background image

Page  2

POWER AND ANALOG OUTPUT WIRING

Use 22 AWG shielded wire for all connections and do not locate the device wires in the same conduit with 

wiring used to supply inductive loads such as motors. Disconnect the power supply before making any 

connections to prevent electrical shock or equipment damage. Make all connections in accordance with 

national and local codes.

The wiring configuration depends on the specific model and the installed options. Follow the example 

wiring diagrams to determine the correct wiring. All models have the same terminal functions. This device 

has a half-wave type power supply so the power supply common is the same as the output signal common. 

Therefore, several devices may be connected to one power supply and the output signals all share the 

same signal common. Use caution when grounding the secondary of an AC transformer or when wiring 

multiple devices so that the circuit ground point is the same on all devices and the controller.

This is a 3-wire sourcing device. All models require a 24 Vac/dc power supply to operate. Connect the 

positive dc voltage or the hot side of the ac voltage to the ANALOG - PWR terminal and the power supply 

common to the ANALOG - COM terminal. Note that the Analog COM terminal is NOT connected to the 

Relay COM terminals. The device is reverse voltage protected and will not operate if the power supply is 

connected backwards.

The linear output signal (either 4-20 mA or 0-5/10 Vdc) is available on the ANALOG - CO terminal. The 

signal is referenced to the Analog COM terminal.  The 4-20 mA output signal operates in the Active mode 

and does not require a loop power supply. This means the signal current is generated by the transmitter 

and must not be connected to a powered input or device damage will result. This is the typical operating 

mode of a “three-wire device”. Ensure the controller Analog Input (AI) matches the CO Transmitter output 

signal type before power is applied. The current signal has a maximum load that it will drive and the 

voltage output has a minimum load. Follow the ratings in the Specification section or inaccurate readings 

may result. The power must be disconnected to change from VOLT to mA. The analog output CO signal is 

typically connected directly to the Building Automation System (BAS) and used as a control parameter or 

for logging purposes.

REMOTE TEST WIRING

The CO Transmitter has a Test function that will test the analog output and the alarm relays which is initiated 

by pressing the front panel TEST switch. The Test function may also be initiated remotely by shorting the 

TEST + and TEST - terminals. Note that the TEST - terminal is connected to the Analog COM terminal. The 

TEST terminals should only be connected to a dry-contact digital output from the controller that is either 

shorted or floating open. Ensure no power is applied to the TEST terminals. The TEST terminals may also be 

connected to a remote switch. If desired, only one wire need be connected to the TEST + terminal and use 

the power supply COM as the return signal path.

ALARM RELAY WIRING

If equipped, the alarm relay outputs are available on the NO, COM and NC terminals for each relay. The 

relay COM terminals are NOT connected to the signal or power supply COM terminal nor to each other. The 

two relays are completely isolated and have both Normally Open (NO) and Normally Closed (NC) contacts. 

These signals can be used to directly control alarms, ventilation fans or may be connected to digital inputs 

of the BAS for status monitoring. Ensure any loads connected to the relays are within the relay ratings in 

the Specification section.

 

Figure 4

Analog Input for 

4-20 mA CO Signal
24 Vac Power

Controller

CO

COM

PWR

250R

Com

Hot

Analog Input for 

0-5 Vdc CO Signal
24 Vdc Power

Controller

CO

COM

PWR

1M

Com

+

Wiring for 4-20 mA Output Signal

Wiring for 0-5 Vdc Output Signal

RELA

Y 1

NC

COM

NO

RELA

Y 2

COMM

LCD

ROLL

MENU

POWER

PCB

VOLT

mA

+

TEST

-

CO

COM

PWR

A-

B+

SHLD

NC

COM

NO

IN-GE-CMD5B5XXX-01-02     03/19

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for CMD5B5 Series

Page 1: ...ve feet from corners and other items that may cause disturbances in the air flow Avoid areas with vibrations or rapid temperature changes The duct CO detector principal of operation is based on the Venturi effect of the probe that extends into the HVAC duct Air flowing through the duct is forced into the vent holes on one side of the probe into the enclosure over the CO sensor and then is drawn ba...

Page 2: ...power is applied The current signal has a maximum load that it will drive and the voltage output has a minimum load Follow the ratings in the Specification section or inaccurate readings may result The power must be disconnected to change from VOLT to mA The analog output CO signal is typically connected directly to the Building Automation System BAS and used as a control parameter or for logging ...

Page 3: ...eset to Normal Mode when the CO level drops below the trip level hysteresis value In order to reset the relay alarms to Normal Mode the user must also press theTEST switch on the front cover or activate the remote TEST input If the CO level is below the alarm level AND the TEST switch is pressed then the relay alarms will return to the Normal Mode The Manual Reset also applies to the buzzer alarm ...

Page 4: ... device network address the installer MUST change the settings before operation Any changes made are saved in non volatile memory and are restored in case of a power loss Only the menu items relevant to the device model will be shown The menu can be accessed at any time after the warm up mode and if there is 5 minutes of inactivity the menu will close and normal operation will continue Note that t...

Page 5: ...used for Fail Safe operation as the relay will change state on power loss Press SAVE to save the setting Use the ROLL key to toggle relay 1 ON or OFF MENU Press to advance to next menu item MENU Press to advance to next menu item MENU Press to advance to next menu item 7 HYSTERESIS 8 DELAY 9 DIRECT 10 TEST Only if Relay 1 installed MENU Press to advance to next menu item Only if Relay 2 installed ...

Page 6: ...when the TEST switch is pressed Use the ROLL key to enable disable or reset When disabled the device will not sound the buzzer or provide LCD and status LED indication when the sensor life is exceeded When enabled the fault alarm will activate to indicate the sensor life is exceeded Press SAVE to save the setting If it is set to reset and SAVE is pressed then the fault condition is cleared the lif...

Page 7: ...he setting to either CO Value or Status When set to CO value the actual ppm value of the CO reading will be displayed on the LCD When set to Status the ppm value will not be displayed only the device operating status Press SAVE to save the setting Use the ROLL key to enable or disable the LCD backlight When enabled the backlight is always on and when disabled it never lights Press SAVE to save the...

Page 8: ... on the cover as before The sensor must be continuously powered for at least 1 2 hour prior to calibration Calibrate the sensor first in clean air with no CO gas present Simply adjust the ZERO pot on the sensor board until 4 mA or 0 Vdc output is obtained and the LCD displays 0 ppm Note that the 0 Filter menu item should be disabled to set the 0 ppm The ZERO and SPAN pots are located on the edge o...

Page 9: ...1 minute increments OPTIONAL RELAY Outputs Form C contacts NO and NC 5 Amps 250 Vac 5 Amps 30 Vdc Relay 1 Trip Point Programmable 20 to 500 ppm in 10 ppm increments Relay 2 Trip Point Programmable 20 to 500 ppm in 10 ppm increments Relay Hysteresis Programmable 10 to 100 ppm in 5 ppm increments Relay Delay Programmable 0 to 10 minutes in 1 minute increments GENERAL Measurement Electrochemical Samp...

Reviews: