9 Trouble shooting

Situation

Fault Code Fault Event Description

Solution

Relay board driver loss

CAN data loss

Host data loss

Current feedback into 
the inverter is detected.

1.Restart the inverter.
2.Check if L1/L2/L3/N cables are not 
connected with wrong sequence in all 
inverters.
3.Make sure the sharing cables are connected 
in all inverters.
4.If the problem remains, please contact your 
installer.

1.Check if sharing cables are connected well 
and restart the inverter.
2.If the problem remains, please contact your 
installer.

1.Check if communication cables are 
connected well and restart the inverter.
2.If the problem remains, please contact your 
installer.

1.Disconnect all of power source.
2.Only connect AC input, and press Enter key 
to let it working in bypass mode.
3.Check if the problem happens again or not, 
and feed back the result to your installer.

1.Update all inverter firmware to the same 
version.
2.After updating, if the problem still remains, 
please contact your installer.

Relay board 

communication loss

The firmware version of 

each inverter is not the 

same.

The output current of 
each inverter is 
different.

Synchronization data 

loss

60

61

62

71

72

1.Remove excessive loads.
2.Restart the inverter.

3.If the problem remains, please contact your 

installer.

Over current on Neutral 

wire

37

80

81

82

Summary of Contents for 10000HYP

Page 1: ...W ENERGY TECHNOLOGY Co LTD 86 755 2747 1900 86 755 2747 2131 info ginverter com www ginverter com T F E W No 28 Guangming Road Shiyan Baoan District Shenzhen P R China Growatt 10000HYP Parallel Installation Guide ...

Page 2: ...erence between inverter and battery to cause parallel inverters not working Be sure the length of all battery cables is the same Otherwise there will Recommended battery cable and terminal size for each inverter 2 Parallel cable 3 Overview You will find the following items in the package Parallel communication cable Current sharing cable 1 Parallel communication port 2 Current sharing port 4 Mount...

Page 3: ...0 mm2 1 4 1 6Nm Recommended breaker specification of battery for each inverter If you want to use only one breaker at the battery side for the whole system the rating of the breaker should be X times current of one unit X indicates the number of inverters connected in parallel Model One unit Growatt 10000HYP 300A 60VDC Recommended battery capacity CAUTION to choose the suitable battery The wrong c...

Page 4: ...centralized monitoring system Then you can use SYNC function to set all the inverters at the same time If using SNMP or Modbus card to set up program the bundled software is SolarPower Pro Use SNMP card to synchronize the parameters Each inverter should be installed one SNMP card Make sure all of the SNMP cards are connected to the router as a LAN Use Modbus card to synchronize the parameters Each...

Page 5: ...to click button before clicking button There is a Sync button in each parameter setting When Sync is clicked and Apply is pressed this new setting will be applied to all inverters If not this setting is only effected in current inverter you choose Note Without centralized monitoring system Sync function is not effective Then you have to set up the inverter one by one through serial communication p...

Page 6: ...o utility at the same time If not it will display fault 82 in following order inverters However these inverters will automatically restart If detecting AC connection they will work normally Fault Code Fault Event Icon on Over current on Neutral wire Power feedback protection 37 60 Relay board driver loss 61 Relay board communication loss Firmware version inconsistent Current sharing fault CAN faul...

Page 7: ...n cables are connected well and restart the inverter 2 If the problem remains please contact your installer 1 Disconnect all of power source 2 Only connect AC input and press Enter key to let it working in bypass mode 3 Check if the problem happens again or not and feed back the result to your installer 1 Update all inverter firmware to the same version 2 After updating if the problem still remain...

Reviews: