background image

 

W:\ELECTRICAL\INSTRUCT\FURNACE\FURNACE GENERAL INSTRUCTIONS 2011.DOC 

17 of 36 

01/2014 

 

5-9

  For Tempering Furnaces, open the exhaust and fresh air dampers enough to prevent 

fouling of the work.  Where significant amounts of smoke or moisture are being driven 
off in the furnace process, it is necessary to exhaust enough air to remove this 
material.  Failure to provide sufficient ventilation may result in condensation of oil or 
solvent vapors inside furnace walls with a resulting risk of fire. 

 

5-9.1

  When the exhaust is increased, the fresh air intake must also be increased.  

Failure to do this will result in cold spots within the furnace, particularly around the 
door, since air will be drawn in past the gaskets.  When the fresh air intake damper 
is properly adjusted, there will be a slight leaking of hot air out of the door gaskets.  
The fresh air intake damper is located on the wall of the heat chamber. 

 

5-9.2

  Proper balance of the fresh air inlet and exhaust outlet are essential for uniform air 

temperature.  Room air entering the fresh air inlet expands when heated and 
pressurizes the work space forcing air out the exhaust or past the door gasket. Too 
much fresh air (or too little exhaust) can result in excessive leakage of hot air at the 
door seal. 

 

5-10

  Where furnaces are equipped with louvered ductwork, the louvers may be adjusted to 

give the best performance for your particular process.  The louvers were originally set 
at the factory in an empty furnace.  Loading of your parts may affect uniformity.  These 
louvers are not designed for frequent adjustment and should only be changed when 
absolutely necessary.  Louvers should be opened where the work space is cold and 
closed where it is hot. 

 

5-11

  Hot loads, tongs and other hot tools or fixtures such as shelves and loading trucks 

should be located in areas clearly marked to warn plant personnel of the potential 
danger of burns or fires caused by the hot parts. 

 

Summary of Contents for Furnaces

Page 1: ...X B REFERENCES 11 APPENDIX C MINIMUM PERIODIC MAINTENANCE REPORT 12 APPENDIX D SAFETY SHUT OFF VALVE LEAK TEST PROCEDURE 13 APPENDIX E WARRANTY AND LIMITATIONS OF REMEDIES Following these GENERAL INST...

Page 2: ...or damage which does not become apparent until the merchandise has been unpacked The contents may be damaged in transit due to rough handling even though the carton may not show external damage When...

Page 3: ...in in the furnace too long thereby encouraging combustion Using a furnace for a process other than that for which it was designed 2 1 4 Furnace operator should shut down the furnace immediately and no...

Page 4: ...ems in accordance with NFPA 11 Dry Chemical Extinguishing Systems in accordance with NFPA 17 Water Mist Systems in accordance with NFPA 750 The extent of protection required will depend upon the const...

Page 5: ...or electrical equipment with guards removed Operating with guards removed could result in bodily injury 2 4 8 Furnaces with vertical lift doors or top loading doors must be blocked open before passin...

Page 6: ...designed and manufactured in accordance with applicable National Codes in effect as of the date of manufacture It is the responsibility of the end user to update equipment as necessary to comply with...

Page 7: ...ations unless they are designed to comply with the applicable requirements of NFPA 70 ANational Electric Code see Appendix B 3 1 7 Equipment shall be protected from corrosive external processes and en...

Page 8: ...tion of combustible material combustible material shall be located at a safe distance from furnace and furnace ductwork The National Fire Protection Association NFPA Standard 86 specifies a minimum di...

Page 9: ...on to the building will require additional make up air to the building to prevent the building from operating under negative pressure Operating building under negative pressure will reduce exhaust rat...

Page 10: ...itable traps or other safe locations 3 5 10 Ducts handling combustible solids shall be designed to minimize the accumulation of solids within the ducts 3 5 11 Exhaust ducts that will contain combustib...

Page 11: ...fuel to be turned off in an emergency and shall be located so that fire or explosion at the furnace does not prevent access to this valve Operators should be instructed on the location of this valve a...

Page 12: ...ude a safety shut off such as a circuit breaker or fused disconnect switch between your power supply and the equipment 3 7 3 The furnace must be adequately grounded Grounding wire must be sized in acc...

Page 13: ...bove process may have to be repeated The following procedure must be followed prior to placing your furnace in operation After the furnace has been installed it is ready for initial dry out Before the...

Page 14: ...s that had been removed for shipment or installation At no time should equipment be operated if covers or guards are open removed or partially closed 4 5 When the equipment is placed in operation chec...

Page 15: ...tion 5 PROCESSING and Section 7 MAINTENANCE 4 11 1 Setpoints of all safety interlocks shall be documented for future reference 4 11 2 Supply piping shall be checked for leaks 4 11 3 Personnel operatin...

Page 16: ...it interlock should indicate in the same temperature units F or C as the main controller 5 5 An alarm should be installed that will sound upon the excess temperature limit interlock being activated Th...

Page 17: ...is located on the wall of the heat chamber 5 9 2 Proper balance of the fresh air inlet and exhaust outlet are essential for uniform air temperature Room air entering the fresh air inlet expands when...

Page 18: ...See Section 7 MAINTENANCE and Appendix C MINIMUM PERIODIC MAINTENANCE REPORT 6 4 Safety devices shall not be removed or rendered ineffective by bypassing them electrically or mechanically 6 5 Minimum...

Page 19: ...ation on the materials involved included elsewhere in this manual 7 3 Disconnect fuel electric power steam compressed air and any other energy source before servicing equipment Furnaces operate under...

Page 20: ...t surfaces duct work air inlets exhaust outlets filters control enclosures motors safety switches door latches and door hinges Care must be taken in cleaning any combustible build up to avoid creating...

Page 21: ...resistant grease is necessary 7 8 5 2 All bearings including those on blowers exhauster or conveyor system should be greased every six 6 months or 500 hours of operation with a good grade of machine g...

Page 22: ...element connections at terminals for tightness 7 8 9 Fuel Gas Furnaces 7 8 9 1 Check main safety shut off valves for leakage See Appendix D Main Safety Shutoff Valve Leak Test Procedure 7 7 9 2 Check...

Page 23: ...to make sure temperature controller calibration is correct 7 8 11 2 Heat furnace above setting of excess temperature limit interlock and make sure excess temperature limit interlock shuts down furnace...

Page 24: ...t in a reduced operating temperature In this case the furnace heater will be running continuously i e 100 output This can be corrected by closing the exhaust damper until the maximum operating tempera...

Page 25: ...INTERLOCK ACTUATION Depending upon the specific device used it may be tripped by either an excessively high furnace temperature or a sensing element failure Before placing the equipment back into oper...

Page 26: ...adequate safety ventilation and sometimes reversal of airflow in the exhaust stack c A record of fires or puffs from work in a particular furnace may indicate inadequate safety ventilation dangerously...

Page 27: ...tion which cannot be obtained with the main heating element contactors or SCR power controller alone The redundant separate contactors provide a second cutoff device to the heating elements which does...

Page 28: ...cally heated furnaces the circuit is opened to the heating element contactors or SCR power controller and separate contactors On gas fired equipment the control circuit is opened to the control and sa...

Page 29: ...limit interlock described previously except that the sensor is located in the heating element chamber or gas burner combustion chamber of the furnace This device will detect and be actuated when the...

Page 30: ...ation of Standpipe and Hose Systems NFPA 15 Standard for Water Spray Fixed Systems for Fire Protection NFPA 17 Standard for Dry Chemical Extinguishing Systems NFPA 17A Standard for Wet Chemical Exting...

Page 31: ...ent per batch or per hour at an operating temperature of ________ F 3 ____ All electrical connections are tight without stray strands 4 ____ All contactors relays motor starters and other components w...

Page 32: ...xhausters combustion blowers and other fans are rotating in the correct direction 23 ____ Check exhaust rate if it is critical for safe operation such as required for removing flammable solvents or co...

Page 33: ...mpare temperature controller indication and excess temperature limit interlock indication to confirm they are similar 45 ____ Disconnect one side of thermocouple connection to confirm upscale break pr...

Page 34: ...ng and must be replaced Do not continue to operate burner until valve is replaced 8 Close the test petcock A remove the 1 4 tube and replace the leak test tap plug B FIRST SAFETY SHUT OFF VALVE 1SSOV...

Page 35: ...k located between the pilot shut off solenoid valves and the burner SECOND SAFETY SHUT OFF VALVE 2SSOV 27 Turn on the Blower Gas cocks open and exhauster still running from step 17 and turn the HEAT s...

Page 36: ...r to obtain repair or replacement under this warranty the user must deliver the defective product or part to GRIEVE s factory on a prepaid basis promptly after discovery of the defect GRIEVE s warrant...

Reviews: