45
KEEP PV OFF
Internal capacitor(s) short
User must switch off PV immediately
C1
High DC current detected
C2
Relay failed
Error
Implication
C3
DC current sensor failed
C4
Internal temperature of inverter high
C5
GFCI detection failed
C6
Currently not used by system
C7
Anti-islanding (or AFD) failed
FAN FAILS
Internal or external cooling fan failed to work
Note on “KEEP PV OFF”
If this message shows up on screen, please turn off the DC
switch of PV immediately. DO NOT turn on again for any
reason. Call for service immediately.
Ground Fault Alarm
In addition to showing “GFCI HIGH“ on display, inverter will
activate audiable alarm of the optional buzzer and show
message on web page while using a computer to monitor.