 meters (4000 

feet) and the maximum number of nodes on one segment 

length is 64. Nodes are any device connected to the loop and 

include controllers but do not include the EOL terminators. 

To install more than 64 devices, or to increase network 

length, repeaters will be required for proper communication. 

The maximum daisy chain length (segment) depends on transmission speed (baud rate), wire size and 

number of nodes. If communication is slow or unreliable, it may be necessary to wire two daisy chains to 

the controller with a repeater for each segment.

An optional signal is the alarm relay output available on the NO (NORMALLY OPEN), NC (NORMALLY 

CLOSED ) and R.COM (RELAY COMMON) terminals. The R.COM terminal is not connected to the power 

supply COM terminal, the relay output is completely isolated. The relay contacts may be connected to a 

controller Digital Input (DI) for status monitoring or used to directly control an alarm or ventilation fan. Do 

not exceed the device contact ratings. In some cases a separate control relay may be used between the 

particulate matter sensor relay and a large fan for example. See Figure 9.

Figure 7

Set EOL Jumper

Building Controller

Device 01

Device 02

Device 03

Connect Shield One End Only

PWR

COM

PWR

COM

PWR

COM

SHLD

B+

A-

SHLD

B+

A-

SHLD

B+

A-

BACnet® Master

24 Vac / dc

Common

Shield

B+

A-

Building Controller

Device 01

Device 02

Device 03

Connect Shield One End Only

PWR

COM

PWR

COM

PWR

COM

SHLD

B+

A-

SHLD

B+

A-

SHLD

B+

A-

BACnet® Master

24 Vac / dc

Common

Shield

B+

A-

External 24 Vdc Power 

Supply or 24 Vac 

Transformer

Figure 8

Figure 9

EOL

EOL

EOL

OFF

ON

Digital Input
Digital Input
Digital Input

NO

R. COM

NC

Controller

IN-GE-PMRMCXXX-05

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for PMRMC Series

Page 1: ...cautions during installation and do not exceed the device ratings MOUNTING The particulate matter transmitter mounts directly on a wall or onto an electrical wall box and should be mounted to a wall box five feet from the floor Do not mount the sensor near doors opening windows supply air diffusers or other known air disturbances Avoid areas where the sensor is exposed to vibrations or rapid tempe...

Page 2: ... options are clearly indicated on the device PCB The analog output signal is typically connected directly to the Building Automation System B A S and used as a control parameter or for logging purposes Check the controller Analog Input type to determine the correct connection and signal type before applying power The device generates the analog output signal sourcing and must not be connected to a...

Page 3: ...gth segment depends on transmission speed baud rate wire size and number of nodes If communication is slow or unreliable it may be necessary to wire two daisy chains to the controller with a repeater for each segment An optional signal is the alarm relay output available on the NO NORMALLY OPEN NC NORMALLY CLOSED and R COM RELAY COMMON terminals The R COM terminal is not connected to the power sup...

Page 4: ...tup The network version of the product allows for configuration of settings via BACnet or Modbus protocol and the BACnet objects or Modbus registers are updated with the appropriate values and alarm conditions are monitored OPERATION ALARM All models except for the analog output only without relay will have a PM setpoint alarm The alarm will controltheoptionalrelayornetworkvariablesasapplicabletot...

Page 5: ...UT MENU Press to advance to next menu item Only if Relay OR Network Option installed PM Alarm 150 ug Alrm Hys 20 ug Alrm Dly 0 min PM Alarm Test Off Setpoint for PM alarm and relay if installed activation Default setpoint for alarm activation is 150 ug m3 Use ROLL to adjust from 50 900 ug m3 Resolution is 10 ug m3 The default PM alarm hysteresis is 20 ug m3 Use ROLL to change to 10 15 20 25 30 35 ...

Page 6: ...fault network baud rate is 9600 Use ROLL to select 9600 19200 38400 57600 76800 or 115200 as required The default network address is 3 for BACnet and 1 for Modbus Use ROLL to select 0 127 for a BACnet device or 1 255 for a Modbus device 11 BAUD RATE 12 ADDRESS MENU Press to advance to next menu item MENU Press to advance to next menu item OPERATION TESTING COMMISSIONING OPTIONAL To perform testing...

Page 7: ...n 0 to 50 ug m3 Moderate Yellow 51 to 150 ug m3 Poor Red 151 to 1000 ug m3 PM Alarm Relay optional Contact Ratings Form C N O N C 2A 140 Vac 2A 30 Vdc Relay Setpoint Hysteresis Programmable via menu Relay Time Delay Programmable via menu General LCD Size 35mm W x 15mm H 1 4 x 0 6 alpha numeric 2 line x 8 characters LCD Backlight Enable or disable via menu Display Values 0 to 500 Air Quality Index ...

Page 8: ...ed to add support to their systems to communicate with the device BACnet and Modbus setup guide downloads are available online BACnet PROTOCOL https downloads greystoneenergy com SG SG PMXXXBAC pdf MODBUS PROTOCOL https downloads greystoneenergy com SG SG PMXXXMOD pdf IN GE PMRMCXXX 05 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com ...

Reviews: