2
1
1
Introduction
This inverter can be used in parallel with maximum 3 units. The supported maximum
output power is 30KW/30KVA.
When installing multiple units, please follow below chart.
NOTE:
of approx. 20 cm to the side and approx. 50 cm above and below the unit. Be sure to
install each unit in the same level.
For proper air circulation to dissipate heat, it’s necessary to allow a clearance
WARNING:
be voltage difference between inverter and battery to cause parallel inverters not
working.
Be sure the length of all battery cables is the same. Otherwise, there will
Recommended battery cable and terminal size for each inverter:
2 Parallel cable
3 Overview
You will find the following items in the package:
Parallel communication cable
Current sharing cable
1.Parallel communication port
2.Current sharing port
4 Mounting the Unit
5
Wiring Connection
The cable size of each inverter is shown as below:
Ring terminal:
Model
Wire Size
Ring Terminal
Torque value
Cable mm2
Dimensions
D (mm)
L (mm)
Growatt 10000HYP
3/0
85
8.4
54.2
7~12 Nm