31
PV-15000T-U/PV-20000T-U (E-Display)
6.9.7 Closing the Front Cover
After connecting all wires, please
1.
Inspect all the connections again
2.
Close front cover and tighten 4 screws gently
3.
Check for any openings in between front cover and inverter
6.9.8 Applicable PV Modules
Only non-grounding PV panel is applicable, user is suggested to consult with a
system installer for PV panel type selection.
6.9.9 DC (PV) Wiring
1.
DC Input Ratings
Model
Rating
PV-5000T-U
PV-8000T-U
PV-10000T-U
PV-15000T-U
PV-20000T-U
Recommended
Max. DC Power (W)
5500
8800
11000
16500
22000
Max. DC (V)
980
980
980
980
980
Max. Current (A)
10
10/String
20 in Total
10/String
20 in Total
20 for
String 1
(Paralleled)
10 for
String 2
30 in Total
20/String
40 in Total
String(s)
1
2
2
2 (3 Inputs) 2 (4 Inputs)
Warning
Require PV modules that have IEC 61730 class A rating.
RS485 Cable for Internet