background image

IN-GE-RPCXXXBAC-01-02             03/19

Page  4

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

averaging setting controls how many readings are averaged to form the output value. The pressure 

averaging time defaults to 5 seconds and can be set from 1 to 60 seconds. The value effectively filters the 

output to prevent noise and false alarms.

The device also compares the output pressure value to the alarm set-points and takes appropriate 

action. If the pressure value exceeds either set-point then an alarm condition is set and the device will 

operate in alarm mode. Alarm mode activation is controlled by certain delay times and user settings 

described later. The device also monitors the keys and takes appropriate action if a key is pressed.

ALARM OPERATION

The alarm feature includes an on-board buzzer, silence switch, control relay, remote buzzer connection 

and LED.

The alarm feature has several settings that can be controlled by the setup menu. The device has two 

alarm trip points designated the high pressure alarm limit and the low pressure alarm limit. The high 

pressure alarm defaults to 50% of the maximum pressure range and the low pressure alarm defaults to 

50% of the minimum pressure range. For example, if the device is set to a ±1"wc range, then the default 

low pressure alarm limit will be -0.5 "wc and the default high pressure alarm limit will be +0.5 "wc. This is 

the same result for Pa ranges.

The alarm set-points can be set over the pressure range with certain conditions. For this example the 

pressure range is ±1"wc.

•  the low pressure alarm limit cannot go below the minimum pressure range setting (-1.0"wc)

•  the high pressure alarm limit cannot go above the maximum pressure range setting (+1.0"wc)

•  the high pressure alarm limit must always be greater than the low pressure alarm limit

•  the minimum alarm span (high alarm - low alarm) must be at least 25 % of the pressure span (2"wc x 

25 % = 0.5"wc)

•  if the minimum span is reached while adjusting one of the alarm limits, then the other alarm limit will 

be "pushed".

In this example for the ±1"wc range, these are some possible alarm settings: -1.0 to 0.5"wc, -0.75 to 

-0/25"wc, -0/5 to 0"wc, -0.25 to 0.25"wc, 0 to 0.5"wc, 0.5 to 1.0"wc.

The alarm also has settings for on delay and off delay which can be set via the menu. Both of these 

default to 5 seconds but may be changed from 1 to 59 seconds or 1 to 10 minutes. For an alarm 

condition to be set the pressure value must exceed either alarm trip point for more than the alarm on 

delay time. For an alarm condition to be reset the pressure value must return to a non-alarm value for 

more than the alarm off delay time.

When an alarm condition is set the red LED with flash, the relay output will activate, the local buzzer will 

sound and the remote buzzer output will activate. If the alarm condition is reset, all four outputs will 

deactivate. The LED flashes at a rate of 1 second on / 1 second off, the relay and remote buzzer are held 

on and the local buzzer sounds at a rate of 1 second on / 5 seconds off.

The alarm can be silenced by pressing the front cover silence switch during an alarm condition. In this 

case the buzzers and relay will de-activate but the LED continues to flash until the alarm condition is 

removed. The alarm silence time can be set in the menu or via BACnet® to 1-60 minutes or forever, and 

the default is 30 minutes. This means that if the silence switch is pressed and the alarms are silenced (and 

the alarm condition is not reset) then the alarm will re-activate after the silence time has expired. For the 

default setting of 30 minutes, the alarm buzzers and relay will activate again after 30 minutes of silence 

if the alarm condition still exists. If the delay is set to forever, then the alarms will not activate again in 

silence mode until the alarm condition is cleared and another alarm condition is set.

The alarm can be disabled by the user by holding the front cover silence switch for 5 seconds. It can be 

re-enabled by holding the switch again for 5 seconds. When the alarm is disabled, the OFF icon will be lit 

on the LCD and no alarms will be activated.

Summary of Contents for RPC Series

Page 1: ...sed to vibrations or rapid temperature changes To prevent erroneous readings due to air disturbances within the wall cavity seal the conduit leading to the junction box The cover is hooked to the base at the top edge and must be removed from the bottom edge first Use a small Phillips screwdriver to loosen the security screw as shown in Figure 1 Complete removal is not required Use a screw driver t...

Page 2: ...evices with RS 485 network connections Connect the RS 485 network with twisted shielded pair to the terminals marked A B and SHIELD The positive wire connects to B and the negative wire connects to A and the cable shield must be connected to the SHIELD terminal on each device If the device is installed at either end of an RS 485 network an end of line EOL termination resistor 121 ohm should be ins...

Page 3: ... signal type is correctly selected on the PCB Also review the specifications to ensure the power supply is correct and that the pressure is within the correct range The product should be allowed to warm up for several minutes before attempting to verify accuracy Operation can be verified by measuring the output signal For voltage output configuration measure the voltage between the PRES OUT and CO...

Page 4: ...um span is reached while adjusting one of the alarm limits then the other alarm limit will be pushed In this example for the 1 wc range these are some possible alarm settings 1 0 to 0 5 wc 0 75 to 0 25 wc 0 5 to 0 wc 0 25 to 0 25 wc 0 to 0 5 wc 0 5 to 1 0 wc The alarm also has settings for on delay and off delay which can be set via the menu Both of these default to 5 seconds but may be changed fr...

Page 5: ... 3 seconds If booth pressure ports are close to zero pressure open to ambient then the device will calibrate with a new zero point SETUP MENU OPERATION The setup menu can be accessed by pressing the internal MENU key at any time after the start up mode The system suspends operation when in the menu and holds the last pressure value on the output If an alarm condition was present then it will be re...

Page 6: ...IGHT MENU The LCD backlight defaults to 1 on It can be toggled to 0 off using UP or DOWN MENU Press to advance to next menu item 11 ALARM TEST MENU The alarm off delay defaults to 5 seconds It can be changed from 1 59 seconds and 1 10 minutes using UP or DOWN MENU Press to advance to next menu item 7 ALARM OFF DELAY MENU OFF The default BACnet MAC address is 3 This can be changed from 0 to 127 usi...

Page 7: ... LCD 0 45 digit height unit symbols and backlight Wiring Connections Screw terminal block 14 to 22 AWG Pressure Connections Ports for 1 16 ID tubing 1 8 ID adapters included Enclosure White ABS IP30 NEMA 1 84mm W x 119mm x 29mm H 3 3 x 4 7 x 1 15 Weight 115g 4oz Country of Origin Canada POWER SUPPLY Power Supply 24 Vac dc 10 Power Consumption 70 mA max with alarms on INTERFACE Communication 2 wire...

Reviews: