Installation and Operation Instruction
Figure 1
Figure 2
360º
Figure 3
The actuator types
FlowCon FNR.0.2
,
FNR.0.2-EQ
and
FNR.0.3
are electrical ac-
tuators. FNR.0.2 and FNR.0.2-EQ are both 24V
modulating and FNR.0.3 is 2-position / 3-point
floating.
Fitting and Re-fitting
Do not connect power to the actuator unless
the actuator is already fitted on the valve
and NEVER install the actuator in closed
position - this may damage the valve.
Actuator is supplied in open position to
ensure easy commissioning of the system.
Mount the actuator on the valve and finger
tighten the connection union. Do not use ad-
ditional tools. In case the actuator will have to
be removed, it is recommended to manually
open the actuator for easier removal. Hereaf-
ter finger loosen the connection union. Again,
no need for additional tools. Please make sure
that the actuator is manually opened, before re-
fitting it on the valve.
Orientation
Upside-down installation is allowed along with
the standard horizontal and vertical installation.
FlowCon FNR Actuators
1B95088 - 11/2020
This paper is a supplement to the
FlowCon General Instruction
Latest release of any FlowCon material is available on
Page 1 of 2
FlowCon International assumes no responsibility for mistakes, if any
, in any printed material.