6.9.4 Ripple Control Receiver (RCR) and RS485 Connections
1.
Remove sealing plug and twist off the cable gland (M25)
2.
Insert wires from rear of guidance and holes of rubber sealing (M25)
3.
Refer to Ch.8 on P.47 for proper RS485 connections
4.
Refer to Ch.9 on P.49 for proper RCR connections
5.
Connect RCR and RS485 wires as shown below
6.
Make sure RCR and RS485 wires are both wound through a grey EMI
core (from accessary kit) with 4 turns each, as for noise immunity
7.
Tighten cable gland to secure cables firmly in position
PV-5000T-U/PV-8000T-U/PV-10000T-U
PV-15000T-U/PV-20000T-U
PV-15000T-U/PV-20000T-U (E-Display)
Note on Wire Selection
To safely secure cable on terminal block, please use solid
wires. If stranded wires are used, apply core end terminals
supplied in accessories.