P
AGE
22
OF
26
DGF100
reference
manual, rev 1, Feb 22, 2022
Ground
Fault
Systems
B.V.
8.3.3
Table 3c
- Current level 6 A
Trip Current Level set at 6 A
Trip Delay
setpoint
Delay when current exceeds trip current setting by a
factor of:
1,2
2
≥ 2,5
20 ms
57 -
90 ms 34 -
53 ms 24 -
46 ms
50 ms
87 - 120 ms 64 -
83 ms 54 -
76 ms
100 ms
137 - 170 ms 114 - 133 ms 104 - 126 ms
200 ms
237 - 270 ms 214 - 233 ms 204 - 226 ms
500 ms
531 - 581 ms 507 - 544 ms 498 - 537 ms
1000 ms
1031 - 1081 ms 1007 - 1044 ms 998 - 1037 ms
2000 ms
2031 - 2081 ms 2007 - 2044 ms 1998 - 2037 ms
5000 ms
4890 - 5081 ms 4867 - 5044 ms 4857 - 5037 ms
8.3.4
Table 3d
- Current level 9 A
Trip Current Level set at 9 A
Trip Delay
setpoint
Delay when current exceeds trip
current setting by a factor of:
1,2
≥ 1,7
20 ms
57 -
90 ms 33 -
55 ms
50 ms
87 - 120 ms 63 -
85 ms
100 ms
137 - 170 ms 113 - 135 ms
200 ms
237 - 270 ms 213 - 235 ms
500 ms
531 - 581 ms 507 - 546 ms
1000 ms
1031 - 1081 ms 1007 - 1046 ms
2000 ms
2031 - 2081 ms 2007 - 2046 ms
5000 ms
4890 – 5081 ms 4866-5046 ms