SPECIFICATIONS

PM Sensor

Sensor ............................................Laser scatter method

Particle Size ..................................PM1.0, PM2.5, PM4.0, or PM10 (selectable)

Mass Concentration ..................0 to 1000 ug/m

3

Resolution ....................................1 ug/m

3

Accuracy .......................................±10 ug/m

3

 (0 to 100 ug/m

3

), ±10% (100 to 1000 ug/m

3

)

Response Time ...........................1 second

Sensor Lifetime ..........................>8 years

Analog Model

Consumption ..............................75 mA max @ 24 Vdc, 100 mA max @ 24 Vac

Output Signals ............................4-20 mA (sourcing) or 0-5 Vdc / 0-10 Vdc (selectable)

Output Drive Capability ..........

Current:

 550Ω max

 

Voltage:

 5,000Ω min

Output Scale ...............................0 to 1000 ug/m

3

 (menu selectable)

BACnet® Model

Consumption ..............................50 mA max @ 24 Vdc, 80 mA max @ 24 Vac

Interface ........................................MS/TP, 2-wire RS-485

Baud Rate .....................................9600, 19200, 38400, 57600, 76800 or 115200 (menu selectable)

Address Range ............................0 to 127 (menu selectable)

Modbus Model

Consumption ..............................50 mA max @ 24 Vdc, 80 mA max @ 24 Vac

Interface ........................................MS/TP, 2-wire RS-485, RTC

Baud Rate .....................................9600, 19200, 38400, 57600, 76800 or 115200 (menu selectable)

Address Range ............................1 to 255 (menu selectable)

Tri-Color LED (optional)

Good ..............................................Green (0 to 50 ug/m

3

)

Moderate ......................................Yellow (51 to 150 ug/m

3

)

Poor ................................................Red (151 to 1000 ug/m

3

PM Alarm Relay (optional)

Contact Ratings ..........................Form C (N.O. + N.C.), 2A @ 140 Vac, 2A @ 30 Vdc

Relay Se Hysteresis ...Programmable via menu

Relay Time Delay ........................Programmable via menu

General

LCD Size ........................................35mm W x 15mm H (1.4" x 0.6") alpha-numeric 2 line x 8 characters

LCD Backlight ..............................Enable or disable via menu

Display Values .............................0 to 500 Air Quality Index or 0 to 1000 ug/m

3

Power Supply ..............................24 Vac/dc ±20% (non-isolated half-wave rectified)

Protection Circuitry ...................Reverse voltage protected, over-voltage protected

Operating Conditions ..............0 to 50°C (32 to 122°F), 20 to 80 %RH non-condensing

Storage Conditions ...................-30 to 60°C (-22 to 140°F)

Wiring Connections ..................Screw terminal block (14 to 22 AWG)

Enclosure Dimensions .............84mm W x 117mm H x 29mm D (3.3" x 4.6" x 1.15")

Enclosure Material .....................White ABS, IP30 (NEMA 1)

Weight ...........................................5.3 oz (150 gm)

Country of Origin .......................Canada

Accessories

PMFRSM ..........................................Replaceable sensor module and wire harness

84 mm

3.3“

119 mm

4.7“

29 mm

1.15 “

82.6 mm

3.25 “

58 mm

2.3 “

DIMENSIONS

IN-GE-PMRMCXXX-05

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for PMRMC Series

Page 1: ...cautions during installation and do not exceed the device ratings MOUNTING The particulate matter transmitter mounts directly on a wall or onto an electrical wall box and should be mounted to a wall box five feet from the floor Do not mount the sensor near doors opening windows supply air diffusers or other known air disturbances Avoid areas where the sensor is exposed to vibrations or rapid tempe...

Page 2: ... options are clearly indicated on the device PCB The analog output signal is typically connected directly to the Building Automation System B A S and used as a control parameter or for logging purposes Check the controller Analog Input type to determine the correct connection and signal type before applying power The device generates the analog output signal sourcing and must not be connected to a...

Page 3: ...gth segment depends on transmission speed baud rate wire size and number of nodes If communication is slow or unreliable it may be necessary to wire two daisy chains to the controller with a repeater for each segment An optional signal is the alarm relay output available on the NO NORMALLY OPEN NC NORMALLY CLOSED and R COM RELAY COMMON terminals The R COM terminal is not connected to the power sup...

Page 4: ...tup The network version of the product allows for configuration of settings via BACnet or Modbus protocol and the BACnet objects or Modbus registers are updated with the appropriate values and alarm conditions are monitored OPERATION ALARM All models except for the analog output only without relay will have a PM setpoint alarm The alarm will controltheoptionalrelayornetworkvariablesasapplicabletot...

Page 5: ...UT MENU Press to advance to next menu item Only if Relay OR Network Option installed PM Alarm 150 ug Alrm Hys 20 ug Alrm Dly 0 min PM Alarm Test Off Setpoint for PM alarm and relay if installed activation Default setpoint for alarm activation is 150 ug m3 Use ROLL to adjust from 50 900 ug m3 Resolution is 10 ug m3 The default PM alarm hysteresis is 20 ug m3 Use ROLL to change to 10 15 20 25 30 35 ...

Page 6: ...fault network baud rate is 9600 Use ROLL to select 9600 19200 38400 57600 76800 or 115200 as required The default network address is 3 for BACnet and 1 for Modbus Use ROLL to select 0 127 for a BACnet device or 1 255 for a Modbus device 11 BAUD RATE 12 ADDRESS MENU Press to advance to next menu item MENU Press to advance to next menu item OPERATION TESTING COMMISSIONING OPTIONAL To perform testing...

Page 7: ...n 0 to 50 ug m3 Moderate Yellow 51 to 150 ug m3 Poor Red 151 to 1000 ug m3 PM Alarm Relay optional Contact Ratings Form C N O N C 2A 140 Vac 2A 30 Vdc Relay Setpoint Hysteresis Programmable via menu Relay Time Delay Programmable via menu General LCD Size 35mm W x 15mm H 1 4 x 0 6 alpha numeric 2 line x 8 characters LCD Backlight Enable or disable via menu Display Values 0 to 500 Air Quality Index ...

Page 8: ...ed to add support to their systems to communicate with the device BACnet and Modbus setup guide downloads are available online BACnet PROTOCOL https downloads greystoneenergy com SG SG PMXXXBAC pdf MODBUS PROTOCOL https downloads greystoneenergy com SG SG PMXXXMOD pdf IN GE PMRMCXXX 05 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com ...