background image

Page  2

WIRING

The transmitter has standard screw block connectors. Use shielded twisted pair wiring of at least 22 AWG 

for all connections and do not run device wires in the same conduit with wiring used to supply inductive 

loads such as motors. Disconnect the power supply before making any connections to prevent electrical 

shock or equipment damage. Make all connections in accordance with national and local electrical codes.

This is a 3-wire sourcing device. Connect the positive dc or the ac voltage hot side (24 Vac/dc ± 10%) to 

the POWER terminal. The supply common is connected to the COMMON terminal. The device is reverse 

voltage protected and will not operate if connected backwards. It has a half-wave rectified power supply 

so the supply common is the same as the signal common. Several devices may be connected to one power 

supply and the output signals all share the same common. Use caution when grounding the secondary of 

a transformer or when wiring multiple devices to ensure the ground point is the same on all devices and 

the controller.

The analog output is available on the OUT terminal. This signal is switch selectable for either voltage or 4-20 

mA active output. In voltage mode the output is 0-5 or 0-10 Vdc, selectable in the User Menu. The current 

output operates in the Active mode and does not require a loop power supply. This means the signal 

current is generated by the transmitter and must not be connected to a powered input or device damage 

will result. Check the controller Analog Input to determine the proper connection before applying power. 

Both current and voltage signals are referenced to the COMMON terminal. The voltage output signal has 

a minimum load that it is able to drive, similarly the current signal has a maximum load. Follow the ratings 

in the Specification section or inaccurate readings may result.

The remote zero feature may be used by wiring a dry-contact (relay only) digital output between the ZERO  

and COMMON terminals. Do not apply voltage to the ZERO terminal.

The RELAY output is a normally open dry contact. This signal can be used to directly control an alarm, 

ventilation fan or may be connected to a digital input of the BAS for status monitoring. Ensure any loads 

connected to the relay is within the relay rating in the Specification section.

Figure 5

mA

VOLT

MENU DOWN ZERO/UP

N.O.

RELAY

B+

A-

SHIELD

OUT

ZERO

PWR

COM

OUT

ZERO

PWR

COM

Analog Input

+24 Vdc
Common

Controller

Wiring all output signals and 24 Vdc power from controller

OUT

ZERO

PWR

COM

Analog Input
Common

Controller

Common
+24 Vdc

24 Vdc Power Supply

Wiring all output signals and external 24 Vdc power supply

OUT

ZERO

PWR

COM

Analog Input
Common

Controller

Common
+24 Vac

24 Vac Transformer

Wiring all output signals and external 24 Vac power supply

Figure 6

Figure 7

NO

RELAY

Digital Input

Controller

ZERO

COM

Digital Input

Controller

Figure 8

High

Low

Relay Output

Remote Zero

CURRENT

VOLTAGE

Figure 9

IN-GE-UPXXX-01 07/20

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for UP Series

Page 1: ...nit See Figure 1 Leave enough space around the unit to connect the pressure tubing and avoid locations with severe vibrations excessive moisture or rapid temperature changes It should be mounted on a vertical surface with the pressure ports on the bottom and the cable entrance on the left The enclosure has a standard conduit opening and may be installed with either conduit and a conduit coupler or...

Page 2: ...ected to a powered input or device damage will result Check the controller Analog Input to determine the proper connection before applying power Both current and voltage signals are referenced to the COMMON terminal The voltage output signal has a minimum load that it is able to drive similarly the current signal has a maximum load Follow the ratings in the Specification section or inaccurate read...

Page 3: ...y at any time after the start up mode Upon applying power to the device it will enter the start up mode During start up the alarm condition is set to off so the relay is off and the analog output is set to the midpoint The LCD will display all segments for 2 seconds and then the software version number such as 1 USER MENU The User Menu can be accessed by pressing the MENU key at any time after the...

Page 4: ...gh pressure alarm limit defaults to about 75 of the range This equals 0 50 for the 1 wc range 130 for the 250 Pa range etc It can be changed using UP or DOWN throughout the range Resolution for each range is 1 wc 0 05 0 25 wc 0 01 250 Pa 10 and 60 Pa 2 Note that the 250 Pa range must be displayed as 10 such that it is 25H to 25H 7 HIGH PRESSURE ALARM MENU Press to advance to next menu item MENU WC...

Page 5: ...u During normal mode the device also compares the output pressure value to the alarm setpoints and takes appropriate action If the pressure value exceeds the setpoints then an alarm condition is set and the device will operate in alarm mode Alarm mode activation is controlled by certain delay times and user settings described later During normal mode the device also monitor the UP DOWN and MENU ke...

Page 6: ...e 38 1 x 16 5 mm 1 5 x 0 65 Digit Height 11 43 mm 0 45 Symbols WC Pa Backlight Enable disable auto ALARM FUNCTIONS Alarm Relay Output N O contact 2 Amps 120 Vac or 30 Vdc Alarm Relay Trip Point Upper and Lower alarms adjustable over pressure range Alarm Relay Delay 0 to 10 minutes via keypad GENERAL Storage Temperature 40 to 95 C 40 to 203 F Wiring Connections Screw terminal block 14 to 22 AWG Pre...

Reviews: