Recommended AC input and output cable size for each inverter:

You need to connect the cables of each inverter together. Take the battery cables for 

example.  You  need  to  use  a  connector  or  bus-bar  as  a  joint  to  connect  the  battery 

cables together, and then connect to the battery terminal. The cable size used from 

joint  to  battery  should  be  X  times  cable  size  in  the  tables  above.  “X”  indicates  the 

number of inverters connected in parallel.
Regarding cable size of AC input and output, please also follow the same principle.

CAUTION!!

can  be  securely  disconnected  during  maintenance  and  fully  protected  from 

overcurrent of battery. 

 Please install a breaker at the battery side. This will ensure the inverter 

Model 

AWG no.

Conductor cross
-section

Torque

Growatt 10000HYP

10~8 AWG

5.5~10 mm2

1.4~1.6Nm

Recommended breaker specification of battery for each inverter:

*

If  you  want  to  use  only  one  breaker  at  the  battery  side  for  the  whole  system,  the 

rating of the breaker should be X times current of one unit. “X” indicates the number 

of inverters connected in parallel.

Model 

One unit*

Growatt 10000HYP

300A/60VDC

Recommended battery capacity 

CAUTION!

to  choose  the  suitable  battery.  The  wrong  charging  parameters  will  reduce  the 

battery lifecycle sharply.

 Please follow the battery charging current and voltage from battery spec 

Inverter parallel numbers

2

3

Battery Capacity

800AH 1200AH

Approximate back-up time table

PV Connection 
Please refer to user manual of single unit for PV Connection.
CAUTION: Each inverter should connect to PV modules separately.  

Load (W)

10,000

20,000

5,000

15,000

25,000

30,000

Backup Time @ 48Vdc 
800Ah (min)

112

40

240

60

20

13

Backup Time @ 48Vdc 
1200Ah (min)

168

60

360

90

30

20

6 Inverters Configuration

Two inverters in parallel:

Power Connection

Summary of Contents for 10000HYP

Page 1: ...W ENERGY TECHNOLOGY Co LTD 86 755 2747 1900 86 755 2747 2131 info ginverter com www ginverter com T F E W No 28 Guangming Road Shiyan Baoan District Shenzhen P R China Growatt 10000HYP Parallel Installation Guide ...

Page 2: ...erence between inverter and battery to cause parallel inverters not working Be sure the length of all battery cables is the same Otherwise there will Recommended battery cable and terminal size for each inverter 2 Parallel cable 3 Overview You will find the following items in the package Parallel communication cable Current sharing cable 1 Parallel communication port 2 Current sharing port 4 Mount...

Page 3: ...0 mm2 1 4 1 6Nm Recommended breaker specification of battery for each inverter If you want to use only one breaker at the battery side for the whole system the rating of the breaker should be X times current of one unit X indicates the number of inverters connected in parallel Model One unit Growatt 10000HYP 300A 60VDC Recommended battery capacity CAUTION to choose the suitable battery The wrong c...

Page 4: ...centralized monitoring system Then you can use SYNC function to set all the inverters at the same time If using SNMP or Modbus card to set up program the bundled software is SolarPower Pro Use SNMP card to synchronize the parameters Each inverter should be installed one SNMP card Make sure all of the SNMP cards are connected to the router as a LAN Use Modbus card to synchronize the parameters Each...

Page 5: ...to click button before clicking button There is a Sync button in each parameter setting When Sync is clicked and Apply is pressed this new setting will be applied to all inverters If not this setting is only effected in current inverter you choose Note Without centralized monitoring system Sync function is not effective Then you have to set up the inverter one by one through serial communication p...

Page 6: ...o utility at the same time If not it will display fault 82 in following order inverters However these inverters will automatically restart If detecting AC connection they will work normally Fault Code Fault Event Icon on Over current on Neutral wire Power feedback protection 37 60 Relay board driver loss 61 Relay board communication loss Firmware version inconsistent Current sharing fault CAN faul...

Page 7: ...n cables are connected well and restart the inverter 2 If the problem remains please contact your installer 1 Disconnect all of power source 2 Only connect AC input and press Enter key to let it working in bypass mode 3 Check if the problem happens again or not and feed back the result to your installer 1 Update all inverter firmware to the same version 2 After updating if the problem still remain...