background image

IN-GE-RPCXXXBAC-01-02             03/19

Page  3

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

The RELAY output is a normally open dry contact. This signal can be used to directly control an alarm, 

ventilation fan or may be connected to a digital input of the BAS for status monitoring. Ensure any load 

connected to the relay is within the relay rating in the Specification section.

The remote buzzer is an optional component that can be installed to give a remote indication of an alarm 

condition. The BUZZER output requires two wires (+ and -) to operate the 24 Vdc remote buzzer. Follow the 

polarity indications on both units when making the connections.

PNEUMATIC CONNECTIONS

The two pressure ports are labeled High Port and Low Port on the PCB. The output signal reads a positive value 

when the port pressure is higher on the High port than the Low port, so ensure these ports are connected 

correctly. One port will be left open to measure the room pressure where the device is installed and the other 

port is connected to a remote pickup outside the room to measure the differential pressure.

Use 1/16" ID flexible silicone tubing for the pressure connections. Tube size adapters are included to allow 

the use of 1/8" ID tubing. Arrange the tubing to minimize stress on the connections and ensure there are 

no kinks in the tubing. The tubing should be routed through the PCB access hole and out the back of the 

enclosure base.

Ensure the tubing to be used is clean and do not allow material to fall into the pressure ports, as contamination 

could damage the sensor. When removing tubing use care to avoid breaking the ports. In some cases it is 

better to cut the tubing off rather than pull it off, be careful not to cut the fitting or an air leak may occur.

POWER UP INSTRUCTION

Before turning on the power, verify all wiring to ensure that it complies with the wiring instructions 

described above and verify that the output signal type is correctly selected on the PCB. Also, review the 

specifications to ensure the power supply is correct and that the pressure is within the correct range. The 

product should be allowed to warm-up for several minutes before attempting to verify accuracy.

Operation can be verified by measuring the output signal. For voltage output configuration, measure 

the voltage between the PRES OUT and COMMON terminals. The voltmeter should read between 0-5 or 

0-10 Vdc depending on the output range selected. For current output configuration, insert a mA meter in 

series with the PRES OUT terminal and it should read between 4 and 20 mA.

Upon applying power to the device the alarm condition is set to off so the relay, buzzer, LED and remote 

alarm are off. The analog output is set to the midpoint and the LCD will display the software version 

number such as 1.00 for 5 seconds. All keys are disabled during start-up mode. At the end of the start-up 

mode the device will enter normal operation.

NORMAL OPERATION

For a bipolar range such as ±1"wc, the pressure applied to the High port should be higher than pressure 

applied to the Low port for a positive output response. In this case, differential pressure can be measured 

using both ports. If the High port has a positive pressure with respect to the Low port, then the output 

indicates a positive pressure. Negative pressure is indicated if the High pressure is less than the Low 

pressure. The output pressure can be calculated as follows:

 

4-20 mA 

Pressure = [(Output current – 4 mA) / 16 mA] x 2 x Range – Offset

 

0-5 Vdc 

Pressure = (Output voltage / 5 V) x 2 x Range – Offset

 

0-10 Vdc 

Pressure = (Output voltage / 10 V) x 2 Range – Offset

In the case of ±1"wc, 4 mA or 0 V = -1"wc and 20 mA or 5 V or 10 V = +1"wc. Since the transmitter is linear, 

0"wc would be 12 mA or 2.5 V or 5 V.

During normal operation the device reads the pressure sensor and calculates the pressure value 

depending on the device model ranges and the selected pressure range. The pressure value is displayed 

on the LCD and sent to the analog output.

The output signal may be affected by the pressure averaging time setting in the menu. The pressure 

Summary of Contents for RPC Series

Page 1: ...sed to vibrations or rapid temperature changes To prevent erroneous readings due to air disturbances within the wall cavity seal the conduit leading to the junction box The cover is hooked to the base at the top edge and must be removed from the bottom edge first Use a small Phillips screwdriver to loosen the security screw as shown in Figure 1 Complete removal is not required Use a screw driver t...

Page 2: ...evices with RS 485 network connections Connect the RS 485 network with twisted shielded pair to the terminals marked A B and SHIELD The positive wire connects to B and the negative wire connects to A and the cable shield must be connected to the SHIELD terminal on each device If the device is installed at either end of an RS 485 network an end of line EOL termination resistor 121 ohm should be ins...

Page 3: ... signal type is correctly selected on the PCB Also review the specifications to ensure the power supply is correct and that the pressure is within the correct range The product should be allowed to warm up for several minutes before attempting to verify accuracy Operation can be verified by measuring the output signal For voltage output configuration measure the voltage between the PRES OUT and CO...

Page 4: ...um span is reached while adjusting one of the alarm limits then the other alarm limit will be pushed In this example for the 1 wc range these are some possible alarm settings 1 0 to 0 5 wc 0 75 to 0 25 wc 0 5 to 0 wc 0 25 to 0 25 wc 0 to 0 5 wc 0 5 to 1 0 wc The alarm also has settings for on delay and off delay which can be set via the menu Both of these default to 5 seconds but may be changed fr...

Page 5: ... 3 seconds If booth pressure ports are close to zero pressure open to ambient then the device will calibrate with a new zero point SETUP MENU OPERATION The setup menu can be accessed by pressing the internal MENU key at any time after the start up mode The system suspends operation when in the menu and holds the last pressure value on the output If an alarm condition was present then it will be re...

Page 6: ...IGHT MENU The LCD backlight defaults to 1 on It can be toggled to 0 off using UP or DOWN MENU Press to advance to next menu item 11 ALARM TEST MENU The alarm off delay defaults to 5 seconds It can be changed from 1 59 seconds and 1 10 minutes using UP or DOWN MENU Press to advance to next menu item 7 ALARM OFF DELAY MENU OFF The default BACnet MAC address is 3 This can be changed from 0 to 127 usi...

Page 7: ... LCD 0 45 digit height unit symbols and backlight Wiring Connections Screw terminal block 14 to 22 AWG Pressure Connections Ports for 1 16 ID tubing 1 8 ID adapters included Enclosure White ABS IP30 NEMA 1 84mm W x 119mm x 29mm H 3 3 x 4 7 x 1 15 Weight 115g 4oz Country of Origin Canada POWER SUPPLY Power Supply 24 Vac dc 10 Power Consumption 70 mA max with alarms on INTERFACE Communication 2 wire...

Reviews: