The setting has no affect unless the PCB switch is in the VOLT position. The analog 

output voltage scale defaults to 0-5 Vdc. Use <UP> or <DOWN> to toggle it to 0-10 

Vdc

1. OUTPUT

<MENU> 

Press to advance to next menu item

The pressure scale defaults to "wc. Use <UP> or <DOWN> to toggle it to Pa.

<MENU> 

Press to advance to next menu item

2. PRESSURE SCALE

MENU

MENU "WC

The default pressure range is bi (bidirectional ± max). Use <UP> or <DOWN> to 

toggle to uni (unidirectional 0-max). Applicable units symbol is displayed.

The default pressure range is HI (± 1 “wc, ± 250 Pa, ± 0.25 “wc or ± 60 Pa depending 

on the model and units). Use <UP> or <DOWN> to toggle to LO (± 0.5 “wc, ± 125 

Pa, ± 0.125 “wc or ± 30 Pa depending on the model and units). Applicable units 

symbol is displayed.

<MENU> 

Press to advance to next menu item

3. PRESSURE RANGE

4. DIRECTIONALITY

MENU "WC

MENU "WC

MENU

MENU "WC

MENU PA

START-UP

The Setup Menu can be accessed by pressing the internal <MENU> key at any time after the start-up 

mode.

Upon applying power to the device, it will enter the start-up mode. During start-up the alarm condition 

is set to off so the relay is off and the analog output is set to the midpoint. The LCD will display all 

segments for 2 seconds and then the software version number, such as 1.

USER MENU

The User Menu can be accessed by pressing the <MENU> key at any time after the start-up mode. Note 

that the <Auto-Zero> key function changes to an <UP> key function when a menu is active.

The system suspends operation when in the menu and holds the last pressure value as the output value. 

If an alarm condition was present then it will be reset to enter the menu and alarm operation is disabled 

while in the menu (except for alarm test). If the User Menu is not active for 5 minutes (no key press), then 

the menu will exit and the device returns to normal operation.

The Setup menu operation and parameters are explained below

<MENU> 

Press and release to enter the SETUP menu

IN-GE-UPXXX-01 07/20

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for UP Series

Page 1: ...nit See Figure 1 Leave enough space around the unit to connect the pressure tubing and avoid locations with severe vibrations excessive moisture or rapid temperature changes It should be mounted on a vertical surface with the pressure ports on the bottom and the cable entrance on the left The enclosure has a standard conduit opening and may be installed with either conduit and a conduit coupler or...

Page 2: ...ected to a powered input or device damage will result Check the controller Analog Input to determine the proper connection before applying power Both current and voltage signals are referenced to the COMMON terminal The voltage output signal has a minimum load that it is able to drive similarly the current signal has a maximum load Follow the ratings in the Specification section or inaccurate read...

Page 3: ...y at any time after the start up mode Upon applying power to the device it will enter the start up mode During start up the alarm condition is set to off so the relay is off and the analog output is set to the midpoint The LCD will display all segments for 2 seconds and then the software version number such as 1 USER MENU The User Menu can be accessed by pressing the MENU key at any time after the...

Page 4: ...gh pressure alarm limit defaults to about 75 of the range This equals 0 50 for the 1 wc range 130 for the 250 Pa range etc It can be changed using UP or DOWN throughout the range Resolution for each range is 1 wc 0 05 0 25 wc 0 01 250 Pa 10 and 60 Pa 2 Note that the 250 Pa range must be displayed as 10 such that it is 25H to 25H 7 HIGH PRESSURE ALARM MENU Press to advance to next menu item MENU WC...

Page 5: ...u During normal mode the device also compares the output pressure value to the alarm setpoints and takes appropriate action If the pressure value exceeds the setpoints then an alarm condition is set and the device will operate in alarm mode Alarm mode activation is controlled by certain delay times and user settings described later During normal mode the device also monitor the UP DOWN and MENU ke...

Page 6: ...e 38 1 x 16 5 mm 1 5 x 0 65 Digit Height 11 43 mm 0 45 Symbols WC Pa Backlight Enable disable auto ALARM FUNCTIONS Alarm Relay Output N O contact 2 Amps 120 Vac or 30 Vdc Alarm Relay Trip Point Upper and Lower alarms adjustable over pressure range Alarm Relay Delay 0 to 10 minutes via keypad GENERAL Storage Temperature 40 to 95 C 40 to 203 F Wiring Connections Screw terminal block 14 to 22 AWG Pre...

Reviews: