Page  4

OPERATION - START-UP

After applying power to the device, it will enter the start-up mode and the LCD will indicate the software 

version number, the PM range, the PM alarm setpoint (if applicable) and the analog output type for two 

seconds each.

If the network option is installed, then the start-up sequence will also show the network protocol, the baud 

rate and the device address. Then the device will start normal operation and display the PM concentration 

value.

OPERATION - NORMAL

During normal mode the device reads the PM sensor and calculates the Air Quality Index based on a 24 

hour time average. The real time PM concentration value is displayed on the LCD and set as the output 

value for the analog output. The output value is updated once per second. The LCD may be configured via 

the menu to display either the PM value or the AQI. If the optional tri-color LED is installed, it will change 

color to indicate Good (Green), Moderate (Yellow) or Poor (Red) air quality.

On start-up when the first readings are obtained, the Air Quality reading for the device averages the 

concentration level as necessary until the required time base setting is reached. For example, if only 10 

readings are available then the output value is calculated as the average of those 10 readings. The next 

output value will be an average of 11 readings. This short-averaging will continue until the unit has been 

running for 24 hours. Once 24 hours is reached then the AQI value will always be the average of readings 

over the past 24 hours. 

The device also monitors the keypad and takes appropriate menu actions for setup. The network version of 

the product allows for configuration of settings via BACnet® or Modbus protocol and the BACnet® objects 

or Modbus registers are updated with the appropriate values and alarm conditions are monitored.

OPERATION - ALARM

All models except for the analog output only without relay will have a PM setpoint alarm. The alarm will 

control the optional relay or network variables as applicable to the model. The PM alarm setpoint, hysteresis 

and time delay may be configured via the menu or network. The details of each setting and operation is 

explained in the Setup Menu section.

OPERATION - SETUP MENU

The Setup Menu has several items as shown below. To enter the menu, press and release the <MENU> key 

while in normal operation. This will enter the Setup Menu step 1, pressing the <MENU> key a second time 

advances to step 2. Each press of the <MENU> key saves the selection and advances the menu item. The 

<ROLL> key is used to make changes to program variables by scrolling through the available options. If 

the Setup Menu is not active for 5 minutes (no key press), then the menu will exit and the device returns 

to normal operation.

Network

Modbus

BaudRate

9600

Address

3

100

ug/m3

Version

1.00

PM Range

PM1.0

PM Alarm

150ug/m3

Output

4-20 mA

PM Range

PM10

The default PM Range is PM10. Use <ROLL> to change the range as required to 

either PM1.0, PM2.5, PM4.0, or PM10.

Output

0-5 Vdc

Use <ROLL> to set the voltage output signal type to 0-5 or 0-10 Vdc. The factory 

default is 0-5 Vdc. 

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

<MENU> 

Press and hold to enter the setup menu. Once in menu release <MENU>.

1. PARTICULATE MATTER RANGE

2. VOLTAGE OUTPUT SIGNAL

IN-GE-PMRMCXXX-05

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for PMRMC Series

Page 1: ...cautions during installation and do not exceed the device ratings MOUNTING The particulate matter transmitter mounts directly on a wall or onto an electrical wall box and should be mounted to a wall box five feet from the floor Do not mount the sensor near doors opening windows supply air diffusers or other known air disturbances Avoid areas where the sensor is exposed to vibrations or rapid tempe...

Page 2: ... options are clearly indicated on the device PCB The analog output signal is typically connected directly to the Building Automation System B A S and used as a control parameter or for logging purposes Check the controller Analog Input type to determine the correct connection and signal type before applying power The device generates the analog output signal sourcing and must not be connected to a...

Page 3: ...gth segment depends on transmission speed baud rate wire size and number of nodes If communication is slow or unreliable it may be necessary to wire two daisy chains to the controller with a repeater for each segment An optional signal is the alarm relay output available on the NO NORMALLY OPEN NC NORMALLY CLOSED and R COM RELAY COMMON terminals The R COM terminal is not connected to the power sup...

Page 4: ...tup The network version of the product allows for configuration of settings via BACnet or Modbus protocol and the BACnet objects or Modbus registers are updated with the appropriate values and alarm conditions are monitored OPERATION ALARM All models except for the analog output only without relay will have a PM setpoint alarm The alarm will controltheoptionalrelayornetworkvariablesasapplicabletot...

Page 5: ...UT MENU Press to advance to next menu item Only if Relay OR Network Option installed PM Alarm 150 ug Alrm Hys 20 ug Alrm Dly 0 min PM Alarm Test Off Setpoint for PM alarm and relay if installed activation Default setpoint for alarm activation is 150 ug m3 Use ROLL to adjust from 50 900 ug m3 Resolution is 10 ug m3 The default PM alarm hysteresis is 20 ug m3 Use ROLL to change to 10 15 20 25 30 35 ...

Page 6: ...fault network baud rate is 9600 Use ROLL to select 9600 19200 38400 57600 76800 or 115200 as required The default network address is 3 for BACnet and 1 for Modbus Use ROLL to select 0 127 for a BACnet device or 1 255 for a Modbus device 11 BAUD RATE 12 ADDRESS MENU Press to advance to next menu item MENU Press to advance to next menu item OPERATION TESTING COMMISSIONING OPTIONAL To perform testing...

Page 7: ...n 0 to 50 ug m3 Moderate Yellow 51 to 150 ug m3 Poor Red 151 to 1000 ug m3 PM Alarm Relay optional Contact Ratings Form C N O N C 2A 140 Vac 2A 30 Vdc Relay Setpoint Hysteresis Programmable via menu Relay Time Delay Programmable via menu General LCD Size 35mm W x 15mm H 1 4 x 0 6 alpha numeric 2 line x 8 characters LCD Backlight Enable or disable via menu Display Values 0 to 500 Air Quality Index ...

Page 8: ...ed to add support to their systems to communicate with the device BACnet and Modbus setup guide downloads are available online BACnet PROTOCOL https downloads greystoneenergy com SG SG PMXXXBAC pdf MODBUS PROTOCOL https downloads greystoneenergy com SG SG PMXXXMOD pdf IN GE PMRMCXXX 05 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com ...