Page 4
The alarm on delay defaults to 5" (seconds). It can be changed from 1-59"
(seconds) and 1-10' (minutes) using <UP> or <DOWN>.
<MENU>
Press to advance to next menu item
9. ALARM DELAY
The alarm off delay defaults to 5" (seconds). It can be changed from 1-59"
(seconds) and 1-10' (minutes) using <UP> or <DOWN>.
<MENU>
Press to advance to next menu item
10. ALARM DELAY
MENU
OFF MENU
The alarm test defaults to OFF. It can be set to On using <UP> or <DOWN>. This
forces the relay to activate.
<MENU>
Press to advance to next menu item
11. ALARM TEST
MENU
8. ALARM TEST
The low pressure alarm limit defaults to about 25% of the range. This equals - 0.50
for the ± 1 "wc range, - 130 for the ± 250 Pa range, etc. It can be changed using
<UP> or <DOWN> throughout the range. Resolution for each range is: ± 1 "wc
(0.05), ± 0.25 "wc (0.01), ± 250 Pa (10) and ± 60 Pa (2). Note that the ± 250 Pa range
must be displayed as /10 such that it is - 25H to 25H.
<MENU>
Press to advance to next menu item
MENU "WC
The high pressure alarm limit defaults to about 75% of the range. This
0.50 for the ± 1 "wc range, + 130 for the ± 250 Pa range, etc. It can be changed
using <UP> or <DOWN> throughout the range. Resolution for each range is: ± 1
"wc (0.05), ± 0.25 "wc (0.01), ± 250 Pa (10) and ± 60 Pa (2). Note that the ± 250 Pa
range must be displayed as /10 such that it is - 25H to 25H.
7. HIGH PRESSURE ALARM
<MENU>
Press to advance to next menu item
MENU "WC
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
The pressure averaging time defaults to 5" (seconds). This can be changed from
1-60" (seconds) using <UP> or <DOWN>.
5. PRESSURE AVERAGING
MENU
Only if a relay is installed.
The alarm enable/disable defaults to enable (On). The
alarm can be disabled here. Use <UP> or <DOWN> to disable (OFF) the alarm. If
the alarm is disabled no alarm condition will be set. Note if the alarm is disabled,
then none of the alarm menu settings will be shown in the menu. Use <MENU> to
save and advance.
6. ALARM
<MENU>
Press to advance to next menu item
MENU
IN-GE-UPXXX-01 07/20
Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com