background image

2

1

1

 

Introduction

This inverter can be used in parallel with maximum 3 units. The supported maximum 
output power is 30KW/30KVA.

When installing multiple units, please follow below chart. 

NOTE:
of approx. 20 cm to the side and approx. 50 cm above and below the unit. Be sure to 
install each unit in the same level.

 For proper air circulation to dissipate heat, it’s necessary to allow a clearance 

WARNING:
be  voltage  difference  between  inverter  and  battery  to  cause  parallel  inverters  not 
working. 

 Be sure the length of all battery cables is the same. Otherwise, there will 

Recommended battery cable and terminal size for each inverter:

2 Parallel cable

3 Overview

You will find the following items in the package:

 

Parallel communication cable                 

Current sharing cable

1.Parallel communication port

2.Current sharing port

4 Mounting the Unit 

5

 

Wiring Connection

The cable size of each inverter is shown as below:

Ring terminal:

Model

Wire Size

Ring Terminal

Torque value

Cable mm2

Dimensions

D (mm)

L (mm)

Growatt 10000HYP

3/0

85

8.4

54.2

7~12 Nm

Summary of Contents for 10000HYP

Page 1: ...W ENERGY TECHNOLOGY Co LTD 86 755 2747 1900 86 755 2747 2131 info ginverter com www ginverter com T F E W No 28 Guangming Road Shiyan Baoan District Shenzhen P R China Growatt 10000HYP Parallel Installation Guide ...

Page 2: ...erence between inverter and battery to cause parallel inverters not working Be sure the length of all battery cables is the same Otherwise there will Recommended battery cable and terminal size for each inverter 2 Parallel cable 3 Overview You will find the following items in the package Parallel communication cable Current sharing cable 1 Parallel communication port 2 Current sharing port 4 Mount...

Page 3: ...0 mm2 1 4 1 6Nm Recommended breaker specification of battery for each inverter If you want to use only one breaker at the battery side for the whole system the rating of the breaker should be X times current of one unit X indicates the number of inverters connected in parallel Model One unit Growatt 10000HYP 300A 60VDC Recommended battery capacity CAUTION to choose the suitable battery The wrong c...

Page 4: ...centralized monitoring system Then you can use SYNC function to set all the inverters at the same time If using SNMP or Modbus card to set up program the bundled software is SolarPower Pro Use SNMP card to synchronize the parameters Each inverter should be installed one SNMP card Make sure all of the SNMP cards are connected to the router as a LAN Use Modbus card to synchronize the parameters Each...

Page 5: ...to click button before clicking button There is a Sync button in each parameter setting When Sync is clicked and Apply is pressed this new setting will be applied to all inverters If not this setting is only effected in current inverter you choose Note Without centralized monitoring system Sync function is not effective Then you have to set up the inverter one by one through serial communication p...

Page 6: ...o utility at the same time If not it will display fault 82 in following order inverters However these inverters will automatically restart If detecting AC connection they will work normally Fault Code Fault Event Icon on Over current on Neutral wire Power feedback protection 37 60 Relay board driver loss 61 Relay board communication loss Firmware version inconsistent Current sharing fault CAN faul...

Page 7: ...n cables are connected well and restart the inverter 2 If the problem remains please contact your installer 1 Disconnect all of power source 2 Only connect AC input and press Enter key to let it working in bypass mode 3 Check if the problem happens again or not and feed back the result to your installer 1 Update all inverter firmware to the same version 2 After updating if the problem still remain...

Reviews: