background image

Page  6

ModBus

Stop 1

Use <ROLL> to toggle the stop bits between 1 and 2. The 

default Modbus stop bits is 1.

14. STOP BITS

<MENU> 

Press to advance to next menu item

Only if 

Modbus Option

 installed

ModBus

CRC A001

ModBus

CRC A001

Use <ROLL> to set the CRC value to A001 (CRC-16 reverse), 

1021 (CITT), 8005 (CRC-16) or 8408 (CITT reverse). The default 

CRC polynomial is 0xA001.

Use <ROLL> to change the value from MIN (minimum) to 50, 

100, 150, 200, 250, 300 or 350ms. The factory default slave 

response delay is minimum (minimum delay means just  

more than 3.5 character time delays, 4ms for 9600 baud rate, 

for example).

15. CRC VALUE

16. SLAVE

 RESPONSE

<MENU> 

Press to advance to next menu item

<MENU> 

Exits the Setup Menu and returns to normal mode.

ModBus

Parity N

Use <ROLL> to select a parity value of N (none), O (odd) or E 

(even). The factory default Modbus parity bit is N (none).

13. PARITY VALUE

<MENU> 

Press to advance to next menu item

Only if 

Network Option

 installed

BaudRate

9600

Address

3

The default network baud rate is 9600. Use <ROLL> to select 

9600, 19200, 38400, 57600, 76800 or 115200 as required.

The default network address is 3 for BACnet® and 1 for Modbus. 

Use <ROLL> to select 0-127 for a BACnet® device or 1-255 for a 

Modbus device.

11. BAUD RATE

12. ADDRESS

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

OPERATION - TESTING/COMMISSIONING (OPTIONAL)

To perform testing or commissioning the unit should be configured to display PM reading since AQI 

reading requires operation over 24-hour period. To verify sensor is reading properly a Greystone CO BUMP 

KIT or equivalent can be used to generate particulates. 

To prepare for testing open CO BUMP KIT, follow instructions included with kit to generate smoke from 

wick. The CO Adapter is not required for testing the PM sensor.

Hold wick close to inlet of sensor (bottom of cover).

Sensor PM reading should increase.

This will verify sensor is reading higher PM levels and is operational.  If sensor readings do not increase 

with smoke then sensor is faulty.

IN-GE-PMRMCXXX-05

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for PMRMC Series

Page 1: ...cautions during installation and do not exceed the device ratings MOUNTING The particulate matter transmitter mounts directly on a wall or onto an electrical wall box and should be mounted to a wall box five feet from the floor Do not mount the sensor near doors opening windows supply air diffusers or other known air disturbances Avoid areas where the sensor is exposed to vibrations or rapid tempe...

Page 2: ... options are clearly indicated on the device PCB The analog output signal is typically connected directly to the Building Automation System B A S and used as a control parameter or for logging purposes Check the controller Analog Input type to determine the correct connection and signal type before applying power The device generates the analog output signal sourcing and must not be connected to a...

Page 3: ...gth segment depends on transmission speed baud rate wire size and number of nodes If communication is slow or unreliable it may be necessary to wire two daisy chains to the controller with a repeater for each segment An optional signal is the alarm relay output available on the NO NORMALLY OPEN NC NORMALLY CLOSED and R COM RELAY COMMON terminals The R COM terminal is not connected to the power sup...

Page 4: ...tup The network version of the product allows for configuration of settings via BACnet or Modbus protocol and the BACnet objects or Modbus registers are updated with the appropriate values and alarm conditions are monitored OPERATION ALARM All models except for the analog output only without relay will have a PM setpoint alarm The alarm will controltheoptionalrelayornetworkvariablesasapplicabletot...

Page 5: ...UT MENU Press to advance to next menu item Only if Relay OR Network Option installed PM Alarm 150 ug Alrm Hys 20 ug Alrm Dly 0 min PM Alarm Test Off Setpoint for PM alarm and relay if installed activation Default setpoint for alarm activation is 150 ug m3 Use ROLL to adjust from 50 900 ug m3 Resolution is 10 ug m3 The default PM alarm hysteresis is 20 ug m3 Use ROLL to change to 10 15 20 25 30 35 ...

Page 6: ...fault network baud rate is 9600 Use ROLL to select 9600 19200 38400 57600 76800 or 115200 as required The default network address is 3 for BACnet and 1 for Modbus Use ROLL to select 0 127 for a BACnet device or 1 255 for a Modbus device 11 BAUD RATE 12 ADDRESS MENU Press to advance to next menu item MENU Press to advance to next menu item OPERATION TESTING COMMISSIONING OPTIONAL To perform testing...

Page 7: ...n 0 to 50 ug m3 Moderate Yellow 51 to 150 ug m3 Poor Red 151 to 1000 ug m3 PM Alarm Relay optional Contact Ratings Form C N O N C 2A 140 Vac 2A 30 Vdc Relay Setpoint Hysteresis Programmable via menu Relay Time Delay Programmable via menu General LCD Size 35mm W x 15mm H 1 4 x 0 6 alpha numeric 2 line x 8 characters LCD Backlight Enable or disable via menu Display Values 0 to 500 Air Quality Index ...

Page 8: ...ed to add support to their systems to communicate with the device BACnet and Modbus setup guide downloads are available online BACnet PROTOCOL https downloads greystoneenergy com SG SG PMXXXBAC pdf MODBUS PROTOCOL https downloads greystoneenergy com SG SG PMXXXMOD pdf IN GE PMRMCXXX 05 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com ...

Reviews: