background image

[6] Duct Smoke Detector Maintenance And Test Pro-
cedures
Test and maintain duct detectors as recommended in NFPA
72. The tests contained in this manual were devised to as-
sist maintenance personnel in verification of proper detector
operation.
Before conducting these tests, notify the proper authorities
that the smoke detection system will be temporarily out of
service. Disable the zone or system under test to prevent
unwanted alarms.
[6.1] Smoke Entry Tests
[6.1.1] Air Flow
To verify sufficient sampling of ducted air, use a manometer to
measure the differential pressure created from air flow across
the sampling tubes. The pressure should measure no less than
0.03 inches of water and no greater than 1.4 inches of water.
The air handler must be operating for this test.

[6.1.2] Smoke Response
To determine if smoke is capable of entering the sensing
chamber, visually identify any obstructions. Plug the ex-
haust and inlet tube holes to prevent ducted air from carrying
smoke away from the detector head, then blow smoke such
as cigarette, cotton wick, or punk directly at the head to
cause an alarm. REMEMBER TO REMOVE THE PLUGS
AFTER THIS TEST, OR THE DETECTOR WILL NOT FUNC-
TION PROPERLY.

[6.1.3] Filter Replacement
The filters do not substantially affect smoke performance
even when up to 90% of the filter is clogged. Quarterly visual
inspection usually suffices to determine whether the filters
should be replaced because only a high percentage of con-
tamination affects performance. If further testing is required,
compare differential pressure readings with and without the
filters installed. If the difference exceeds 10% replace the fil-
ters. In no case should the pressure differential fall below
0.03 inches of water.
[6.2] Standby, Alarm, And Sensitivity Tests
[6.2.1] Standby And Trouble

Standby — Look for the presence of the flashing green

LED through the transparent housing cover.
The LED should flash approximately every 10
seconds.

Trouble —

If the detector LED does not flash, then the
detector lacks power (check wiring, panel, or
power supply), the detector board is missing

(replace), or the unit is defective (return for re-
pair)

Test —

The trouble condition can be caused inten-
tionally to verify correct operation of the sys-
tem. Remove the detector board to cause a
trouble condition locally and at the system
control panel.

Cover
Tamper —

If the cover is removed for a period longer than
20 minutes, a trouble signal is generated to
indicate the cover is missing.

[6.2.2] Alarm Tests
[6.2.2.1] M02-04-00 Magnet Test

1. Place the painted surface of the magnet onto the TEST

locator on the bottom of the housing (Figure 11).

2. The red alarm LED on the detector should latch on, as

should any accessories (i.e. RA400Z, RTS451). Verify
system control panel alarm status and control panel ex-
ecution of all intended auxiliary functions (i.e. fan shut-
down, damper control, etc.).

3. The detector must be reset by system control panel, front

cover reset button, or remote accessory.

D100-68-00

5

I56-1525-000

Summary of Contents for DH100ACDCPA

Page 1: ...el interface alarm initiation HVAC control and other auxiliary functions Auxiliary relays are also provided for fan shut down or signaling of up to 9 other detectors in the loop for multiple fan shut down These detec For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm oc curs A ...

Page 2: ...s of 500 to 4000 feet per minute Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these pa rameters If necessary use a velocity meter to check the air velocity in the duct 5 2 Drill The Mounting Holes Remove the paper backing from the mounting template sup plied Affix the template to the duct at the desired mounting location Make sure the templat...

Page 3: ...dth All other lengths must be purchased sepa rately Order the correct length as specified in Table 1 for width of the duct where it will be installed The exhaust tube is molded onto the base of the duct housing and the A2440 00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not ex tend at least 2 inches into the duct The inlet tube is always i...

Page 4: ...mation Replacement filters can be ordered from Sys tem Sensor 6581 Kitimat Rd Unit 6 Mississauga Ontario L5N 3T5 Exhaust tube intake tube filter P N F36 09 00 5 6 Field Wiring Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction Proper wire gauges should be used The conductors used to connect smoke detec...

Page 5: ...filters should be replaced because only a high percentage of con tamination affects performance If further testing is required compare differential pressure readings with and without the filters installed If the difference exceeds 10 replace the fil ters In no case should the pressure differential fall below 0 03 inches of water 6 2 Standby Alarm And Sensitivity Tests 6 2 1 Standby And Trouble Sta...

Page 6: ...FORMATION FOR WIRING OF AUXILIARY DEVICES REFER TO MANUFACTURER S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER NOTE THE SUPERVISORY RELAY NOW PROVIDES A FORM C CONTACT FOR CUSTOMIZED APPLICATIONS FOR STANDARD APPLICATIONS ONLY THE NO CONTACT IS USED POWER INPUTS ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTO...

Page 7: ...ed with dirt replace them with new filters If they are not heavily coated use a vacuum cleaner or compressed air nozzle to remove dust then reinstall the filters 7 2 Photo Detector Boards 1 Remove the screen by gently grasping on each side and pulling straight off 2 Lift the photo chamber in the same fashion Vacuum the screen and cover Use clean compressed air to loosen and blow out any remaining ...

Page 8: ...cement 1 Disconnect wiring from the terminal block 2 Remove the two power board mounting screws 3 Pull gently on the board to remove it 4 To replace the board align the board mounting features holes and the interconnect terminals Push the board into place 5 Secure board with the two mounting screws 6 Re connect wiring to terminal block Power Supply Voltage 20 29 VDC 24 VAC 50 60 Hz 120 VAC 50 60 H...

Reviews: